See other bills
under the
same topic
                                                      PRINTER'S NO. 2136

THE GENERAL ASSEMBLY OF PENNSYLVANIA


SENATE BILL

No. 1349 Session of 2006


        INTRODUCED BY REGOLA AND D. WHITE, OCTOBER 11, 2006

        REFERRED TO ENVIRONMENTAL RESOURCES AND ENERGY, OCTOBER 11, 2006


                                     AN ACT

     1  Reenacting and amending the former act of December 15, 1980
     2     (P.L.1203, No.222), entitled "An act providing for the
     3     regulation for energy conservation purposes of the
     4     construction of buildings, the establishment of a Building
     5     Energy Conservation Committee and a Board on Variances,
     6     appeals and for penalties," restoring the act to the state in
     7     which it existed prior to repeal by the Pennsylvania
     8     Construction Code Act.

     9     The General Assembly of the Commonwealth of Pennsylvania
    10  hereby enacts as follows:
    11     Section 1.  The title, the heading of Chapter 1 and section
    12  101 of the act of December 15, 1980 (P.L.1203, No.222), entitled
    13  "An act providing for the regulation for energy conservation
    14  purposes of the construction of buildings, the establishment of
    15  a Building Energy Conservation Committee and a Board on
    16  Variances, appeals and for penalties," repealed November 10,
    17  1999 (P.L.491, No.45), are reenacted to read:
    18                               AN ACT
    19  Providing for the regulation for energy conservation purposes of
    20     the construction of buildings, the establishment of a


     1     Building Energy Conservation Committee and a Board on
     2     Variances, appeals and for penalties.
     3                             CHAPTER 1
     4                         GENERAL PROVISIONS
     5  Section 101.  Short title.
     6     This act shall be known and may be cited as the "Building
     7  Energy Conservation Act."
     8     Section 2.  Sections 102 and 103 of the act, amended December
     9  19, 1985 (P.L.344, No.98) and repealed November 10, 1999
    10  (P.L.491, No.45), are reenacted and amended to read:
    11  Section 102.  Legislative findings and declaration of purpose.
    12     (a)  Findings.--The Legislature hereby determines that:
    13         (1)  Energy shortages in the domestic supply present far-
    14     reaching problems that promise to persist. These energy
    15     shortages affect the continued efficient operation of the
    16     Commonwealth's economy and social structure.
    17         (2)  It is the Commonwealth's responsibility to provide
    18     for energy conservation through regulation of design and
    19     construction standards.
    20         (3)  The Legislature intends, by this act, to respond to
    21     these shortages by devising a specific responsible energy
    22     conservation policy for building systems.
    23     (b)  Purpose.--The purpose of this act is to grant to the
    24  Department of Labor and Industry and the Department of Community
    25  [Affairs] and Economic Development and direct these departments
    26  to exercise specific authority in building construction to
    27  assure that such construction is performed using materials and
    28  techniques that will provide for energy conservation in the
    29  future operation and maintenance of said buildings.
    30  Section 103.  Definitions.
    20060S1349B2136                  - 2 -     

     1     The following words and phrases when used in this act shall
     2  have, unless the context clearly indicates otherwise, the
     3  meanings given to them in this section:
     4     "Addition."  Any addition to an existing building. The
     5  provisions of this act shall only apply to the portion of the
     6  building which is being added and not to the entire building.
     7     "Building."  Any structure that provides facilities or
     8  shelter for public assembly or for educational, business,
     9  mercantile, institutional, warehouse or residential occupancy,
    10  or industrial use including, but not limited to, those portions
    11  of factory and industrial occupancy such as office space except
    12  for:
    13         (1)  Buildings and structures or portions thereof whose
    14     peak design rate of energy usage is less than one watt per
    15     square foot or 3.5 BTU/hr per square foot of floor area for
    16     all purposes.
    17         (2)  Structures or those portions of structures used for
    18     housing equipment or machinery, or in which manufacturing or
    19     processing is done, where the operation of such equipment or
    20     machinery, or the manufacturing or processing procedures
    21     employed require the use of or generate substantial heat
    22     producing energy or cooling within the structure. As used
    23     herein, the generation of substantial heat shall mean
    24     generation of more than 6 watts per square foot of floor
    25     area.
    26         (3)  Buildings which are neither heated nor cooled.
    27         (4)  Historic buildings.
    28         (5)  Buildings owned by the Federal Government.
    29         (6)  All units subject to the act of May 11, 1972
    30     (P.L.286, No.70), known as the "Industrialized Housing Act."
    20060S1349B2136                  - 3 -     

     1         (7)  All units subject to Title VI (Public Law 93-383),
     2     referred to as the Federal Mobile Home Construction and
     3     Safety Standards Act of 1974.
     4         (8)  Buildings which are constructed primarily of tree
     5  logs and only incidentally of other materials.
     6     "Construction."  The erection, fabrication or renovation of a
     7  building.
     8     "Department."  The Pennsylvania Department of Labor and
     9  Industry except that for all buildings classified as Use Group
    10  R-3, herein, department means the Pennsylvania Department of
    11  Community [Affairs] and Economic Development.
    12     "Design."  Calculations and resultant drawings and
    13  specifications which are used for the construction of a
    14  building.
    15     "Historic building."  Any building determined by the State
    16  Historic Preservation Officer to meet the criteria for listing
    17  on the National Register of Historic Places but only to the
    18  extent that compliance with this act would prevent preservation
    19  of the historic or architectural integrity of the building.
    20     "Licensed design professional."  A person licensed as an
    21  architect or professional engineer pursuant to the appropriate
    22  licensure act.
    23     "Life-cycle cost."  The cost of a building including its
    24  initial cost, the cost of the energy consumed over its economic
    25  life and the cost of its operation and maintenance.
    26     "Municipality."  A city, borough, incorporated town, township
    27  or home rule municipality.
    28     "Performance standards."  Parameters within which designers
    29  of buildings shall work. The specific practices that a designer
    30  employs shall not be prescribed as long as the result is within
    20060S1349B2136                  - 4 -     

     1  the parameters established by the standards.
     2     "Public utility."  A person or corporation in this
     3  Commonwealth owning or operating equipment or facilities for
     4  producing, generating, transmitting, distributing or furnishing
     5  electricity to or for the public for compensation for any
     6  purpose. The term includes such persons or corporations
     7  regulated by the Pennsylvania Public Utility Commission under
     8  Title 66 of the Pennsylvania Consolidated Statutes (relating to
     9  public utilities), but does not include any of the following:
    10         (1)  A generator or producer of electricity not engaged
    11     in distributing the electricity directly to the public for
    12     compensation.
    13         (2)  A person not otherwise a public utility who
    14     furnishes service only to himself.
    15         (3)  A bona fide cooperative association which furnishes
    16     services only to its stockholders or members on a nonprofit
    17     basis.
    18     "Renovation."  The rehabilitation of an existing building
    19  which requires more than 25% of the gross floor area or volume
    20  of the entire building to be rebuilt. Cosmetic work such as
    21  painting, wall covering, wall paneling, floor covering and
    22  suspended ceiling work shall not be included. The provisions of
    23  this act shall only apply to such portion of the building being
    24  renovated and not to the entire building.
    25     "Utility provider."  A municipal corporation in this
    26  Commonwealth owning or operating equipment or facilities for
    27  producing, generating, transmitting, distributing or furnishing
    28  electricity to or for the public within its corporate limits for
    29  compensation for any purpose, or an electric cooperative
    30  corporation created under the provisions of the act of June 21,
    20060S1349B2136                  - 5 -     

     1  1937 (P.L.1969, No.389), known as the "Electric Cooperative
     2  Corporation Act," and which provides retail electric service to
     3  its members on a nonprofit basis. The term does not include:
     4         (1)  A public utility regulated by the Pennsylvania
     5     Public Utility Commission under Title 66 of the Pennsylvania
     6     Consolidated Statutes (relating to public utilities).
     7         (2)  A generator, producer or manufacturer of
     8     electricity, gas or steam not engaged in distributing such
     9     electricity, gas or steam directly to the public for
    10     compensation.
    11         (3)  A person or corporation not otherwise a public
    12     utility who or which furnishes service only to himself or
    13     itself.
    14         (4)  A generator, producer or manufacturer of gas or
    15     steam engaged in distributing such gas or steam to the public
    16     for compensation.
    17     Section 3.  Chapter 2 heading, Subchapters A, B, C and D,
    18  Subchapter E heading and sections 209, 210, 211, 212, 213, 214
    19  215, 216, 217, 218, 219, 220, 221, 222 and 223 of the act,
    20  repealed November 10, 1999 (P.L.491, No.45), are reenacted to
    21  read:
    22                             CHAPTER 2
    23                   ENERGY CONSERVATION STANDARDS
    24                            SUBCHAPTER A
    25                         GENERAL PROVISIONS
    26  Section 201.  Provisions.
    27     The provisions of this chapter regulate the design and
    28  construction of the exterior envelopes and selection of HVAC,
    29  service water heating, electrical distribution, and illumination
    30  systems and equipment required for the purpose of effective use
    20060S1349B2136                  - 6 -     

     1  of energy and shall govern the construction of all buildings, or
     2  portions thereof, as provided herein other than a building
     3  classified as Use Group R-3 except where specifically noted
     4  otherwise. Minimum insulation requirements for buildings
     5  classified as Use Group R-3 are contained in Subchapter J,
     6  section 240.
     7                            SUBCHAPTER B
     8                      PLANS AND SPECIFICATIONS
     9  Section 202.  Submission.
    10     (a)  Plans.--Plans, specifications, computations where
    11  necessary, and any changes thereto together with the necessary
    12  certification required by section 305 shall be submitted for all
    13  buildings except those classified as Use Group R-3 to indicate
    14  conformance with this chapter and other applicable chapters of
    15  this act, except as provided in subsections (b) and (c).
    16     (b)  Standard design.--Whenever a person is constructing a
    17  building in accordance with plans, specifications and
    18  computations which he has submitted within the previous two
    19  years, such plans need not be resubmitted but such person shall
    20  indicate upon the certificate required by section 305 that they
    21  meet the standards currently in effect and identify the
    22  previously submitted plans, specifications and computations.
    23     (c)  Prescriptive standards.--When the prescriptive standards
    24  provided in the Energy Conservation Manual established by
    25  section 303 are employed in the construction of a building only
    26  such information as shall be required by the department shall be
    27  submitted. The prescriptive standards applicable to Use Group R-
    28  3 buildings are contained in section 240.
    29  Section 203.  Contents.
    30     The plans and specifications, where required by section 202,
    20060S1349B2136                  - 7 -     

     1  shall show in sufficient detail all pertinent data and features
     2  of the building and the equipment and systems as herein
     3  governed, including but not limited to: exterior envelope
     4  component materials, U values of elements, R values of
     5  insulating materials, size and type of apparatus and equipment,
     6  equipment and system controls and other pertinent data to
     7  indicate conformance with the requirements herein.
     8                            SUBCHAPTER C
     9                      DEFINITIONS RELATING TO
    10                   ENERGY CONSERVATION STANDARDS
    11  Section 204.  Definitions relating to standards.
    12     The following words and phrases when used in this chapter
    13  shall have, unless the context clearly indicates otherwise, the
    14  meanings given to them in this section:
    15     "Coefficient of beam utilization" (CBU).  The ratio of the
    16  luminous flux (lumens) reaching a specified area directly from a
    17  floodlight or projector to the total beam luminous flux.
    18     "Coefficient of performance" (COP) - cooling.  The ratio of
    19  the rate of net heat removal to the rate of total energy input,
    20  expressed in consistent units and under designated rating
    21  conditions.
    22     "Coefficient of performance" (COP) - heat pump, heating.  The
    23  ratio of the rate of net heat output to the rate of total energy
    24  input, expressed in consistent units and under designated rating
    25  conditions.
    26     The rate of net heat output shall be defined as the change in
    27  the total heat contents of the air entering and leaving the
    28  equipment not including supplementary heat.
    29     Total energy input shall be determined by combining the
    30  energy inputs to all elements, except supplementary heaters, of
    20060S1349B2136                  - 8 -     

     1  the heat pump, including, but not limited to, compressors,
     2  pumps, supply air fans, return air fans, outdoor air fans,
     3  cooling tower fans and the heating, ventilating and air
     4  conditioning system equipment control circuit.
     5     "Coefficient of utilization" (CU).  The ratio of the luminous
     6  flux (lumens) from a luminaire received on the work plane to the
     7  lumens emitted by the luminaire's lamps alone.
     8     "Color rendition."  General expression for the effect of a
     9  light source on the color. Appearance of objects in conscious or
    10  subconscious comparison with their color appearance under a
    11  reference light source.
    12     "Degree day, heating."  A unit, based upon temperature
    13  difference and time, used in estimating fuel consumption and
    14  specifying nominal heating load of a building in winter. For any
    15  one day, when the mean temperature is less than 65 F., there
    16  exist as many degree days as there are Fahrenheit degrees
    17  difference in temperature between the mean temperature for the
    18  day and 65 F.
    19     "Energy efficiency ratio" (EER).  The ratio of net cooling
    20  capacity in Btuh to total rate of electric input in watts under
    21  designated operating conditions.
    22     "Equivalent sphere illumination" (ESI).  The level of sphere
    23  illumination which would produce task visibility equivalent to
    24  that produced by a specific lighting environment.
    25     "Exterior envelope."  The elements of a building which
    26  enclose conditioned spaces through which thermal energy may be
    27  transferred to or from the exterior.
    28     "Floodlighting."  A lighting system designated to light an
    29  area using projector type luminaires usually capable of being
    30  pointed in any direction.
    20060S1349B2136                  - 9 -     

     1     "Floor area, gross."  Gross floor area shall be the floor
     2  area within the perimeter of the outside walls of the building
     3  under consideration, without deduction for hallways, stairs,
     4  closets, thickness of walls, columns or other features.
     5     "Illumination."  The density of the luminous flux incident on
     6  a surface. It is the quotient of the luminous flux by the area
     7  of the surface when the latter is uniformly illuminated.
     8     "Light loss factor" (LLF).  A factor used in calculating the
     9  level of illumination after a given period of time and under
    10  given conditions. It takes into account temperature and voltage
    11  variations, dirt accumulation on luminaire and room surfaces,
    12  lamp depreciation, maintenance procedures and atmosphere
    13  conditions.
    14     "Luminaire."  A complete lighting unit consisting of a lamp
    15  or lamps together with the parts designed to distribute the
    16  light, to position and protect the lamps and to connect the
    17  lamps to the power supply.
    18     "Multiglazing."  An arrangement whereby two or more sheets of
    19  glazing material are affixed in or on to a window frame to
    20  create one or more closed insulating air spaces. Multiglazing
    21  can be achieved by installing a preassembled sealed insulating
    22  glass unit, consisting of two or more layers of glazing
    23  materials with insulating, closed air space in between, or by
    24  affixing one or more additional glazing materials onto a single
    25  glazed window sash, creating one or more closed insulating air
    26  spaces.
    27     "Packaged terminal air conditioner."  A factory selected
    28  combination of heating and cooling components, assemblies or
    29  sections, intended to serve a room or zone.
    30     "Power."  In connection with machines, power is the time rate
    20060S1349B2136                 - 10 -     

     1  of doing work. In connection with the transmission of energy of
     2  all types, power refers to the rate at which energy is
     3  transmitted; in customary units, it is measured in watts (W) or
     4  British thermal units per hour (Btuh) and in SI units is
     5  measured in watts (W).
     6     "Reflectance."  The ratio of the light reflected by a surface
     7  to the light falling upon it.
     8     "Reheat."  The application of sensible heat to supply air
     9  that has been previously cooled below the temperature of the
    10  conditioned space by either mechanical refrigeration or the
    11  introduction of outdoor air to provide cooling.
    12     "Residential buildings."  All buildings and structures or
    13  parts thereof shall be classified in the residential (R) use
    14  group in which families or households live, or in which sleeping
    15  accommodations are provided for individuals with or without
    16  dining facilities, excluding those that are classified as
    17  institutional buildings. Residential buildings shall be
    18  classified as follows:
    19     (1)  Use Group R-1 structures.  This use group shall include
    20  all hotel and motel buildings, lodging houses, boarding houses
    21  and dormitory buildings arranged for the shelter and sleeping
    22  accommodation of more than 20 individuals.
    23     (2)  Use Group R-2 structures.  This use group shall include
    24  all multiple-family dwellings having more than two dwelling
    25  units and not included in Use Group R-3; and shall also include
    26  all dormitories, boarding and lodging houses arranged for
    27  shelter and sleeping accommodation by more than five and not
    28  more than 20 individuals.
    29     (3)  Use Group R-3 structures.  This use group shall include
    30  all buildings arranged for the use of one or two family dwelling
    20060S1349B2136                 - 11 -     

     1  units including not more than five lodgers or boarders per
     2  family and all rowhouses, townhouses and garden apartment
     3  construction not exceeding three stories in height used for
     4  residential purposes whenever each unit has its own individual
     5  and self-supporting heating, ventilating and air conditioning
     6  systems.
     7     "Resistance, thermal" (R).  A measure of the ability to
     8  retard the flow of heat. The R value is the reciprocal of a heat
     9  transfer coefficient, as expressed by U. (R = 1/U).
    10     "Thermal transmittance" (U).  Overall coefficient of heat
    11  transmission or thermal transmittance (air to air) expressed in
    12  units of BTU per hour per square foot per degree F. It is the
    13  time rate of heat flow. The U value applies to combinations of
    14  different materials used in series along the heat flow path and
    15  also to single materials that comprise a building section and
    16  include cavity air spaces and surface air films on both sides.
    17     "Thermal transmittance" (Uo).  Overall (average) heat
    18  transmission or thermal transmittance of a gross area of the
    19  exterior building envelope, expressed in units of BTU per hour
    20  per square foot per degree F.
    21     The Uo value applies to the combined effect of the time rate
    22  of heat flows through the various parallel paths, such as
    23  windows, doors and opaque construction areas, comprising the
    24  gross area of one or more exterior building components, such as
    25  walls, floor or roof/ceiling.
    26     "Thermostat."  An instrument which measures changes in
    27  temperature and controls devices for maintaining a desired
    28  temperature.
    29     "Veiling reflections."  Regular reflections superimposed upon
    30  diffuse reflections from an object that partially or totally
    20060S1349B2136                 - 12 -     

     1  obscure the details to be seen by reducing the contrast. This
     2  sometimes is called "reflected glare."
     3     "Window management."  Any one or combination of acts and
     4  activities whose purpose is to take maximum advantage of the
     5  energy conserving aspects of utilizing solar energy to heat a
     6  building and/or utilize solar illumination within a building to
     7  augment energy-consuming lighting systems. Such acts and
     8  activities include, but are not limited to, building-window
     9  siting and orientation, selection of glazing materials, design
    10  of overhangs, sun screens or placement of shrubbery.
    11     "Work plane."  The plane at which work usually is done and at
    12  which the illumination is specified and measured. Unless
    13  otherwise indicated, this is assumed to be a horizontal plane 30
    14  in. (0.76 m) above the floor.
    15     "Zone."  A space or group of spaces within a building with
    16  heating or cooling requirements sufficiently similar so that
    17  comfort conditions can be maintained throughout by a single
    18  controlling device.
    19                            SUBCHAPTER D
    20                         BUILDING ENVELOPE
    21  Section 205.  General provisions.
    22     (a)  Purpose of subchapter.--The intent of this subchapter is
    23  to provide minimum requirements for exterior envelope
    24  construction in the interest of energy conservation.
    25     In addition to the criteria set forth in this subchapter
    26  provisions shall be made to maximize the energy conserving
    27  benefits of solar daylight and passive solar heat gain through
    28  window management. The proposed design may also take into
    29  consideration the thermal mass of the building in considering
    30  energy conservation. The administering agency shall provide the
    20060S1349B2136                 - 13 -     

     1  guidelines necessary to implement these provisions.
     2     (b)  Thermal performance.--All buildings and structures that
     3  are heated or mechanically cooled shall be constructed so as to
     4  provide the required thermal performance of the various
     5  components.
     6     The required thermal transmittance value (Uo) of any one
     7  component, such as roof/ceiling, wall or floor may be increased
     8  and the Uo value for other components decreased provided that
     9  the overall heat gain or loss for the entire building envelope
    10  does not exceed the total resulting from conformance to the
    11  required Uo values.
    12     (c)  Different requirements.--
    13         (1)  A building that is designed to be both heated and
    14     cooled shall meet the more stringent of the heating or
    15     cooling requirements of the exterior envelope as provided in
    16     this subchapter when requirements differ.
    17         (2)  A building which is not cooled whose primary purpose
    18     is storage and has an indoor design temperature of 50 degrees
    19     F. or less, the building is exempt from the requirements of
    20     this subchapter.
    21     (d)  Exterior walls.--For the purpose of this subchapter the
    22  gross area of exterior walls consists of all opaque wall areas,
    23  including foundation walls above grade, peripheral edges of
    24  floors, window areas including sash, and door areas, where such
    25  surfaces are exposed to outdoor air and enclose a heated or
    26  mechanically cooled space.
    27     (e)  Roof assembly.--For the purpose of this subchapter a
    28  roof assembly shall be considered as all components of the
    29  roof/ceiling envelope through which heat flows, thereby creating
    30  a building transmission heat loss or gain, where such assembly
    20060S1349B2136                 - 14 -     

     1  is exposed to outdoor air and encloses a heated or mechanically
     2  cooled space.
     3     The gross area of a roof assembly consists of the total
     4  interior surface of such assembly, including skylights, exposed
     5  to the heated or mechanically cooled space.
     6     Where air ceiling plenums are employed, the roof or ceiling
     7  assembly shall:
     8         (1)  For thermal transmittance purposes not include the
     9     ceiling proper nor the plenum space as part of the assembly.
    10         (2)  For gross area purposes be based upon the interior
    11     face of the upper plenum surface.
    12  Section 206.  Criteria for residential buildings.
    13     (a)  Applicability.--The requirements herein shall apply to
    14  all buildings and structures or portions thereof of Use Groups
    15  R-1 and R-2 that are heated or mechanically cooled when not more
    16  than 3 stories or 40 feet in height.
    17     (b)  Walls.--The gross area of exterior walls above grade,
    18  including foundation walls, shall have a combined thermal
    19  transmittance value (Uo) not exceeding those specified in Table
    20  1.
    21                              Table 1
    22                 Maximum Allowable "Uo" Values for
    23                   Gross Exterior Wall Assemblies
    24                                             R-1 and R-2
    25     Annual heating degree days*             residential
    26                 4000                            0.31
    27                 5000                            0.29
    28                 6000                            0.27
    29                 7000                            0.26
    30     *As specified in Chapter 43 ASHRAE Handbook-Systems.
    20060S1349B2136                 - 15 -     

     1     (c)  Roof/ceiling.--The roof/ceiling assemblies shall have a
     2  combined thermal transmittance value (Uo) not to exceed 0.05
     3  except that roof/ceiling assemblies in which the finished
     4  interior surface is essentially the underside of the roof deck,
     5  such as a wooden cathedral ceiling, may have a "Uo" value not to
     6  exceed 0.08. These values presume no significant thermal
     7  transmission through framing members, skylights or other
     8  interruptions in the roof envelope. If such interruptions occur,
     9  calculations must be made showing conformance to the required
    10  "Uo" values.
    11     (d)  Floors over unheated spaces.--The floor of a heated or
    12  mechanically cooled space located over an unheated space shall
    13  have a combined thermal transmittance value (Uo) not to exceed
    14  0.08.
    15     (e)  Slab-on grade floors.--
    16         (1)  For slab-on grade floors, the perimeter of the floor
    17     shall be insulated with a material having a thermal
    18     resistance value (R) not less than those specified in Table
    19     2.
    20                              Table 2
    21             Minimum Allowable "R" Values of Perimeter
    22                Insulation for Slab-On Grade Floors
    23     Annual heating degree days      Heated slab     Unheated slab
    24                 4000*                   5.5             3.5
    25                 5000                    6.3             4.2
    26                 6000                    7.0             4.9
    27                 7000                    7.8             5.5
    28     *Table values may be interpolated.
    29         (2)  The insulation shall extend downward from the top of
    30     the slab for a minimum distance of 24 inches or downward to
    20060S1349B2136                 - 16 -     

     1     the bottom of the slab then horizontally beneath the slab for
     2     a minimum total distance of 24 inches.
     3  Section 207.  Other buildings.
     4     (a)  Coverage.--The heating and cooling requirements herein
     5  shall govern all buildings and structures or portions thereof
     6  other than defined by section 206.
     7     (b)  Heating criteria for walls.--All buildings and
     8  structures that are heated shall have a combined thermal
     9  transmittance value (Uo) for the gross area of exterior walls
    10  not exceeding those specified in Table 3.

    11                              Table 3
    12                   Maximum Allowable "Uo" Values
    13                 for Gross Exterior Wall Assemblies
    14                                     3 stories or    More than
    15     Annual heating degree days     40 ft. or less  3 stories or
    16                                                       40 ft.
    17                 4000                    0.31            0.38
    18                 5000                    0.29            0.36
    19                 6000                    0.27            0.33
    20                 7000                    0.26            0.31
    21     (c)  Heating criteria for roof/ceiling.--All buildings and
    22  structures that are heated shall have combined thermal
    23  transmittance value (Uo) for roof/ceiling assemblies not
    24  exceeding those specified in Table 4.
    25                              Table 4
    26                   Maximum Allowable "Uo" Values
    27                    for Roof/Ceiling Assemblies
    28     Annual heating degree days              Maximum Uo
    29             4000*                              0.092
    20060S1349B2136                 - 17 -     

     1             5000                               0.084
     2             6000                               0.076
     3             7000                               0.068
     4     *Table values may be interpolated.
     5     (d)  Heating criteria for floors over unheated spaces.--The
     6  floor of a heated space located over an unheated space shall
     7  have a thermal transmittance value (Uo) not exceeding 0.08.
     8     (e)  Heating criteria for slab-on grade floors.--For slab-on
     9  grade floors, the perimeter of the floor shall be insulated with
    10  a material having a thermal resistance value (R) not less than
    11  those specified in Table 5.
    12     The insulation shall extend downward from the top of the slab
    13  for a minimum distance of 24 inches or downward to the bottom of
    14  the slab then horizontally beneath the slab for a minimum total
    15  distance of 24 inches.
    16                              Table 5
    17             Minimum Allowable "R" Values of Perimeter
    18                Insulation for Slab-On Grade Floors
    19     Annual heating degree days      Heated slab    Unheated slab
    20                 4000*                   5.5             3.5
    21                 5000                    6.3             4.2
    22                 6000                    7.0             4.9
    23                 7000                    7.8             5.5
    24     *Table values may be interpolated.
    25     (f)  Cooling criteria for walls.--All buildings and
    26  structures that are mechanically cooled shall have an overall
    27  thermal transfer value for the gross area of exterior walls not
    28  exceeding 33.5 BTU's per hour per square foot based on the
    29  following equation:
    30  OTTV = (Uw x Aw x TDEQ) + (Af x Sf x Sc) + (Uf x Af x Delta T)
    20060S1349B2136                 - 18 -     

     1                                     Ao
     2  OTTV = Overall thermal transfer value where:
     3    Uw = The thermal transmittance of all elements of the opaque
     4          wall area Btu/h. ft2.F (W/m2K)
     5    Aw = Opaque wall area, ft2 (m2)
     6    Uf = The thermal transmittance of the fenestration area
     7          Btu/h. ft2.F (W/m2K)
     8    Af = Fenestration area, ft2 (m2)
     9  TDEQ = Value given in the following table, F, (c):
    10 
    11                  TABLE FOR TEMPERATURE DIFFERENCE
    12     Wall Construction-mass per unit area      TDEQ
    13             LB/FT2          Kg/m2           F     C
    14             0-25            0-125           44  24.5
    15            26-40          126-195           37  21.0
    16            41-70          196-345           30  17.0
    17            71 and above   346 and above     23  13.0
    18 
    19     Weight of wall construction shall be determined from the
    20     1972 ASHRAE Handbook of Fundamentals, Chapter 22.
    21    Sc = Shading coefficient of the fenestration
    22  Delta T = Temperature difference between exterior and interior
    23         design conditions, F, for which the following
    24         temperatures shall apply:
    25                             Indoor          Outdoor
    26                               F  C
    27             Winter           72  22.0       97 1/2%*
    28             Summer           78  25.5        2 1/2%*
    29     *Values from 1972 ASHRAE Handbook of Fundamentals,
    30  Chapter 33.
    20060S1349B2136                 - 19 -     

     1    SF = Solar factor value given Btu/h.ft2 (W/m2).
     2         (use 127 Btu/h.ft2)
     3    AO = Gross area of exterior walls, ft2 (m2). The gross
     4         area of exterior walls consists of all opaque wall
     5         areas (including foundation walls, between floor span-
     6         drels, peripheral edges of floors, etc.), window
     7         areas (including sash), and door areas, where such
     8         surfaces are exposed to outdoor air and enclose a
     9         heated and/or mechanically cooled space (including
    10         intersticial areas between two such spaces).
    11  Note:  Where more than one type of wall and/or fenestration
    12         is used, the respective term or terms shall be expanded
    13         into sub-elements, as:
    14         (Uw x Aw x TDEQ) + (Uw2 x Aw2 x TDEQ2), etc.
    15     (g)  Cooling criteria for roof/ceilings.--All buildings and
    16  structures that are mechanically cooled shall have a combined
    17  thermal transmittance value (Uo) for roof/ceiling assemblies the
    18  same as specified in Table 4 for heating.
    19  Section 208.  Air leakage.
    20     (a)  Application.--The requirements of this section shall
    21  apply to all buildings and structures and apply only to those
    22  locations separating outdoor ambient conditions from interior
    23  spaces that are heated or mechanically cooled and are not
    24  applicable to separation of interior spaces from each other.
    25     (b)  Standard.--Compliance with the criteria for air leakage
    26  shall be determined by ASTM E-283, Standard Method of Test for
    27  Rate of Air Leakage through Exterior Windows, Curtain Walls and
    28  Doors, at a pressure differential of 1.567 lb/ft2 which is
    29  equivalent to the effect of a 25 m.p.h. wind.
    30     (c)  Acceptance criteria.--The following criteria shall
    20060S1349B2136                 - 20 -     

     1  represent the maximum allowable air leakage:
     2         (1)  The air infiltration rate for windows shall not
     3     exceed 0.5 Cfm per foot of sash crack.
     4         (2)  The air infiltration rate for sliding glass doors in
     5     residential buildings shall not exceed 0.5 Cfm per square
     6     foot of door area.
     7         (3)  The air infiltration rate for swinging doors in
     8     residential buildings shall not exceed 1.25 Cfm per square
     9     foot of door area.
    10         (4)  The air infiltration rate for swinging, revolving or
    11     sliding doors in other than residential buildings shall not
    12     exceed 11 Cfm per lineal foot of door crack.
    13     (d)  Caulking and sealants.--Exterior joints around windows
    14  and door frames, between wall cavities and window or door
    15  frames, between wall and foundation, between wall and roof,
    16  between wall panels, at penetrations or utility services through
    17  walls, floors and roofs, and all other openings in the exterior
    18  envelope shall be caulked, gasketed, weatherstripped, or
    19  otherwise sealed.
    20                            SUBCHAPTER E
    21         WARM AIR HEATING, VENTILATING AND AIR CONDITIONING
    22                       SYSTEMS AND EQUIPMENT
    23  Section 209.  General provisions.
    24     This subchapter applies to air duct systems employing
    25  mechanical means for the movement of air used for warm air
    26  heating, ventilating, air conditioning systems, exhaust systems
    27  and combination heating and air conditioning systems, except
    28  that this subchapter shall not apply to systems for the removal
    29  of flammable vapors or residues or to systems for conveying
    30  dust, stock or refuse by means of air currents. Heating,
    20060S1349B2136                 - 21 -     

     1  ventilating and air conditioning systems of all buildings and
     2  structures or portions thereof shall be designed and installed
     3  for efficient use of energy as herein provided. Special
     4  applications, such as but not limited to hospitals,
     5  laboratories, thermally sensitive equipment, computer rooms,
     6  manufacturing processes and supermarkets, are exempt from the
     7  requirements of this subchapter.
     8  Section 210.  Design requirements.
     9     In determining design conditions for calculations under this
    10  section the following design temperatures shall apply:
    11         (1)  Outdoor design temperature shall be selected for
    12     listed locations in Chapter 33 of the ASHRAE Handbook of
    13     Fundamentals, from columns of 97 1/2% values for heating and
    14     2 1/2% values for cooling.
    15         (2)  Indoor design temperature shall be 72 degrees F. for
    16     heating and 78 degrees F. for cooling.
    17         (3)  Indoor design relative humidity for heating shall
    18     not exceed 30%. For cooling, the actual design relative
    19     humidity within the comfort envelope as defined in ASHRAE
    20     Standard 55-74 "Thermal Environmental Conditions for Human
    21     Occupancy" shall be selected for the minimum total heating,
    22     ventilating, and air conditioning system energy use.
    23  Section 211.  Cooling with outdoor air.
    24     (a)  Fan system design.--Each fan system shall be designed to
    25  use up to and including 100% of the fan system capacity for
    26  cooling with outdoor air automatically whenever its use will
    27  result in lower usage of energy than would be required under its
    28  normal operation.
    29     (b)  Exceptions.--Cooling with outdoor air is not required
    30  under any one or more of the following conditions:
    20060S1349B2136                 - 22 -     

     1         (1)  Fan system capacity less than 5,000 Cfm or 134,000
     2     Btu/Hr total cooling capacity.
     3         (2)  The quality of the outdoor air is so poor as to
     4     require extensive treatment of the air.
     5         (3)  The need for humidification or dehumidification
     6     requires the use of more energy than is conserved by outdoor
     7     air cooling.
     8         (4)  The use of outdoor air cooling may affect the
     9     operation of other systems (such as return or exhaust air
    10     fans or supermarket refrigeration) so as to increase the
    11     overall energy consumption of the building.
    12         (5)  Internal/external zone heat recovery or other energy
    13     recovery is used.
    14         (6)  When all space cooling is accomplished by a
    15     circulating liquid which transfers space heat directly or
    16     indirectly to a heat rejection device such as a cooling tower
    17     without the use of a refrigeration system.
    18  Section 212.  Mechanical ventilation.
    19     Each mechanical ventilation system shall be equipped with a
    20  readily accessible means for either shut-off or volume reduction
    21  and shut-off when ventilation is not required.
    22  Section 213.  Simultaneous heating and cooling.
    23     Systems that employ both heating and cooling simultaneously
    24  in order to achieve comfort conditions within a space shall be
    25  limited to those situations where more efficient methods of
    26  heating and air conditioning cannot be effectively utilized to
    27  meet system objectives. Simultaneous heating and cooling by
    28  reheating or recooling supply air or by concurrent operation or
    29  independent heating and cooling systems serving a common zone
    30  shall be restricted as specified herein.
    20060S1349B2136                 - 23 -     

     1  Section 214.  Recovered energy.
     2     Recovered energy, provided the new energy expended in the
     3  recovery process is less than the amount recovered, may be used
     4  for control of temperature and humidity. New energy is defined
     5  as energy, other than recovered, utilized for the purpose of
     6  heating or cooling.
     7  Section 215.  New energy.
     8     (a)  Prevention of excess humidity.--New energy may be used,
     9  when necessary, to prevent relative humidity from rising above
    10  60% for comfort control or to prevent condensation on terminal
    11  units or outlets.
    12     (b)  Control of temperature.--New energy may be used for
    13  control of temperature if minimized as specified in sections 216
    14  through 220.
    15  Section 216.  Reheat systems.
    16     Systems employing reheat and serving multiple zones, other
    17  than those employing variable air volume for temperature
    18  control, shall be provided with control that will automatically
    19  reset the system cold air supply to the highest temperature
    20  level that will satisfy the zone requiring the coolest air.
    21  Single zone reheat systems shall be controlled to sequence
    22  reheat and cooling.
    23  Section 217.  Dual duct and multizone systems.
    24     These systems shall be provided with control that will
    25  automatically reset the cold deck air supply to the highest
    26  temperature that will satisfy the zone requiring the coolest air
    27  and the hot deck air supply to the lowest temperature that will
    28  satisfy the zone requiring the warmest air.
    29  Section 218.  Recooling systems.
    30     Systems in which heated air is recooled directly or
    20060S1349B2136                 - 24 -     

     1  indirectly, to maintain space temperature, shall be provided
     2  with control that will automatically reset the temperature to
     3  which the supply air is heated to the lowest level that will
     4  satisfy the zone requiring the warmest air.
     5  Section 219.  Multiple zones.
     6     For systems with multiple zones, one or more zones may be
     7  chosen to represent a number of zones with similar heating or
     8  cooling characteristics. A multiple zone heating, ventilating
     9  and air conditioning system that employs reheating or recooling
    10  for control of not more than 5,000 Cfm or 20% of the total
    11  supply air of the system, whichever is less, shall be exempt
    12  from the supply air temperature reset requirements of sections
    13  216 through 218.
    14  Section 220.  Concurrent operation.
    15     Concurrent operation of independent heating and cooling
    16  systems serving common spaces, and requiring the use of new
    17  energy for heating or cooling shall be minimized by one or both
    18  of the following:
    19         (1)  By providing sequential temperature control of both
    20     heating and cooling capacity in each zone.
    21         (2)  By limiting the heating energy input, through
    22     automatic reset control of the heating medium temperature (or
    23     energy input rate), to only that necessary to offset heat
    24     loss due to transmission and infiltration and, where
    25     applicable, to heat the ventilation air supply to the space.
    26  Section 221.  Equipment performance requirements.
    27     (a)  Application.--The requirements of this section apply to
    28  equipment and component performance for heating, ventilating and
    29  air conditioning systems. Where equipment efficiency levels are
    30  specified, data furnished by the equipment supplier or certified
    20060S1349B2136                 - 25 -     

     1  under a nationally recognized certification program or rating
     2  procedure shall be used to satisfy these requirements.
     3     (b)  Systems equipment - electrical.--Heating ventilating and
     4  air conditioning systems equipment whose energy input in the
     5  cooling mode is entirely electric shall show a coefficient of
     6  performance (COP) and energy efficiency ratio (EER) not less
     7  than the values specified in Table 6. These requirements apply
     8  to, but are not limited to, unitary cooling equipment (air and
     9  water source); packaged air conditioners; and room air
    10  conditioners. These requirements do not apply to equipment used
    11  in areas having open refrigerated food display cases. For
    12  determining coefficient of performance (COP), the rate of net
    13  heat removal shall be defined as the change in the total heat
    14  contents of the air entering and leaving the equipment (without
    15  reheat). Total energy input shall be determined by combining the
    16  energy inputs to all elements of the equipment, including but
    17  not limited to, compressors, pumps, supply-air fans, cooling
    18  tower fans and the system equipment control circuit.

    19                              Table 6
    20       Minimum EER and COP for Electric Heating, Ventilating
    21               and Air Conditioning System Equipment
    22  Standard rating capacity                       EER     COP
    23  Under 65,000 Btu/hr (19,050 watts)             6.1     1.8
    24  65,000 Btu/hr (19,050 watts) and over          6.8     2.0
    25 
    26     (c)  Other system equipment.--Heat operated cooling equipment
    27  shall show a coefficient of performance (COP) in the cooling
    28  mode not less than the values specified in Table 7. These
    29  requirements apply to, but are not limited to, absorption,
    20060S1349B2136                 - 26 -     

     1  engine-driven and turbine-driven equipment. The coefficient of
     2  performance (COP) is determined excluding the electrical
     3  auxiliary inputs.

     4                              Table 7
     5     Minimum COP for Heating, Ventilating and Air Conditioning
     6               System Heat Operated Cooling Equipment
     7         Heat source                             Minimum COP
     8  Direct fired (gas, oil)                            0.40
     9  Indirect fired (steam, hot water)                  0.65
    10 
    11     (d)  System components.--Heating, ventilating and air
    12  conditioning system components whose energy input in the cooling
    13  mode is entirely electric shall show a coefficient of
    14  performance (COP) and energy efficiency ratio (EER) not less
    15  than the values specified in Table 8. For determining
    16  coefficient of performance (COP), the rate of heat removal is
    17  defined as the difference in total heat contents of the water or
    18  refrigerant entering or leaving the component. Total energy
    19  input shall be determined by combining the energy inputs to all
    20  elements and accessories of the component, including but not
    21  limited to, compressors, internal circulating pumps, condenser-
    22  air fans, evaporative-condenser cooling heater pumps, purge, and
    23  the component control circuit.

    24                              Table 8
    25      Minimum COP for Electrically Driven Heating, Ventilating
    26               and Air Conditioning System Components
    27     Component    Condensing means   Air     Water     Evaporation
    28                                   EER COP  EER COP     EER COP
    20060S1349B2136                 - 27 -     

     1  Self-contained    Centrifugal    7.5 2.2  12.9 3.8
     2  water chillers
     3                     Positive
     4                   displacement    7.2 2.1  10.9 3.2
     5  Condenserless      Positive
     6  water chillers   displacement    8.9 2.6  10.9 3.2
     7  Compressor and
     8  condenser units    Positive
     9  65,000 Btu/hr.   displacement    7.8 2.3  11.3 3.3   11.3 3.3
    10  (19,050 watts)
    11  and over
    12     (e)  Heat pumps.--Heat pumps whose energy input is entirely
    13  electric shall show a coefficient of performance (COP), heating,
    14  not less than the values specified in Table 9.

    15                              Table 9
    16              Minimum COP for Heat Pumps, Heating Mode
    17  Source and outdoor temperature (degree F.)         Minimum COP
    18  Air source--47 DB/43 WB                               2.2
    19  Air source--17 DB/15 WB                               1.2
    20  Water source--60 entering                             2.2
    21     (f)  Supplementary heater.--The heat pump shall be installed
    22  with a control to prevent supplementary heater operation when
    23  the heating load can be met by the heat pump alone.
    24  Supplementary heater operation is permitted during transient
    25  periods, such as start-ups, following room thermostat setpoint
    26  advance, and during defrost. A two-stage room thermostat, which
    27  controls the supplementary heat on its second stage, shall be
    28  accepted as meeting this requirement. The cut-on temperature for
    29  the compression heating shall be higher than the cut-on
    20060S1349B2136                 - 28 -     

     1  temperature for the supplementary heat, and the cut-off
     2  temperature for the compression heating shall be higher than the
     3  cut-off temperature for the supplementary heat. Supplementary
     4  heat may be derived from any source of electric resistance
     5  heating or combustion heating.
     6     (g)  Combustion heating equipment.--All gas and oil-fired
     7  comfort heating equipment shall show a minimum combustion
     8  efficiency of 75% at maximum rated output. Combustion efficiency
     9  shall be determined in accordance with the ASHRAE Standard 90.
    10  Section 222.  Duct insulation.
    11     (a)  Insulation.--All duct systems, or portions thereof,
    12  exposed to nonconditioned spaces shall be insulated to provide a
    13  thermal resistance, excluding film resistance, of
    14             ti - to
    15         R = --------(hr) (sq.ft) (F)/BTU
    16               15
    17  where ti - to is the design temperature differential (absolute
    18  value) between the air in the duct and the surrounding air with
    19  the following exceptions. Duct insulation, except when needed to
    20  prevent condensation, is not required in any of the following
    21  cases:
    22         (1)  Where ti - to is 25 degrees F. or less.
    23         (2)  When the heat gain or loss of the ducts, without
    24     insulation, will not increase the energy requirements of the
    25     building.
    26         (3)  Exhaust air ducts.
    27         (4)  Supply or return air ducts installed in crawl spaces
    28     with insulated walls, basements or cellars in one and two-
    29     family dwellings.
    30     (b)  Vapor barriers.--Where required to prevent condensation,
    20060S1349B2136                 - 29 -     

     1  insulation with vapor barriers shall be installed in addition to
     2  insulation required above.
     3  Section 223.  System controls.
     4     (a)  Application.--All heating, ventilating and air
     5  conditioning systems shall be provided controls as specified
     6  herein.
     7     (b)  Temperature.--Each heating, ventilating and air
     8  conditioning system shall be provided with at least one
     9  thermostat for the regulation of temperature. Each thermostat
    10  shall be capable of being set from 55 degrees F. to 75 degrees
    11  F. where used to control heating only and from 70 degrees F. to
    12  85 degrees F. where used to control cooling only. Where used to
    13  control both heating and cooling it shall be capable of being
    14  set from 55 degrees F. to 85 degrees F. and shall be capable of
    15  operating the system heating and cooling in sequence. It shall
    16  be adjustable to provide a temperature range of up to 10 degrees
    17  F. between full heating and full cooling, except as allowed in
    18  section 220.
    19     (c)  Humidity.--If a heating, ventilating and air
    20  conditioning system is equipped with a means for adding moisture
    21  to maintain specific selected relative humidities in spaces or
    22  zones, a humidistat shall be provided. This device shall be
    23  capable of being set to prevent new energy from being used to
    24  produce space relative humidity above 30% R.H. Where a
    25  humidistat is used in a heating, ventilating and air
    26  conditioning system for controlling moisture removal to maintain
    27  specific selected relative humidities in spaces or zones, it
    28  shall be capable of being set to prevent new energy from being
    29  used to produce a space relative humidity below 60%.
    30     (d)  Temperature zoning.--
    20060S1349B2136                 - 30 -     

     1         (1)  In all buildings and structures of Use Group R-3, at
     2     least one thermostat for regulation of space temperature
     3     shall be provided for each separate heating, ventilating and
     4     air conditioning system. In addition, a readily accessible
     5     manual or automatic means shall be provided to partially
     6     restrict or shut-off the heating or cooling input to each
     7     zone or floor, excluding unheated or uncooled basements and
     8     garages.
     9         (2)  In all buildings and structures of Use Group R-2,
    10     each individual dwelling unit shall be considered separately
    11     and shall meet the requirements for one and two-family
    12     dwellings above.
    13         (3)  In all buildings and structures other than Use Group
    14     R-3 and in spaces other than dwelling units in Use Group R-2,
    15     at least one thermostat for regulation of space temperature
    16     shall be provided for each separate heating, ventilating and
    17     air conditioning system and for each floor of the building.
    18     (e)  Set-back and shut-off.--
    19         (1)  In all buildings and structures, or portions thereof
    20     of Use Group R-3, the thermostat, or an alternate means such
    21     as a switch or a clock, shall provide a readily accessible,
    22     manual or automatic means for reducing the energy required
    23     for heating and cooling during periods of nonuse or reduced
    24     need.
    25         (2)  In all other buildings and structures, or portions
    26     thereof each heating, ventilating and air conditioning system
    27     shall be equipped with a readily accessible means of reducing
    28     the energy used for heating, ventilating and air conditioning
    29     during periods of nonuse or alternate uses of the building
    30     spaces or zones served by the system, such as with manually
    20060S1349B2136                 - 31 -     

     1     adjustable automatic timing devices, manual devices for use
     2     by operating personnel, or automatic control systems.
     3         (3)  Lowering thermostat set points to reduce energy
     4     consumption of heating systems shall not cause energy to be
     5     expended to reach the reduced setting.
     6     Section 4.  Section 224 of the act, amended July 10, 1981
     7  (P.L.231, No.75) and repealed November 10, 1999 (P.L.491,
     8  No.45), is reenacted to read:
     9  Section 224.  Steam and hot water heating systems.
    10     (a)  Combustion heating equipment.--All gas and oil-fired
    11  comfort heating equipment shall show a minimum combustion
    12  efficiency of 75% at maximum rated output. Combustion efficiency
    13  shall be determined in accordance with ASHRAE 90.
    14     (b)  Piping insulation.--All piping serving as part of a
    15  heating or cooling system installed to serve buildings and
    16  within buildings shall be thermally insulated as shown in Table
    17  10.
    18                              Table 10
    19                      Minimum Pipe Insulation
    20 
    21                                 Insulation thickness in inches
    22             Fluid                       for pipe sizes
    23  Piping  temperature
    24  system     range,   Runouts  1" and  1 1/4-  2 1/2-  5&   8" and
    25  types        F.     up to 2"  less     2       4     6    larger
    26  Heating systems
    27     Steam &
    28     hot water
    29  High pressure/
    30  temp       306-450   1 1/2     1 1/2    2    2 1/2  3 1/2  3 1/2
    20060S1349B2136                 - 32 -     

     1  Med. pressure/
     2  temp       251-305   1 1/2     1 1/2    2    2 1/2  3      3
     3  Low pressure/
     4  temp       201-250   1         1       1 1/2 1 1/2  2      2
     5  Low tem-
     6  perature   120-200    1/2       3/4     1    1      1      1 1/2
     7  Steam con-
     8  densate      Any     1         1        1    1 1/2  1 1/2  2
     9  (for feed
    10  water)
    11  Cooling systems
    12  Chilled
    13  water,      40-55     1/2       1/2      3/4 1      1      1
    14  Refrigerant,
    15  or brine  Below 40   1         1       1 1/2  1 1/2 1 1/2  1 1/2
    16  Insulation thicknesses are based on insulation having thermal
    17  resistances in the range of 4.0 to 4.6 per inch of thickness on
    18  a flat surface at a mean temperature of 75 degrees F. Minimum
    19  insulation thickness shall be increased for materials having R
    20  values less than 4.0 or may be reduced for materials having R
    21  values greater than 4.6 per inch of thickness as follows:
    22     (c)  High thermal resistance.--For materials with thermal
    23  resistance greater than R=4.6, the minimum insulation thickness
    24  may be reduced as follows:
    25         4.6 x Table 10 Thickness    =   New Minimum Thickness
    26               Actual R
    27     (d)  Low thermal resistance.--For materials with thermal
    28  resistance less than R=4.0 the minimum insulation thickness
    29  shall be increased as follows:
    30         4.0 x Table 10 Thickness    =   New Minimum Thickness
    20060S1349B2136                 - 33 -     

     1               Actual R
     2  Piping insulation, except when needed to prevent condensation,
     3  is not required in any of the following cases:
     4         (1)  Piping installed within heating, ventilating and air
     5     conditioning equipment.
     6         (2)  Piping at temperatures between 55 degrees F. and 120
     7     degrees F.
     8         (3)  When the heat loss or heat gain of the piping,
     9     without insulation, does not increase the energy requirements
    10     of the building.
    11         (4)  Piping installed in basements or cellars in one and
    12     two-family dwellings.
    13     (e)  Vapor barriers.--Where required to prevent condensation,
    14  insulation with vapor barriers shall be installed in addition to
    15  insulation required above.
    16     Section 5.  Subchapters F, G, H, I and J of Chapter 2,
    17  heading of Chapter 3 and section 301 of the act, repealed
    18  November 10, 1999 (P.L.491, No.45), are reenacted to read:
    19                            SUBCHAPTER F
    20                          PLUMBING SYSTEMS
    21  Section 225.  Purpose.
    22     This subchapter sets forth provisions for design and
    23  equipment selection for energy conservation in service water
    24  heating systems.
    25  Section 226.  Fixtures.
    26     (a)  Lavatories.--Lavatories in restrooms of public
    27  facilities shall be equipped with self-closing outlet devices
    28  which limit the flow of hot water to a maximum of 0.5 Gpm,
    29  devices which limit the outlet temperature to a maximum of 110
    30  degrees F. and self-closing valves which limit the quantity of
    20060S1349B2136                 - 34 -     

     1  hot water to a maximum of 0.25 gallon.
     2     (b)  Showers.--Showers used for other than safety reasons
     3  shall be equipped with flow control devices to limit total flow
     4  to a maximum of 3 Gpm per shower head.
     5  Section 227.  Insulation.
     6     (a)  Piping insulation.--Piping in required return
     7  circulation systems shall be insulated so that heat loss is
     8  limited to a maximum of 25 Btuh per square foot of external pipe
     9  surface for above ground piping and a maximum of 35 Btuh per
    10  square foot of external pipe surface for underground piping.
    11  Maximum heat loss shall be determined at a temperature
    12  differential equal to the maximum water temperature minus a
    13  design ambient temperature no higher than 65 degrees F. except
    14  that conformance with table 10 for "low temperature piping
    15  system" shall be deemed as complying with this section.
    16     (b)  Tanks.--Unfired hot water storage tanks shall be
    17  insulated so that heat loss is limited to a maximum of 15 Btuh
    18  per square foot of external tank surface area. For purposes of
    19  determining this heat loss, the design ambient temperature shall
    20  be no higher than 65 degrees F.
    21  Section 228.  Equipment.
    22     (a)  Pump operation.--Circulating hot water systems shall be
    23  arranged so that the circulating pump can be conveniently turned
    24  off either automatically or manually when the hot water system
    25  is not in operation.
    26     (b)  Electric water heaters.--All automatic electric storage
    27  water heaters shall have a stand-by loss not exceeding 4 watts
    28  per square foot of tank surface area. The method of test of
    29  stand-by loss shall be as described in section 4.3.1 of ANSI
    30  C72.1 Household Automatic Electrical Storage-Type Water Heaters.
    20060S1349B2136                 - 35 -     

     1     (c)  Gas and oil-fired water heaters.--All gas and oil-fired
     2  automatic storage heaters shall have a recovery efficiency, ER,
     3  not less than 75% and a stand-by loss percentage S, not
     4  exceeding S=2.3+67/V where V=rated volume in gallons. The method
     5  of test of ER and S shall be as described in section 2.7 of ANSI
     6  Z21.10.3 Circulating Tank, Instantaneous and Large Automatic
     7  Storage Type Water Heaters, Approval Requirements for Gas Water
     8  Heaters.
     9  Section 229.  Controls.
    10     (a)  Temperature controls.--All hot water supply systems
    11  shall be equipped with automatic temperature controls capable of
    12  adjustments from the lowest to the highest acceptable
    13  temperature settings for the intended use.
    14     (b)  Shut down.--A separate switch shall be provided to
    15  terminate the energy supplied to electric hot water supply
    16  systems. A separate valve shall be provided to turn off the
    17  energy supplied to the main burner of all other types of hot
    18  water supply systems.
    19                            SUBCHAPTER G
    20                         ELECTRICAL SYSTEMS
    21  Section 230.  System requirements.
    22     (a)  Service voltage.--Where a choice of service voltage is
    23  available, the voltage resulting in the least energy loss shall
    24  be used.
    25     (b)  Voltage drop.--In any building, the maximum total
    26  voltage drop shall not exceed 3% in branch circuits or feeders,
    27  for a total of 5% to the farthest outlet based on steady state
    28  design load conditions.
    29     (c)  Lighting switching.--Switching shall be provided for
    30  each lighting circuit, or for portions of each circuit, so that
    20060S1349B2136                 - 36 -     

     1  the partial lighting required for custodial or for effective
     2  complementary use with natural lighting may be operated
     3  selectively.
     4     (d)  Separate metering.--In all multi-family dwellings,
     5  including buildings classified as Use Group R-3, provisions
     6  shall be made to determine the electrical energy consumed by
     7  each tenant.
     8                            SUBCHAPTER H
     9                              LIGHTING
    10  Section 231.  Lighting power budget.
    11     A lighting power budget is the upper limit of the power to be
    12  available to provide the lighting needs in accordance with a
    13  given set of criteria and given calculation procedure.
    14  Section 232.  Calculation methods.
    15     The criteria specified below shall be utilized for
    16  computation of the lighting power budget. All calculations shall
    17  be in accordance with accepted engineering practice. When
    18  insufficient information is known about the specific use of the
    19  building space (e.g., number of occupants, space function,
    20  location of partitions), the budget shall be based on the
    21  apparent intended use of the building space.
    22  Section 233.  Building interiors.
    23     (a)  Procedure.--The allowable electric power for lighting
    24  shall be established by using the criteria and the calculation
    25  procedures specified in section 236. The value shall be based on
    26  the use for which the space within the building is intended and
    27  on efficient energy utilization.
    28     (b)  Illumination level criteria.--For the purpose of
    29  establishing a budget, levels of illumination shall be those
    30  listed in fig. 9-80 of the IES Lighting Handbook, and those
    20060S1349B2136                 - 37 -     

     1  levels shall be used as follows:
     2         (1)  For task lighting, the levels of illumination listed
     3     are for specific tasks. These levels are for the task areas
     4     defined in the IES Lighting Handbook or, where not defined,
     5     at all usable portions of task surfaces. In some cases, the
     6     levels of illumination are listed for locations (e.g.,
     7     auditoriums). These levels are to be considered as average
     8     levels.
     9         (2)  For general lighting, in areas surrounding task
    10     locations, the average level of general lighting, for budget
    11     purposes only, shall be one-third the level for the tasks
    12     performed in the area but in no case less than 20-foot
    13     candles. Where more than one task level occurs in a space,
    14     the general level shall be one-third the weighted average of
    15     the specific task levels.
    16         (3)  For noncritical lighting, in circulation and seating
    17     areas, where no specific visual tasks occur, the average
    18     level of illumination shall be one-third of the average
    19     general lighting in the adjacent task spaces but in no case
    20     less than ten-foot candles.
    21         (4)  For the purpose of establishing a power budget, only
    22     lamp efficacies and coefficients of utilization (CU)
    23     specified in Table 11, shall be assumed.
    24  Section 234.  Building exteriors.
    25     (a)  Basis on use.--In exterior spaces, the lighting power
    26  budget shall be based on the use of which the space is intended
    27  (for task performance, safety, or security) and on efficient
    28  energy utilization.
    29     (b)  Criteria.--The same criteria as those for interior
    30  spaces apply for illumination levels and lighting systems with
    20060S1349B2136                 - 38 -     

     1  the addition of luminaires for floodlighting. For power budget
     2  purposes floodlighting shall be selected with luminaires having
     3  a greater percentage of their beam lumens restricted to the area
     4  to be lighted. Such luminaires are defined as those with at
     5  least the minimum efficiencies listed in the IES Lighting
     6  Handbook.
     7     (c)  Facade lighting.--Facade lighting for budget purposes
     8  shall be no greater than 2% of the total interior load of the
     9  building.
    10     (d)  Calculation procedure.--In establishing a lighting power
    11  budget the following procedures shall be used:
    12         (1)  For overhead lighting the procedure specified in
    13     section 236 shall be followed, but using reflectances as
    14     found.
    15         (2)  For floodlighting the beam lumen method, as shown in
    16     the IES Lighting Handbook and a coefficient of beam
    17     utilization (CBU) of 0.75 shall be used for floodlighting
    18     calculations.
    19  Section 235.  Exceptions to criteria.
    20     (a)  Spaces.--The criteria of section 233 shall not apply to
    21  the following areas when calculating the load:
    22         (1)  Portions of residential occupancies except for
    23     kitchens, bathrooms, and laundry areas and public spaces
    24     including lobbies, halls, stairways, basement areas and
    25     utility rooms.
    26         (2)  Residential type spaces similar to those stated in
    27     paragraph (1) in institutions, such as hospitals, hotels,
    28     funeral homes, churches, museums, etc.
    29         (3)  Theater auditoriums, entertainment and audiovisual
    30     presentations where the lighting is an essential technical
    20060S1349B2136                 - 39 -     

     1     element for the function performed.
     2     (b)  Luminaires.--The criteria of section 234 shall not apply
     3  to the following lamps and luminaires; however, their use shall
     4  be accounted for in the calculation of task lighting loads for
     5  specific tasks. The allowable load shall be based on the
     6  luminaire wattage to achieve the levels of illumination as
     7  covered in section 233 using a point calculation method given in
     8  the IES Lighting Handbook. The excepted lamps and luminaires are
     9  as follows:
    10         (1)  Luminaires for medical and dental purposes.
    11         (2)  Luminaires for highlighting applications, such as
    12     sculpture exhibits, art exhibits, and individual items of
    13     display merchandise.
    14         (3)  Luminaires for specialized lighting applications
    15     (color matching, where electrical interference cannot be
    16     tolerated, etc.).
    17     (c)  Control of reflectances.--The criteria of Table 11 shall
    18  not apply in spaces where it is impractical to control
    19  reflectances and where a dirty atmosphere cannot be avoided.
    20  Where this condition exists, the values for reflectances and
    21  light loss factors shall be those expected to be found and shall
    22  be approved by the department. The calculation shall make a note
    23  of this deviation.
    24  Section 236.  Calculation procedure.
    25     To establish a lighting power budget the following procedures
    26  shall be used:
    27     (a)  To determine illumination levels and areas:
    28         (1)  Determine the visual tasks that are expected to be
    29     performed in each space and the number of planned work
    30     locations where tasks will be performed. If assumptions are
    20060S1349B2136                 - 40 -     

     1     made, their bases shall be indicated.
     2         (2)  Select the illumination level, in foot-candles for
     3     those expected tasks in accordance with section 233(b)(1).
     4         (3)  Calculate total task areas to be illuminated to the
     5     same level by multiplying the number of work locations by 50
     6     square feet per work location. Use actual task area if
     7     greater than 50 square feet. If the sum of all task areas is
     8     greater than 50% of the total space area, then the task area
     9     per work location shall be reduced proportionately, so that
    10     the total task area is limited to one-half the total space
    11     area. If special task lighting or localized lighting is to be
    12     employed, use the actual task areas and point calculation
    13     procedures.
    14         (4)  Calculate the level of general lighting by
    15     multiplying the task lighting level by one-third, where there
    16     is only one task level, or by taking one-third of the sum of
    17     the products of the task levels as provided for in paragraph
    18     (2) and their areas as provided for in paragraph (3) divided
    19     by the total task areas.
    20         (5)  Calculate the level of noncritical lighting.
    21     (b)  To determine lighting system data:
    22         (1)  Determine light source and luminaire types to use.
    23         (2)  Determine lamp lumens per watt and luminaire
    24     coefficients of utilization for room and luminaire mounting
    25     height dimensions. Luminaire CUs shall be selected from the
    26     IES Lighting Handbook. In all cases, no luminaire shall have
    27     a CU for RCR = 1 of less than that given in Table 11 lamp
    28     efficacies for the appropriate space.
    29     (c)  To determine allowable wattage:
    30         (1)  Using data from subsection (b), the illumination
    20060S1349B2136                 - 41 -     

     1     levels and areas determined in subsection (a), and the
     2     criteria of Table 11 on Reflectance, calculate the allowable
     3     wattages using the lumen method.
     4         (2)  Calculate the total space wattage by adding the
     5     task, general and noncritical lighting loads.
     6         (3)  Add the wattage of luminaires allowed in section
     7     235(b).
     8                              Table 11
     9     (a)  Lamp efficacies.--The following are initial lumen output
    10  per watt input, including ballast losses:
    11                 Application                             Lumens
    12                                                        per Watt
    13     Where moderate color rendition is appropriate         55
    14     Where good color rendition is appropriate             40
    15     Where high color rendition is appropriate,
    16     spaces are less than 50 square feet or where
    17     use of low wattage High Intensity Discharge
    18     (HID) lamps under 250 W or fluorescent
    19     lamps under 40 W is appropriate.                          25
    20     (b)  Luminaire coefficients of utilization (CU).--
    21  Coefficients of utilization (CUs) are to be for luminaires for
    22  use in the types of spaces listed below, and those luminaires
    23  shall have a CU of no less than that listed below (for each type
    24  space) for a Room Cavity Ratio (RCR) of 1 and reflectances as in
    25  (c).
    26                 Space Use                           Minimum CU
    27                                                    (at RCR = 1)
    28     For spaces with tasks subjected to veiling
    29     reflections, where recommended levels of
    30     illumination are listed in terms of
    20060S1349B2136                 - 42 -     

     1     equivalent sphere illumination (ESI), and
     2     where visual comfort is important.                  0.55
     3     For spaces without tasks, or with tasks
     4     not subjected to veiling reflections, but
     5     where visual comfort is important.                  0.63
     6     For spaces without tasks and where visual
     7     comfort is not a criterion.                         0.70
     8     (c)  Other criteria:
     9         (1)  Reflectances. For interior spaces, the following
    10     initial cavity and surface reflectances shall be assumed:
    11     Ceiling cavity reflectance              80%
    12     Wall reflectance                        50%
    13     Floor cavity reflectance                20%
    14         (2)  Light loss factor. A light loss factor (LLF) of 0.70
    15     shall be used.
    16                            SUBCHAPTER I
    17                        ALTERNATIVE SYSTEMS
    18  Section 237.  Performance alternative.
    19     Alternative building systems and equipment design may be
    20  approved by the department when they can be shown to have energy
    21  consumption not greater than that of a similar building with
    22  similar forms of energy requirements, designed in accordance
    23  with the provisions of this act or when they can be shown to
    24  have energy consumption not greater than that which shall be
    25  established by the department with the approval of the Building
    26  Energy Conservation Committee, for the purposes of this section:
    27  Provided, however, That for all buildings classified as Use
    28  Group R-3 alternate building systems and equipment design which
    29  satisfy the criteria of this section shall not require the
    30  approval of the department but the use of such an alternate
    20060S1349B2136                 - 43 -     

     1  building system or equipment design shall be indicated in the
     2  warranty provided in section 306.
     3  Section 238.  Nondepletable sources; exemption.
     4     When such alternative systems utilize solar, geothermal, wind
     5  or other nondepletable energy sources for all or part of their
     6  energy sources, such nondepletable energy supplied to the
     7  building shall be excluded from the total energy chargeable to
     8  the proposed alternative design. Any structure that is designed
     9  and built free of any dependence on depletable energy sources
    10  shall be exempt from the provisions of section 239 and any other
    11  provisions of this act.
    12  Section 239.  Documentation.
    13     Proposed alternative designs, submitted to the department as
    14  requests for exception to the standard design criteria, must be
    15  accompanied by an energy analysis prepared in accordance with
    16  the ASHRAE Standard 90-75.
    17                            SUBCHAPTER J
    18                USE GROUP R-3 PRESCRIPTIVE STANDARDS
    19  Section 240.  Minimum insulation requirements for Use Group R-3.
    20     Except as provided in section 237, Use Group R-3 buildings
    21  shall be constructed utilizing the following minimum insulation
    22  standards:
    23  Ceilings                                           R - 19
    24  Exterior Walls                                     R - 13
    25  Floors Over Unheated Basements
    26     and Crawl Spaces*                               R - 11
    27     *Basements containing a furnace
    28       and/or hot water heater may be
    29       considered heated
    30  Edge Insulation for:
    20060S1349B2136                 - 44 -     

     1     Heated Slabs                                    R - 6.3
     2     Unheated Slabs                                  R - 4.2
     3  Windows                                        Multiglazing
     4  Entrance Doors                                     R - 2.5
     5  Sliding Glass Doors (if applicable)            Multiglazing
     6  Ducts in Unheated Areas                            R - 3
     7                             CHAPTER 3
     8              APPLICATION OF STANDARDS: ESTABLISHMENT
     9                     OF COMMITTEE AND PENALTIES
    10  Section 301.  Modification of standards; criteria.
    11     (a)  Recommendations to General Assembly.--The department,
    12  with the approval of the Building Energy Conservation Committee
    13  established pursuant to section 304, after one or more public
    14  hearings, may recommend to the General Assembly modifications to
    15  the energy conservation standards contained in Chapter 2 hereof.
    16  Any recommended modification to the energy conservation
    17  standards shall meet the following criteria:
    18         (1)  It shall be consistent with the latest and most
    19     effective technology.
    20         (2)  It shall not be in conflict with existing safeguards
    21     for public health and safety.
    22         (3)  It shall be economically feasible as determined by
    23     life-cycle-cost procedures.
    24         (4)  It shall be sufficiently stringent to effect a
    25     significant savings of energy resources.
    26         (5)  It shall be a performance standard for the design of
    27     buildings and systems within buildings to assure maximum
    28     practical conservation of energy.
    29         (6)  Consideration shall be given to building and energy
    30     standards promulgated by national and other State
    20060S1349B2136                 - 45 -     

     1     governmental agencies, private organizations and any other
     2     available energy data.
     3     (b)  Federal performance standards.--In the event that the
     4  Federal Government promulgates performance standards that are
     5  inconsistent or more stringent than the standards detailed in
     6  this act, and the Federal Government mandates the states to
     7  enact legislation to comply with its standards, then the
     8  department, with the approval of the Building Energy
     9  Conservation Committee, may modify the energy conservation
    10  standards contained in this bill without the approval of the
    11  General Assembly, in order to comply with the Federal standards.
    12     Section 6.  Section 302 of the act, amended May 9, 1986
    13  (P.L.181, No.55) and repealed November 10, 1999 (P.L.491,
    14  No.45), is reenacted and amended to read:
    15  Section 302.  Application of energy conservation standards.
    16     The energy conservation standards contained herein or as
    17  promulgated by the department with the approval of the Building
    18  Energy Conservation Committee shall apply to new buildings or to
    19  renovations or additions on which actual construction and/or
    20  design has not commenced prior to their effective dates. Except
    21  for the authority of the Department of Community [Affairs] and
    22  Economic Development to promulgate rules or regulations for all
    23  units subject to the act of May 11, 1972 (P.L.286, No.70), known
    24  as the "Industrialized Housing Act," provided such standards
    25  invoked are equal to or more stringent than those contained in
    26  this act, or as mandated by Federal law, no public utility as
    27  defined in 66 Pa.C.S. § 102 (relating to definitions),
    28  department, board, agency or commission other than as provided
    29  herein, shall promulgate or adopt any mandatory building energy
    30  conservation standards, rules or regulations other than the
    20060S1349B2136                 - 46 -     

     1  standards contained in Chapter 2, Subchapters D through J or
     2  promulgated under Chapter 4 of this act except as mandated by
     3  Federal law.
     4     Section 7.  Sections 303 and 304 of the act, repealed
     5  November 12, 1999 (P.L.491, No.45), are reenacted to read:
     6  Section 303.  Energy conservation manual for buildings.
     7     (a)  Production of manual.--Concurrent with the adoption of
     8  the energy conservation codes required by this act, the
     9  department in conjunction with the Governor's Energy Council
    10  shall produce an energy conservation manual for use by
    11  designers, builders, contractors of residential and
    12  nonresidential buildings, and municipalities of the
    13  Commonwealth. This manual shall contain the established
    14  standards and accepted practices. The manual shall further
    15  contain prescriptive standards which, if complied with, will
    16  result in conformance with the performance standards contained
    17  herein or as promulgated by the department and shall be written
    18  in such manner as to be easily understood by persons possessing
    19  a minimal technical background. The manual shall be furnished
    20  upon request to members of the public at a price sufficient to
    21  cover the cost of printing.
    22     (b)  Review of manual.--The manual shall be reviewed by the
    23  department and the Building Energy Conservation Committee at
    24  least annually and shall be updated as significant new energy
    25  conservation information becomes available.
    26     (c)  Educational programs.--The department in conjunction
    27  with the Governor's Energy Council shall provide seminars and
    28  other educational programs throughout the Commonwealth to
    29  provide information and counseling to builders, architects,
    30  other licensed design professionals, local building officials
    20060S1349B2136                 - 47 -     

     1  and other persons affected by this act on the standards
     2  contained herein or as promulgated by the department.
     3  Section 304.  Building Energy Conservation Committee.
     4     (a)  Composition of committee.--In order to further the
     5  coordinated and effective administration of this act, there is
     6  hereby established within the Governor's Energy Council a
     7  Building Energy Conservation Committee. It shall consist of
     8  twelve members, the membership of which shall be appointed by
     9  the Governor. The committee shall consist of the following
    10  members or their designees:
    11         (1)  Two representatives of State Government.
    12         (2)  One representative of local government.
    13         (3)  One licensed professional engineer.
    14         (4)  Two building contractors, one residential and one
    15     industrial.
    16         (5)  One licensed architect.
    17         (6)  One representative of the energy supply industry.
    18         (7)  Four representatives of such other agencies and
    19     organizations or individuals as the Governor may find are
    20     necessary and proper to carry out the purposes of the
    21     committee.
    22     (b)  Powers and duties.--In addition to the powers and duties
    23  enumerated in this act, the Building Energy Conservation
    24  Committee shall:
    25         (1)  Be responsible for the regular exchange of
    26     information and plans regarding building energy conservation,
    27     for the development, review and approval of proposed and
    28     existing standards, guidelines, regulations and manuals.
    29         (2)  Elect from its members a Board on Variances.
    30     (c)  Expenses.--The members of the committee shall not
    20060S1349B2136                 - 48 -     

     1  receive any compensation for their services but shall be
     2  reimbursed for their actual and necessary expenses incurred in
     3  the performance of their duties. Provided, however, when acting
     4  on matters concerning variances members of the Board on
     5  Variances shall receive $50 per day plus their actual and
     6  necessary expenses.
     7     Section 8.  Section 305 of the act, amended December 19, 1985
     8  (P.L.344, No.98) and repealed November 10, 1999 (P.L.491,
     9  No.45), is reenacted to read:
    10  Section 305.  Certification.
    11     (a)  Applicability.--The provisions of this section shall
    12  apply to all buildings subject to this act except those
    13  classified as Use Group R-3.
    14     (b)  Compliance with act.--It shall be the duty of the
    15  licensed design professional retained in connection with the
    16  design or construction of a building to certify that, in his
    17  professional opinion and in accordance with the accepted
    18  standards of his profession, the drawings, specifications and
    19  other data will achieve compliance with the provisions of this
    20  act. If no licensed design professional is retained in
    21  connection with the design or construction of a building, then
    22  this certification shall be made by the builder or the owner, if
    23  he is the builder. All such information required in this
    24  provision to be submitted to the department must be accompanied
    25  by a filing fee of $10. The filing fee may be subject to change
    26  by the Building Energy Conservation Committee upon the
    27  recommendation of the department to the Building Energy
    28  Conservation Committee, provided, however, that advance notice
    29  of such change has appeared in the Pennsylvania Bulletin. If the
    30  building is subject to the provisions of the act of April 27,
    20060S1349B2136                 - 49 -     

     1  1927 (P.L.465, No.299), referred to as the Fire and Panic Act,
     2  the certification required hereunder shall be submitted on a
     3  form with the application for plan approval under the said Fire
     4  and Panic Act.
     5     (c)  Inspection.--Each licensed design professional retained
     6  by the owner or his designee, where any of such are retained
     7  during the construction of a building, shall make periodic
     8  inspections of the building progression to observe compliance
     9  with this act: Provided, That such inspection shall not be
    10  construed as a guarantee of satisfactory performance by others
    11  or as an assumption of financial liability for unknown defects
    12  or deficiencies in the work of others.
    13     (d)  Final certification.--Each builder retained by the owner
    14  or the owner, if he is the builder, shall make a final
    15  certification of every completed building stating that such
    16  building has been constructed in compliance with the approved
    17  drawings and specifications prepared by a licensed design
    18  professional or with the provisions of this act.
    19     Section 9.  Section 306 of the act, amended December 19, 1985
    20  (P.L.344, No.98) and repealed November 10, 1999 (P.L.491,
    21  No.45), is reenacted and amended to read:
    22  Section 306.  Use Group R-3; notice; warranty.
    23     (a)  Notice to department.--Prior to construction of any
    24  building classified as Use Group R-3, the builder shall notify
    25  the department by first class mail of his intent to begin
    26  construction. Such notice shall include a filing fee of $10 and
    27  contain the name of the owner of the building and its location.
    28  The filing fee may be subject to change by the Building Energy
    29  Conservation Committee, upon the recommendation of the
    30  department to the Building Energy Conservation Committee,
    20060S1349B2136                 - 50 -     

     1  provided, however, that advance notice of such change has
     2  appeared in the Pennsylvania Bulletin.
     3     (a.1)  Restricted account.--All filing fees shall be
     4  deposited in a restricted account in the State Treasury to be
     5  known as the Building Energy Conservation Account. All fees
     6  collected for the purpose of this act shall be deposited in this
     7  account and the department shall draw from the account
     8  sufficient funds to cover the administrative and enforcement
     9  costs of operating the program. The funds in the account are
    10  hereby appropriated to the department to carry out this act and
    11  shall not lapse at the end of any fiscal year. The balance of
    12  funds remaining in any existing Building Energy Conservation
    13  Account and held by the department on the effective date of this
    14  act is hereby transferred to the special Building Energy
    15  Conservation Account established pursuant to this subsection.
    16     (a.2)  Notice to public utilities and utility providers.--
    17         (1)  Prior to construction and except as provided in
    18     paragraph (5), the builder shall also provide a copy of the
    19     notice of intent to begin construction required by subsection
    20     (a) and certified as received by the department to all public
    21     utilities or utility providers which may be requested to
    22     furnish any electric service to or for buildings classified
    23     as Use Group R-3 which are constructed after the effective
    24     date of this subsection.
    25         (2)  All public utilities and utility providers shall
    26     rely on the certified copy of the required notice in
    27     furnishing, rendering or supplying any electric service to or
    28     for a building classified as Use Group R-3, except as
    29     provided in paragraph (5), and no public utility or utility
    30     provider shall conduct any audit, inspection or examination
    20060S1349B2136                 - 51 -     

     1     of the building for the purpose of determining compliance
     2     with this act. The furnishing, rendering or supplying of
     3     electric service by a public utility or utility provider to
     4     or for a building classified as Use Group R-3 shall not
     5     constitute a certification or determination by the public
     6     utility or utility provider that the building has been
     7     constructed in compliance with this act.
     8         (3)  Except as provided in paragraph (5), no public
     9     utility or utility provider shall furnish any electric
    10     service to or for any building classified as Use Group R-3
    11     which is constructed after the effective date of this
    12     subsection unless it has first received the required copy of
    13     the notice of intent to begin construction which has been
    14     certified as received by the department.
    15         (4)  Each public utility or utility provider shall be
    16     required to retain the certified copy of the notice of intent
    17     to begin construction which is submitted to it for at least
    18     two years: Provided, however, That if a utility or utility
    19     provider uses data processing equipment to record and
    20     maintain information derived from the certified copy of the
    21     notice of intent to begin construction, such utility or
    22     utility provider shall not be required to retain the
    23     certified copy of the notice or a photocopy thereof.
    24         (5)  (i)  Each public utility or utility provider shall
    25         be exempt from the provisions of paragraphs (1) through
    26         (4) when any electric service is requested for a building
    27         classified as Use Group R-3 which is located in a
    28         municipality which has elected to administer this act in
    29         accordance with sections 501 and 502 and which requires
    30         that a notice of intent to begin construction be filed
    20060S1349B2136                 - 52 -     

     1         with the municipality prior to or at the time that
     2         application is made for a building permit.
     3             (ii)  Each public utility or utility provider shall
     4         be exempt from the provisions of paragraphs (1) through
     5         (4) in situations where, in the public utility's or
     6         utility provider's judgment, strict compliance may
     7         jeopardize the public health or safety or impose an undue
     8         hardship. In such event, the public utility or utility
     9         provider shall notify the department or the administering
    10         municipality, in writing, on forms prescribed by the
    11         department, of the exemption.
    12         (6)  If a builder fails to file the required notice with
    13     the department or the administering municipality within 30
    14     days of receiving an exemption under paragraph (5), the
    15     department or the administering municipality shall serve
    16     written notice on the builder that he is in violation of this
    17     act and subject to a penalty as provided for in subsection
    18     (d).
    19     (b)  Warranty.--At the time a contract for the construction
    20  of any building classified as Use Group R-3 is entered into, the
    21  builder shall warrant to the owner in writing that the building
    22  shall be constructed in accordance with the provisions of this
    23  act. Such warranty shall be a document separate from the
    24  contract and shall be in the following form:
    25         I, (Builder), hereby warrant to (Owner) that the premises
    26     known as (Description) shall be constructed in accordance
    27     with the provisions of the Act of December 15, 1980 (No.222),
    28     known as the "Building Energy Conservation Act."
    29         This law provides building standards to make your home
    30     energy efficient and also provides you with legal remedies if
    20060S1349B2136                 - 53 -     

     1     your home is not built according to the State standards. If
     2     you would like the State to do an energy audit of your home
     3     to determine if it conforms to State standards, you may call
     4     the Pennsylvania Department of Community [Affairs] and
     5     Economic Development at (Telephone), and they will perform an
     6     inspection of your home for a fee of $35.
     7         Indicate if alternate building system or equipment design
     8     is being employed.
     9     (c)  If the builder is also the owner of the building at the
    10  time of construction, he shall provide the warranty required by
    11  subsection (b) at the time of its initial sale to a new owner.
    12  Such warranty shall be in substantially the same form as
    13  provided in subsection (b).
    14     (d)  Failure to provide notice.--The Department of Community
    15  [Affairs] and Economic Development, after hearing, may assess a
    16  civil penalty payable to the Commonwealth of Pennsylvania not to
    17  exceed $100 for a first offense upon any builder who fails to
    18  give the notice required by subsection (a). In determining the
    19  amount of the civil penalty for a first offense, the department
    20  shall consider the willfulness of the violation and the cost
    21  incurred by the department in discovering the violation. In the
    22  event a builder fails to give the notice required by subsection
    23  (a) on a second or subsequent occasion, the department shall
    24  assess upon the builder a civil penalty payable to the
    25  Commonwealth of Pennsylvania of $200.
    26     (e)  Failure to provide warranty.--Whenever a builder fails
    27  to provide the warranty required by subsection (b) or (c) such
    28  required warranty shall constitute an implied warranty and the
    29  owner's right to proceed under section 315(a) shall not be
    30  affected. If it is established by a preponderance of the
    20060S1349B2136                 - 54 -     

     1  evidence that the builder's failure to provide the warranty was
     2  willful, then damages in twice the amount provided in section
     3  315 may be awarded.
     4     Section 10.  Sections 307, 308, 309, 310 and 311 of the act,
     5  repealed November 10, 1999 (P.L.491, No.45), are reenacted to
     6  read:
     7  Section 307.  Variances.
     8     (a)  Requests.--Any request for a variance from the energy
     9  conservation standards contained herein shall be made to the
    10  Board on Variances of the Building Energy Conservation Committee
    11  and a decision on such request shall be made within 30 days of
    12  its filing.
    13     (b)  Criteria.--A variance shall be granted only if it is
    14  found that:
    15         (1)  compliance with the provisions of this act would
    16     result in extreme hardship to the owner; and
    17         (2)  the granting of such variance would not result in a
    18     significant increase in the energy usage of the building.
    19  Section 308.  Building permits.
    20     Any building permit issued by the Commonwealth or any of its
    21  political subdivisions shall have printed upon its face notice
    22  that the provisions of this act must be complied with.
    23  Section 309.  Permits for use or occupancy.
    24     Before any building or structure hereafter constructed, other
    25  than a building not subject to this act, or those classified as
    26  Use Group R-3, shall be used or opened for occupancy, the owner
    27  thereof shall notify the department of the completion of the
    28  building for the purposes of this act and submit the necessary
    29  certification therewith: Provided, however, That if a
    30  municipality elects to administer the provisions of this act
    20060S1349B2136                 - 55 -     

     1  under Chapter 5 such notice and certification shall be submitted
     2  to the municipality which shall forward a copy of the notice to
     3  the department. No permit for use or occupancy shall be granted
     4  until such submission has been made. No building official of the
     5  Commonwealth or any of its political subdivisions shall issue a
     6  permit until he has received proof of such compliance. Where the
     7  certificate has been submitted to the department, presentation
     8  to the building official of the mailing receipt together with a
     9  copy of the certification required by section 305 shall
    10  establish proof of compliance for the purposes of this section.
    11  Upon such presentation any building official of the Commonwealth
    12  or any of its political subdivisions shall issue a permit for
    13  use or occupancy, provided all other criteria for such a permit
    14  have been satisfied and said building official shall notify the
    15  department that he has issued the same.
    16  Section 310.  Failure to submit certification.
    17     Whenever the owner of any building, other than a building
    18  classified as Use Group R-3, shall fail to give the notice and
    19  submit the necessary certification in accordance with section
    20  309 and shall nevertheless proceed with the use or occupancy of
    21  the building, the department or the municipality shall serve
    22  notice on the said owner that he is in violation of this act and
    23  order him to comply therewith.
    24  Section 311.  Inspections.
    25     The department may perform a nondestructive inspection within
    26  two years of the date of completion of construction of any
    27  building constructed after the effective date of this act to
    28  determine compliance with the provisions of this act, provided
    29  at least 30 days notice has been given to the owner. The costs
    30  of any such inspection initiated by the department shall not be
    20060S1349B2136                 - 56 -     

     1  assessed on the owner. The department may also cause such an
     2  inspection to be performed at the request of the owner of any
     3  building subject to this act. The fee for such an inspection
     4  upon request under section 306(b) for R-3 buildings is $35. The
     5  fee for inspections performed upon request for all other
     6  buildings subject to this act shall be determined by the
     7  department at such an amount as to cover the necessary costs of
     8  the inspection.
     9     Section 11.  Section 313 of the act, amended December 19,
    10  1985 (P.L.344, No.98) and repealed November 10, 1999 (P.L.491,
    11  No.45), is reenacted to read:
    12  Section 313.  Penalties.
    13     (a)  Applicability.--The provisions of this section shall
    14  apply to all buildings subject to this act except those
    15  classified as Use Group R-3.
    16     (b)  Violations of act.--Any person who shall willfully or
    17  negligently violate any of the provisions of this act, or the
    18  rules and regulations or the orders for the enforcement of the
    19  said provisions or rules and regulations issued by duly
    20  authorized officers of the department or who shall hinder, delay
    21  or interfere with any officer charged with the enforcement of
    22  this act in the performance of his duty, shall, upon conviction
    23  thereof, be punished by a fine of $300 and costs. In the event
    24  of violation of more than one provision of this act, the
    25  violation of each provision shall be deemed a separate and
    26  distinct offense for the purposes of this section.
    27     (c)  Institution of proceedings.--Prosecutions for violations
    28  of this act or the rules and regulations of the department may
    29  be instituted by the Secretary of Labor and Industry or under
    30  his directions by an authorized representative of the
    20060S1349B2136                 - 57 -     

     1  department. Upon conviction after a hearing in a court of
     2  competent jurisdiction, the sentences provided in this act shall
     3  be imposed and shall be final unless an appeal be taken in the
     4  manner prescribed by law.
     5     (d)  Disposition of fines.--All fines collected under this
     6  act shall be forwarded to the department who shall pay the same
     7  into the State Treasury for the use of the Commonwealth.
     8     (e)  False certification.--Any architect or other licensed
     9  design professional who willfully provides a false certification
    10  for any building subject to the provisions of this act shall be
    11  subject to the suspension or revocation of his license by the
    12  State Board of Examiners of Architects or other applicable State
    13  licensing board.
    14     Section 12.  Sections 314 and 315, Chapter 4, Chapter 5
    15  heading and sections 501, 502 and 503 of the act, repealed
    16  November 10, 1999 (P.L.491, No.45), are reenacted to read:
    17  Section 314.  Enforcement.
    18     (a)  Applicability.--The provisions of this act shall apply
    19  to every building enumerated in this act, including buildings
    20  owned in whole or in part by the Commonwealth or any political
    21  subdivision thereof, and with the exception of those buildings
    22  not included in this act or those classified as Use Group R-3,
    23  shall be enforced by the Secretary of Labor and Industry, by and
    24  through his authorized representatives.
    25     (b)  Powers of officers.--For the purpose of enforcing the
    26  provisions of this act, all the officers charged with its
    27  enforcement shall have the power to enter any of the buildings
    28  enumerated in this act, and no person shall hinder or delay, or
    29  interfere with any of the said officers in the performance of
    30  his duty, nor refuse any pertinent information necessary to
    20060S1349B2136                 - 58 -     

     1  determine whether the provisions of this act and the rules and
     2  regulations herein provided for, are or will be complied with.
     3  Section 315.  Civil action.
     4     (a)  Use Group R-3.--The owner of any building subject to the
     5  requirements of section 306 who is aggrieved as the result of
     6  such building not being properly designed or constructed in
     7  conformance with this act shall have a right of action for
     8  breach of warranty. Remedies may include specific performance or
     9  an award of damages in an amount not less than $300. Attorney's
    10  fees shall be recoverable in any action in which the owner
    11  prevails. Any such award shall further provide for payment of
    12  the actual costs in excess of $35 incurred by the department if
    13  it inspected the building for the owner and the owner shall
    14  remit such amount to the department.
    15     (b)  Other buildings.--The owner of any building, other than
    16  a building not included in this act or those classified as Use
    17  Group R-3, at the time of its design or construction under the
    18  provisions of this act who is aggrieved as the result of such
    19  building not being properly designed or constructed in
    20  conformance with the certificate issued under section 305 of
    21  this act shall have a right of action against any person who is
    22  required to submit such certificate.
    23     (c)  Limitation of action.--
    24         (1)  No action brought under subsection (a) shall be
    25     maintained unless brought within three years from the date of
    26     the warranty.
    27         (2)  No action brought under subsection (b) shall be
    28     maintained unless brought within three years from the date of
    29     completion of the building.
    30                             CHAPTER 4
    20060S1349B2136                 - 59 -     

     1                    ADOPTION OF FUTURE STANDARDS
     2  Section 401.  Adoption and promulgation of standards.
     3     The department, with the approval of the Building Energy
     4  Conservation Committee, shall, after one or more public
     5  hearings, adopt and publish energy conservation standards for
     6  all buildings covered by this act in accordance with the
     7  provisions of the act of July 31, 1968 (P.L.769, No.240), known
     8  as the "Commonwealth Documents Law." The purpose of such
     9  standards is to reduce wasteful or uneconomic consumption of
    10  energy by balancing the cost of energy procurement against the
    11  cost of energy-conserving building practices. The energy
    12  conservation standards shall meet the following criteria:
    13         (1)  They shall be consistent with the latest and most
    14     effective technology.
    15         (2)  They shall not be in conflict with existing
    16     safeguards for public health and safety.
    17         (3)  They shall be economically feasible as determined by
    18     life-cycle-cost procedures.
    19         (4)  They shall be sufficiently stringent to effect a
    20     significant savings of energy resources.
    21         (5)  They shall be a performance standard for the design
    22     of buildings and systems within buildings to assure maximum
    23     practical conservation of energy.
    24         (6)  Consideration shall be given to building and energy
    25     standards promulgated by national and other State
    26     governmental agencies, private organizations and any other
    27     available energy data.
    28                             CHAPTER 5
    29                           LOCAL ELECTION
    30  Section 501.  Election; Use Group R-3.
    20060S1349B2136                 - 60 -     

     1     Any municipality of this Commonwealth may elect to administer
     2  the provisions of this act relating to Use Group R-3 buildings,
     3  as defined in section 103, except for units subject to the act
     4  of May 11, 1972 (P.L.286, No.70), known as the "Industrialized
     5  Housing Act" or those units subject to Title VI (Public Law 93-
     6  383) referred to as the Federal Mobile Home Construction and
     7  Safety Standards Act of 1974. Such election shall be made by
     8  resolution of the governing body of such municipality which
     9  shall be in substantially the following form:
    10     The (city, borough, town, or township) of____________________
    11  hereby elects to administer the provisions of the act
    12  of December 15, 1980 (No.222), known as the "Building
    13  Energy Conservation Act" for Use Group R-3 buildings as defined
    14  therein.
    15  Section 502.  Election; cities of the first, second and second
    16             class A.
    17     Any city of the first class, second class and second class A
    18  may elect to administer the provisions of this act for all
    19  buildings subject hereto, except for units subject to the act of
    20  May 11, 1972 (P.L.286, No.70), known as the "Industrialized
    21  Housing Act" or those units subject to Title VI (Public Law 93-
    22  383) referred to as the Federal Mobile Home Construction and
    23  Safety Standards Act of 1974. Such election shall be made by
    24  resolution of the governing body of such city which shall be in
    25  substantially the following form:
    26     The city of________________hereby elects to administer the
    27  provisions of the act of December 15, 1980 (No.222), known as
    28  the "Building Energy Conservation Act."
    29  Section 503.  Powers of municipalities.
    30     Any municipality electing to administer the provisions of
    20060S1349B2136                 - 61 -     

     1  this act under section 501 or 502 shall exercise the same powers
     2  conferred upon the department by this act, including the power
     3  to institute proceedings for violations of the act, with the
     4  exception of those powers specified in sections 301, 303 and in
     5  Chapter 4. In addition, any such municipality may exercise such
     6  other administrative and enforcement procedures as it shall deem
     7  necessary to effect the purposes of this act including, but not
     8  limited to, prior plan approval, building permit requirements,
     9  use or occupancy permit requirements and inspections during the
    10  course of construction.
    11     Section 13.  Section 504 of the act, amended December 19,
    12  1985 (P.L.344, No.98) and repealed November 10, 1999 (P.L.491,
    13  No.45), is reenacted to read:
    14  Section 504.  Variances.
    15     Any municipality electing to administer the provisions of
    16  this act under section 501 or 502 shall establish a Board on
    17  Variances to make determinations on request for variance from
    18  the energy conservation standards contained herein or as
    19  promulgated by the department with the approval of the Building
    20  Energy Conservation Committee, and is authorized exclusive
    21  jurisdiction to grant such variances, section 307(a)
    22  notwithstanding. A municipality, however, need not establish a
    23  Board on Variances if it has established a zoning hearing board
    24  pursuant to the act of July 31, 1968 (P.L.805, No.247), known as
    25  the "Pennsylvania Municipalities Planning Code." If the
    26  municipality does not establish a Board on Variances, the powers
    27  and duties established by this section shall be exercised by
    28  such zoning hearing board. A variance shall only be granted if
    29  the criteria of section 307(b) have been satisfied.
    30     Section 14.  Section 505 and Chapter 6 of the act, repealed
    20060S1349B2136                 - 62 -     

     1  November 10, 1999 (P.L.491, No.45), are reenacted to read:
     2  Section 505.  Disposition of fines and fees.
     3     Any fines or fees collected under this act by any
     4  municipality electing to administer the provisions of this act
     5  under section 501 or 502 shall be retained by the municipality,
     6  section 313(d) notwithstanding.
     7                             CHAPTER 6
     8                     REPORT TO GENERAL ASSEMBLY
     9  Section 601.  Report to General Assembly.
    10     Thirty months after the effective date of this act, the
    11  department shall report to the General Assembly the results of
    12  the inspections it has performed under this act together with a
    13  report on public compliance with this act. The report shall also
    14  document the amount of money that the department received
    15  pursuant to this act and the dispensation of these funds. In
    16  addition, within 24 months of the effective date of this act,
    17  the department shall obtain from every municipality electing to
    18  enforce the provisions of this act a report containing
    19  information similar to that required of the department under
    20  this section. The department shall include such findings in its
    21  report to the General Assembly.
    22  Section 602.  Effective date.
    23     This act shall take effect as follows:
    24         (1)  Chapter 2 shall take effect July 1, 1981 and shall
    25     remain in full force and effect for a period of one year
    26     after which time the provisions of Chapter 2 shall have no
    27     legal effect.
    28         (2)  Section 301 shall take effect January 1, 1981 and
    29     its provisions shall remain in full force and effect for a
    30     period of 18 months after which time said provisions shall
    20060S1349B2136                 - 63 -     

     1     have no legal effect.
     2         (3)  Chapter 4 shall take effect July 1, 1982.
     3         (4)  All other provisions of this act shall take effect
     4     January 1, 1981.
     5     Section 15.  The Secretary of Labor and Industry shall
     6  transmit a notice for publication in the Pennsylvania Bulletin
     7  when the secretary is satisfied that all of the following have
     8  been enacted:
     9         (1)  The addition of sections 2, 3, 3.1, 3.2, 3.6(a),
    10     (b), (c), (d), (e) and (f)(1)(ii) and (iii) and (2), 4, 4.1,
    11     4.2, 5, 6, 7, 8, 9, 10, 11 and 12 of the act of April 27,
    12     1927 (P.L.465, No.299), referred to as the Fire and Panic
    13     Act.
    14         (2)  The reenactment of the act of May 2, 1929 (P.L.1518,
    15     No.452), referred to as the Elevator Regulation Law.
    16         (3)  The reenactment of the act of September 1, 1965
    17     (P.L.459, No.235), entitled, as amended, "An act requiring
    18     that certain buildings and facilities adhere to certain
    19     principles, standards and specifications to make the same
    20     accessible to and usable by persons with physical handicaps,
    21     and providing for enforcement."
    22         (4)  The reenactment of the act of July 9, 1976 (P.L.919,
    23     No.170), entitled "An act providing for the approval or
    24     disapproval of applications for a permit relating to the
    25     construction or maintenance of improvements to real estate."
    26         (5)  The reenactment of the act of December 15, 1980
    27     (P.L.1203, No.222), known as the Building Energy Conservation
    28     Act.
    29         (6)  The reenactment of the act of December 17, 1990
    30     (P.L.742, No.185), entitled "An act providing for restrooms
    20060S1349B2136                 - 64 -     

     1     in facilities where the public congregates; and requiring
     2     that restroom facilities be provided for women on an
     3     equitable basis."
     4         (7)  The reenactment of the act of December 19, 1990
     5     (P.L.1387, No.214), known as the Dry Cleaning Law.
     6         (8)  The repeal of the act of November 10, 1999 (P.L.491,
     7     No.45), known as the Pennsylvania Construction Code Act.
     8     Section 16.  This act shall take effect as follows:
     9         (1)  The following provisions shall take effect
    10     immediately:
    11             (i)  Section 15 of this act.
    12             (ii)  This section.
    13         (2)  The remainder of this act shall take effect upon
    14     publication of the notice under section 15 of this act.











    D22L43RLE/20060S1349B2136       - 65 -