HOUSE AMENDED
        PRIOR PRINTER'S NOS. 613, 911, 2174           PRINTER'S NO. 2188

THE GENERAL ASSEMBLY OF PENNSYLVANIA


SENATE BILL

No. 583 Session of 1977


        INTRODUCED BY GURZENDA, KURY, SWEENEY, MURRAY, MELLOW,
           MESSINGER, ROSS, O'PAKE, ORLANDO, STAUFFER, GEKAS, NOLAN,
           ZEMPRELLI, STAPLETON, SMITH, KELLEY, DUFFIELD, HANKINS,
           LEWIS AND COPPERSMITH, MARCH 28, 1977

        AS AMENDED ON THIRD CONSIDERATION, HOUSE OF REPRESENTATIVES,
           SEPTEMBER 27, 1978

                                     AN ACT

     1  Amending the act of April 9, 1929 (P.L.177, No.175), entitled     <--
     2     "An act providing for and reorganizing the conduct of the
     3     executive and administrative work of the Commonwealth by the
     4     Executive Department thereof and the administrative
     5     departments, boards, commissions, and officers thereof,
     6     including the boards of trustees of State Normal Schools, or
     7     Teachers Colleges; abolishing, creating, reorganizing or
     8     authorizing the reorganization of certain administrative
     9     departments, boards, and commissions; defining the powers and
    10     duties of the Governor and other executive and administrative
    11     officers, and of the several administrative departments,
    12     boards, commissions, and officers; fixing the salaries of the
    13     Governor, Lieutenant Governor, and certain other executive
    14     and administrative officers; providing for the appointment of
    15     certain administrative officers, and of all deputies and
    16     other assistants and employes in certain departments, boards,
    17     and commissions; and prescribing the manner in which the
    18     number and compensation of the deputies and all other
    19     assistants and employes of certain departments, boards and
    20     commissions shall be determined," requiring the Department of
    21     General Services to conduct cost analyses to utilize energy
    22     conservation building standards and the utilization of
    23     abundant fossil fuels or renewable resources in all new
    24     public buildings prior to construction.
    25  PROVIDING FOR THE REGULATION FOR ENERGY CONSERVATION PURPOSES OF  <--
    26     THE CONSTRUCTION OF BUILDINGS, THE ESTABLISHMENT OF A
    27     BUILDING ENERGY CONSERVATION COMMITTEE AND A BOARD ON
    28     VARIANCES, APPEALS AND FOR PENALTIES.
    29                         TABLE OF CONTENTS
    30  CHAPTER 1.  GENERAL PROVISIONS


     1     SECTION 101.  SHORT TITLE.
     2     SECTION 102.  LEGISLATIVE FINDINGS AND DECLARATION OF
     3                   PURPOSE.
     4     SECTION 103.  DEFINITIONS.
     5  CHAPTER 2.  ENERGY CONSERVATION STANDARDS
     6     SUBCHAPTER A.  GENERAL PROVISIONS
     7     SECTION 201.  PROVISIONS.
     8     SUBCHAPTER B.  PLANS AND SPECIFICATIONS
     9     SECTION 202.  SUBMISSION.
    10     SECTION 203.  CONTENTS.
    11     SUBCHAPTER C.  DEFINITIONS RELATING TO ENERGY CONSERVATION
    12                    STANDARDS
    13     SECTION 204.  DEFINITIONS RELATING TO STANDARDS.
    14     SUBCHAPTER D.  BUILDING ENVELOPE
    15     SECTION 205.  GENERAL PROVISIONS.
    16     SECTION 206.  CRITERIA FOR RESIDENTIAL BUILDINGS.
    17     SECTION 207.  OTHER BUILDINGS.
    18     SECTION 208.  AIR LEAKAGE.
    19     SUBCHAPTER E.  WARM AIR HEATING, VENTILATING AND AIR
    20                    CONDITIONING SYSTEMS AND EQUIPMENT
    21     SECTION 209.  GENERAL PROVISIONS.
    22     SECTION 210.  DESIGN REQUIREMENTS.
    23     SECTION 211.  COOLING WITH OUTDOOR AIR.
    24     SECTION 212.  MECHANICAL VENTILATION.
    25     SECTION 213.  SIMULTANEOUS HEATING AND COOLING.
    26     SECTION 214.  RECOVERED ENERGY.
    27     SECTION 215.  NEW ENERGY.
    28     SECTION 216.  REHEAT SYSTEMS.
    29     SECTION 217.  DUAL DUCT AND MULTIZONE SYSTEMS.
    30     SECTION 218.  RECOOLING SYSTEMS.
    31     SECTION 219.  MULTIPLE ZONES.
    32     SECTION 220.  CONCURRENT OPERATION.
    33     SECTION 221.  EQUIPMENT PERFORMANCE REQUIREMENTS.
    34     SECTION 222.  DUCT INSULATION.
    35     SECTION 223.  SYSTEM CONTROLS.
    36     SECTION 224.  STEAM AND HOT WATER HEATING PIPING.
    37     SUBCHAPTER F.  PLUMBING SYSTEMS
    38     SECTION 225.  PURPOSE.
    39     SECTION 226.  FIXTURES.
    40     SECTION 227.  INSULATION.
    41     SECTION 228.  EQUIPMENT.
    42     SECTION 229.  CONTROLS.
    43     SUBCHAPTER G.  ELECTRICAL SYSTEMS
    44     SECTION 230.  SYSTEM REQUIREMENTS.
    45     SUBCHAPTER H.  LIGHTING
    46     SECTION 231.  LIGHT POWER BUDGET.
    47     SECTION 232.  CALCULATION METHODS.
    48     SECTION 233.  BUILDING INTERIORS.
    49     SECTION 234.  BUILDING EXTERIORS.
    50     SECTION 235.  EXCEPTIONS TO CRITERIA.
    51     SECTION 236.  CALCULATION PROCEDURE.
    52     SUBCHAPTER I.  ALTERNATIVE SYSTEMS
    53     SECTION 237.  PERFORMANCE ALTERNATIVE.
    54     SECTION 238.  NONDEPLETABLE SOURCES.
    55     SECTION 239.  DOCUMENTATION.
    56     SUBCHAPTER J.  USE GROUP R-3 PRESCRIPTIVE STANDARDS
    57     SECTION 240.  MINIMUM INSULATION REQUIREMENTS FOR USE
    58                   GROUP R-3.
    59  CHAPTER 3.  APPLICATION OF STANDARDS:  ESTABLISHMENT OF

    19770S0583B2188                  - 2 -

     1              COMMITTEE AND PENALTIES
     2     SECTION 301.  MODIFICATION OF STANDARDS; CRITERIA.
     3     SECTION 302.  APPLICATION OF ENERGY CONSERVATION STANDARDS.
     4     SECTION 303.  ENERGY CONSERVATION MANUAL FOR BUILDINGS.
     5     SECTION 304.  BUILDING ENERGY CONSERVATION COMMITTEE.
     6     SECTION 305.  CERTIFICATION.
     7     SECTION 306.  USE GROUP R-3; NOTICE; WARRANTY.
     8     SECTION 307.  VARIANCES.
     9     SECTION 308.  BUILDING PERMITS.
    10     SECTION 309.  PERMITS FOR USE OR OCCUPANCY.
    11     SECTION 310.  FAILURE TO SUBMIT CERTIFICATION.
    12     SECTION 311.  INSPECTIONS.
    13     SECTION 312.  APPEALS.
    14     SECTION 313.  PENALTIES.
    15     SECTION 314.  ENFORCEMENT.
    16     SECTION 315.  CIVIL ACTION.
    17  CHAPTER 4.  ADOPTION OF FUTURE STANDARDS
    18     SECTION 401.  ADOPTION AND PROMULGATION OF STANDARDS.
    19  CHAPTER 5.  LOCAL ELECTION
    20     SECTION 501.  ELECTION; USE GROUP R-3.
    21     SECTION 502.  ELECTION; CITIES OF THE FIRST, SECOND AND
    22                   SECOND CLASS A.
    23     SECTION 503.  POWERS OF MUNICIPALITIES.
    24     SECTION 504.  VARIANCES.
    25     SECTION 505.  DISPOSITION OF FINES.
    26  CHAPTER 6.  REPORT TO GENERAL ASSEMBLY
    27     SECTION 601.  REPORT TO GENERAL ASSEMBLY
    28     SECTION 602.  EFFECTIVE DATE.

    29     The General Assembly of the Commonwealth of Pennsylvania
    30  hereby enacts as follows:
    31     Section 1.  Paragraph (9) of section 2401.1, act of April 9,   <--
    32  1929 (P.L.177, No.175), known as "The Administrative Code of
    33  1929," added July 22, 1975 (P.L.75, No.45) is amended to read:
    34     Section 2401.1.  Specific Powers of the Department of General
    35  Services.--In addition to all other powers and duties set forth
    36  in this act, the Department of General Services shall have the
    37  power, and its duty shall be:
    38     * * *
    39     (9)  To formulate and establish minimum specifications and
    40  standards for construction, room design, materials and utilities
    41  and to conduct appropriate costing analyses to make mandatory
    42  standards at least as energy conserving as "ASHRAE 90-75" and
    43  its subsequent revisions and to utilize where environmentally

    19770S0583B2188                  - 3 -

     1  acceptable coal and abundant nonrenewable energy resources, and
     2  renewable energy resources such as solar and solid waste over
     3  other exhaustible and vulnerable fossil fuels for all projects
     4  to be constructed by or the construction of which is subsidized
     5  in whole or in part by the Commonwealth and to be used by any
     6  department, board, agency, commission, or State supported
     7  institution, agency, or project; prior to construction for this
     8  purpose, the Department of General Services may establish a
     9  laboratory for testing new construction materials, procedures
    10  and systems and shall issue reports on the results of any such
    11  laboratory tests and shall request the approval of utilizing
    12  other nonrenewable and nonabundant fossil fuels as primary
    13  energy sources by the General Assembly prior to construction.
    14     * * *
    15     Section 2.  For the purposes of this amendatory act the
    16  following words and phrases as used in this amendatory act shall
    17  have the following meanings:
    18     Appropriate Costing Analyses--shall be defined as the initial
    19  cost of a building considered jointly with the long term
    20  operating and maintenance cost.
    21     ASHRAE 90-75--is the consensus standards for energy
    22  conservation in new building designs of the American Society of
    23  Heating, Refrigerating and Air Conditioning Engineers, Inc.
    24     Fossil Fuels--fuels which contain the remains of ancient
    25  plant and animal life (e.g. coal, oil, oil shale, tar sands,
    26  natural gas).
    27     Renewable Resources--is defined to be capable of being
    28  replaced by natural ecological cycles or sound management
    29  practices.
    30     Section 3.  This act shall take effect immediately.
    19770S0583B2188                  - 4 -

     1                             CHAPTER 1                              <--
     2                         GENERAL PROVISIONS
     3  SECTION 101.  SHORT TITLE.
     4     THIS ACT SHALL BE KNOWN AND MAY BE CITED AS THE "BUILDING
     5  ENERGY CONSERVATION ACT."
     6  SECTION 102.  LEGISLATIVE FINDINGS AND DECLARATION OF PURPOSE.
     7     (A)  FINDINGS.--THE LEGISLATURE HEREBY DETERMINES THAT:
     8         (1)  ENERGY SHORTAGES IN THE DOMESTIC SUPPLY PRESENT FAR-
     9     REACHING PROBLEMS THAT PROMISE TO PERSIST. THESE ENERGY
    10     SHORTAGES AFFECT THE CONTINUED EFFICIENT OPERATION OF THE
    11     COMMONWEALTH'S ECONOMY AND SOCIAL STRUCTURE.
    12         (2)  IT IS THE COMMONWEALTH'S RESPONSIBILITY TO PROVIDE
    13     FOR ENERGY CONSERVATION THROUGH REGULATION OF DESIGN AND
    14     CONSTRUCTION STANDARDS.
    15         (3)  THE LEGISLATURE INTENDS, BY THIS ACT, TO RESPOND TO
    16     THESE SHORTAGES BY DEVISING A SPECIFIC RESPONSIBLE ENERGY
    17     CONSERVATION POLICY FOR BUILDING SYSTEMS.
    18     (B)  PURPOSE.--THE PURPOSE OF THIS ACT IS TO GRANT TO THE
    19  COMMONWEALTH OF PENNSYLVANIA AND DIRECT IT TO EXERCISE SPECIFIC
    20  AUTHORITY IN BUILDING CONSTRUCTION TO ASSURE THAT SUCH
    21  CONSTRUCTION IS PERFORMED USING MATERIALS AND TECHNIQUES THAT
    22  WILL PROVIDE FOR ENERGY CONSERVATION IN THE FUTURE OPERATION AND
    23  MAINTENANCE OF SAID BUILDINGS.
    24  SECTION 103.  DEFINITIONS.
    25     THE FOLLOWING WORDS AND PHRASES WHEN USED IN THIS ACT SHALL
    26  HAVE, UNLESS THE CONTEXT CLEARLY INDICATES OTHERWISE, THE
    27  MEANINGS GIVEN TO THEM IN THIS SECTION:
    28     "BUILDING."  ANY STRUCTURE THAT PROVIDES FACILITIES OR
    29  SHELTER FOR PUBLIC ASSEMBLY OR FOR EDUCATIONAL, BUSINESS,
    30  MERCANTILE, INSTITUTIONAL, WAREHOUSE OR RESIDENTIAL OCCUPANCY,
    19770S0583B2188                  - 5 -

     1  OR INDUSTRIAL USE INCLUDING, BUT NOT LIMITED TO, THOSE PORTIONS
     2  OF FACTORY AND INDUSTRIAL OCCUPANCY SUCH AS OFFICE SPACE EXCEPT
     3  FOR:
     4         (1)  BUILDINGS AND STRUCTURES OR PORTIONS THEREOF WHOSE
     5     PEAK DESIGN RATE OF ENERGY USAGE IS LESS THAN ONE WATT PER
     6     SQUARE FOOT OR 3.4 BTU/HR PER SQUARE FOOT OF FLOOR AREA FOR
     7     ALL PURPOSES.
     8         (2)  STRUCTURES OR THOSE PORTIONS OF STRUCTURES USED FOR
     9     MANUFACTURING OR PROCESSING AND WHOSE MANUFACTURING OR
    10     PROCESSING PROCEDURES REQUIRE THE USE OF SUBSTANTIAL HEAT
    11     PRODUCING ENERGY OR COOLING TO CREATE THEIR PRODUCT.
    12         (3)  BUILDINGS WHICH ARE NEITHER HEATED NOR COOLED.
    13         (4)  HISTORIC BUILDINGS.
    14         (5)  BUILDINGS OWNED BY THE FEDERAL GOVERNMENT.
    15     "CONSTRUCTION."  THE ERECTION, FABRICATION OR RENOVATION OF A
    16  BUILDING.
    17     "DEPARTMENT."  THE PENNSYLVANIA DEPARTMENT OF LABOR AND
    18  INDUSTRY EXCEPT THAT FOR ALL UNITS SUBJECT TO THE ACT OF MAY 11,
    19  1972 (P.L.286, NO.70), KNOWN AS THE "INDUSTRIALIZED HOUSING
    20  ACT," ALL UNITS SUBJECT TO THE ACT OF MAY 11, 1972 (P.L.281,
    21  NO.69), KNOWN AS THE "UNIFORM STANDARDS CODE FOR MOBILE HOMES,"
    22  AND ALL BUILDINGS CLASSIFIED AS USE GROUP R-3, HEREIN,
    23  DEPARTMENT MEANS THE PENNSYLVANIA DEPARTMENT OF COMMUNITY
    24  AFFAIRS.
    25     "DESIGN."  CALCULATIONS AND RESULTANT DRAWINGS AND
    26  SPECIFICATIONS WHICH ARE USED FOR THE CONSTRUCTION OF A
    27  BUILDING.
    28     "HISTORIC BUILDING."  ANY BUILDING DETERMINED BY THE STATE
    29  HISTORIC PRESERVATION OFFICER TO MEET THE CRITERIA FOR LISTING
    30  ON THE NATIONAL REGISTER OF HISTORIC PLACES BUT ONLY TO THE
    19770S0583B2188                  - 6 -

     1  EXTENT THAT COMPLIANCE WITH THIS ACT WOULD PREVENT PRESERVATION
     2  OF THE HISTORIC OR ARCHITECTURAL INTEGRITY OF THE BUILDING.
     3     "LICENSED DESIGN PROFESSIONAL."  A PERSON LICENSED AS AN
     4  ARCHITECT OR PROFESSIONAL ENGINEER PURSUANT TO THE APPROPRIATE
     5  LICENSURE ACT.
     6     "LIFE-CYCLE COST."  THE COST OF A BUILDING INCLUDING ITS
     7  INITIAL COST, THE COST OF THE ENERGY CONSUMED OVER ITS ECONOMIC
     8  LIFE AND THE COST OF ITS OPERATION AND MAINTENANCE.
     9     "MUNICIPALITY."  A CITY, BOROUGH, INCORPORATED TOWN OR
    10  TOWNSHIP.
    11     "PERFORMANCE STANDARDS."  PARAMETERS WITHIN WHICH DESIGNERS
    12  OF BUILDINGS SHALL WORK. THE SPECIFIC PRACTICES THAT A DESIGNER
    13  EMPLOYS SHALL NOT BE PRESCRIBED AS LONG AS THE RESULT IS WITHIN
    14  THE PARAMETERS ESTABLISHED BY THE STANDARDS.
    15     "RENOVATION."  (A)  THE REHABILITATION OF AN EXISTING
    16  BUILDING WHICH REQUIRES MORE THAN 25% OF THE GROSS FLOOR AREA OR
    17  VOLUME OF THE ENTIRE BUILDING TO BE REBUILT. COSMETIC WORK SUCH
    18  AS PAINTING, WALL COVERING, WALL PANELING, FLOOR COVERING, AND
    19  SUSPENDED CEILING WORK SHALL NOT BE INCLUDED; OR
    20     (B)  ANY ADDITION TO AN EXISTING BUILDING: PROVIDED, HOWEVER,
    21  THAT THE PROVISIONS OF THIS ACT SHALL ONLY APPLY TO SUCH PORTION
    22  OF THE BUILDING BEING RENOVATED AND NOT TO THE ENTIRE BUILDING.
    23                             CHAPTER 2
    24                   ENERGY CONSERVATION STANDARDS
    25                            SUBCHAPTER A
    26                         GENERAL PROVISIONS
    27  SECTION 201.  PROVISIONS.
    28     EXCEPT FOR USE GROUP R-3, THE FOLLOWING PROVISIONS REGULATE
    29  THE DESIGN AND CONSTRUCTION OF THE EXTERIOR ENVELOPES AND
    30  SELECTION OF HVAC, SERVICE WATER HEATING, ELECTRICAL
    19770S0583B2188                  - 7 -

     1  DISTRIBUTION, AND ILLUMINATION SYSTEMS AND EQUIPMENT REQUIRED
     2  FOR THE PURPOSE OF EFFECTIVE USE OF ENERGY AND SHALL GOVERN THE
     3  CONSTRUCTION OF ALL BUILDINGS, OR PORTIONS THEREOF, AS PROVIDED
     4  HEREIN.
     5     THE PROVISIONS REGULATING THE CONSTRUCTION OF BUILDINGS
     6  CLASSIFIED AS USE GROUP R-3 ARE CONTAINED IN SUBCHAPTER J,
     7  SECTION 240.
     8                            SUBCHAPTER B
     9                      PLANS AND SPECIFICATIONS
    10  SECTION 202.  SUBMISSION.
    11     (A)  PLANS.--PLANS, SPECIFICATIONS, COMPUTATIONS WHERE
    12  NECESSARY, AND ANY CHANGES THERETO TOGETHER WITH THE NECESSARY
    13  CERTIFICATION REQUIRED BY SECTION 305 SHALL BE SUBMITTED FOR ALL
    14  BUILDINGS EXCEPT THOSE CLASSIFIED AS USE GROUP R-3 TO INDICATE
    15  CONFORMANCE WITH THIS CHAPTER AND OTHER APPLICABLE CHAPTERS OF
    16  THIS ACT, EXCEPT AS PROVIDED IN SUBSECTIONS (B) AND (C).
    17     (B)  STANDARD DESIGN.--WHENEVER A PERSON IS CONSTRUCTING A
    18  BUILDING IN ACCORDANCE WITH PLANS, SPECIFICATIONS AND
    19  COMPUTATIONS WHICH HE HAS SUBMITTED WITHIN THE PREVIOUS TWO
    20  YEARS, SUCH PLANS NEED NOT BE RESUBMITTED BUT SUCH PERSON SHALL
    21  INDICATE UPON THE CERTIFICATE REQUIRED BY SECTION 305 THAT THEY
    22  MEET THE STANDARDS CURRENTLY IN EFFECT AND IDENTIFY THE
    23  PREVIOUSLY SUBMITTED PLANS, SPECIFICATIONS AND COMPUTATIONS.
    24     (C)  PRESCRIPTIVE STANDARDS.--WHEN THE PRESCRIPTIVE STANDARDS
    25  PROVIDED IN THE ENERGY CONSERVATION MANUAL ESTABLISHED BY
    26  SECTION 303 ARE EMPLOYED IN THE CONSTRUCTION OF A BUILDING ONLY
    27  SUCH INFORMATION AS SHALL BE REQUIRED BY THE DEPARTMENT SHALL BE
    28  SUBMITTED. THE PRESCRIPTIVE STANDARDS APPLICABLE TO USE GROUP R-
    29  3, BUILDINGS ARE CONTAINED IN SECTION 240.
    30  SECTION 203.  CONTENTS.
    19770S0583B2188                  - 8 -

     1     THE PLANS AND SPECIFICATIONS, WHERE REQUIRED BY SECTION 202,
     2  SHALL SHOW IN SUFFICIENT DETAIL ALL PERTINENT DATA AND FEATURES
     3  OF THE BUILDING AND THE EQUIPMENT AND SYSTEMS AS HEREIN
     4  GOVERNED, INCLUDING BUT NOT LIMITED TO: EXTERIOR ENVELOPE
     5  COMPONENT MATERIALS, U VALUES OF ELEMENTS, R VALUES OF
     6  INSULATING MATERIALS, SIZE AND TYPE OF APPARATUS AND EQUIPMENT,
     7  EQUIPMENT AND SYSTEM CONTROLS AND OTHER PERTINENT DATA TO
     8  INDICATE CONFORMANCE WITH THE REQUIREMENTS HEREIN.
     9                            SUBCHAPTER C
    10                      DEFINITIONS RELATING TO
    11                   ENERGY CONSERVATION STANDARDS
    12  SECTION 204.  DEFINITIONS RELATING TO STANDARDS.
    13     THE FOLLOWING WORDS AND PHRASES WHEN USED IN THIS CHAPTER
    14  SHALL HAVE, UNLESS THE CONTEXT CLEARLY INDICATES OTHERWISE, THE
    15  MEANINGS GIVEN TO THEM IN THIS SECTION:
    16     "COEFFICIENT OF BEAM UTILIZATION" (CBU).  THE RATIO OF THE
    17  LUMINOUS FLUX (LUMENS) REACHING A SPECIFIED AREA DIRECTLY FROM A
    18  FLOODLIGHT OR PROJECTOR TO THE TOTAL BEAM LUMINOUS FLUX.
    19     "COEFFICIENT OF PERFORMANCE" (COP) - COOLING. THE RATIO OF
    20  THE RATE OF NET HEAT REMOVAL TO THE RATE OF TOTAL ENERGY INPUT,
    21  EXPRESSED IN CONSISTENT UNITS AND UNDER DESIGNATED RATING
    22  CONDITIONS.
    23     "COEFFICIENT OF PERFORMANCE" (COP) - HEAT PUMP, HEATING. THE
    24  RATIO OF THE RATE OF NET HEAT OUTPUT TO THE RATE OF TOTAL ENERGY
    25  INPUT, EXPRESSED IN CONSISTENT UNITS AND UNDER DESIGNATED RATING
    26  CONDITIONS.
    27     THE RATE OF NET HEAT OUTPUT SHALL BE DEFINED AS THE CHANGE IN
    28  THE TOTAL HEAT CONTENTS OF THE AIR ENTERING AND LEAVING THE
    29  EQUIPMENT NOT INCLUDING SUPPLEMENTARY HEAT.
    30     TOTAL ENERGY INPUT SHALL BE DETERMINED BY COMBINING THE
    19770S0583B2188                  - 9 -

     1  ENERGY INPUTS TO ALL ELEMENTS, EXCEPT SUPPLEMENTARY HEATERS, OF
     2  THE HEAT PUMP, INCLUDING, BUT NOT LIMITED TO, COMPRESSORS,
     3  PUMPS, SUPPLY AIR FANS, RETURN AIR FANS, OUTDOOR AIR FANS,
     4  COOLING TOWER FANS AND THE HEATING, VENTILATING AND AIR
     5  CONDITIONING SYSTEM EQUIPMENT CONTROL CIRCUIT.
     6     "COEFFICIENT OF UTILIZATION" (CU).  THE RATIO OF THE LUMINOUS
     7  FLUX (LUMENS) FROM A LUMINAIRE RECEIVED ON THE WORK PLANE TO THE
     8  LUMENS EMITTED BY THE LUMINAIRE'S LAMPS ALONE.
     9     "COLOR RENDITION."  GENERAL EXPRESSION FOR THE EFFECT OF A
    10  LIGHT SOURCE ON THE COLOR. APPEARANCE OF OBJECTS IN CONSCIOUS OR
    11  SUBCONSCIOUS COMPARISON WITH THEIR COLOR APPEARANCE UNDER A
    12  REFERENCE LIGHT SOURCE.
    13     "DEGREE DAY, HEATING."  A UNIT, BASED UPON TEMPERATURE
    14  DIFFERENCE AND TIME, USED IN ESTIMATING FUEL CONSUMPTION AND
    15  SPECIFYING NOMINAL HEATING LOAD OF A BUILDING IN WINTER. FOR ANY
    16  ONE DAY, WHEN THE MEAN TEMPERATURE IS LESS THAN 65 F., THERE
    17  EXIST AS MANY DEGREE DAYS AS THERE ARE FAHRENHEIT DEGREES
    18  DIFFERENCE IN TEMPERATURE BETWEEN THE MEAN TEMPERATURE FOR THE
    19  DAY AND 65 F.
    20     "ENERGY EFFICIENCY RATIO" (EER).  THE RATIO OF NET COOLING
    21  CAPACITY IN BTUH TO TOTAL RATE OF ELECTRIC INPUT IN WATTS UNDER
    22  DESIGNATED OPERATING CONDITIONS.
    23     "EQUIVALENT SPHERE ILLUMINATION" (ESI).  THE LEVEL OF SPHERE
    24  ILLUMINATION WHICH WOULD PRODUCE TASK VISIBILITY EQUIVALENT TO
    25  THAT PRODUCED BY A SPECIFIC LIGHTING ENVIRONMENT.
    26     "EXTERIOR ENVELOPE."  THE ELEMENTS OF A BUILDING WHICH
    27  ENCLOSE CONDITIONED SPACES THROUGH WHICH THERMAL ENERGY MAY BE
    28  TRANSFERRED TO OR FROM THE EXTERIOR.
    29     "FLOODLIGHTING."  A LIGHTING SYSTEM DESIGNATED TO LIGHT AN
    30  AREA USING PROJECTOR TYPE LUMINAIRES USUALLY CAPABLE OF BEING
    19770S0583B2188                 - 10 -

     1  POINTED IN ANY DIRECTION.
     2     "FLOOR AREA, GROSS."  GROSS FLOOR AREA SHALL BE THE FLOOR
     3  AREA WITHIN THE PERIMETER OF THE OUTSIDE WALLS OF THE BUILDING
     4  UNDER CONSIDERATION, WITHOUT DEDUCTION FOR HALLWAYS, STAIRS,
     5  CLOSETS, THICKNESS OF WALLS, COLUMNS OR OTHER FEATURES.
     6     "ILLUMINATION."  THE DENSITY OF THE LUMINOUS FLUX INCIDENT ON
     7  A SURFACE. IT IS THE QUOTIENT OF THE LUMINOUS FLUX BY THE AREA
     8  OF THE SURFACE WHEN THE LATTER IS UNIFORMLY ILLUMINATED.
     9     "LIGHT LOSS FACTOR" (LLF).  A FACTOR USED IN CALCULATING THE
    10  LEVEL OF ILLUMINATION AFTER A GIVEN PERIOD OF TIME AND UNDER
    11  GIVEN CONDITIONS. IT TAKES INTO ACCOUNT TEMPERATURE AND VOLTAGE
    12  VARIATIONS, DIRT ACCUMULATION ON LUMINAIRE AND ROOM SURFACES,
    13  LAMP DEPRECIATION, MAINTENANCE PROCEDURES AND ATMOSPHERE
    14  CONDITIONS.
    15     "LUMINAIRE."  A COMPLETE LIGHTING UNIT CONSISTING OF A LAMP
    16  OR LAMPS TOGETHER WITH THE PARTS DESIGNED TO DISTRIBUTE THE
    17  LIGHT, TO POSITION AND PROTECT THE LAMPS AND TO CONNECT THE
    18  LAMPS TO THE POWER SUPPLY.
    19     "MULTIGLAZING."  AN ARRANGEMENT WHEREBY TWO OR MORE SHEETS OF
    20  GLAZING MATERIAL ARE AFFIXED IN OR ON TO A WINDOW FRAME TO
    21  CREATE ONE OR MORE CLOSED INSULATING AIR SPACES. MULTIGLAZING
    22  CAN BE ACHIEVED BY INSTALLING A PREASSEMBLED SEALED INSULATING
    23  GLASS UNIT, CONSISTING OF TWO OR MORE LAYERS OF GLAZING
    24  MATERIALS WITH INSULATING, CLOSED AIR SPACE IN BETWEEN, OR BY
    25  AFFIXING ONE OR MORE ADDITIONAL GLAZING MATERIALS ONTO A SINGLE
    26  GLAZED WINDOW SASH, CREATING ONE OR MORE CLOSED INSULATING AIR
    27  SPACES.
    28     "PACKAGED TERMINAL AIR CONDITIONER."  A FACTORY SELECTED
    29  COMBINATION OF HEATING AND COOLING COMPONENTS, ASSEMBLIES OR
    30  SECTIONS, INTENDED TO SERVE A ROOM OR ZONE.
    19770S0583B2188                 - 11 -

     1     "POWER."  IN CONNECTION WITH MACHINES, POWER IS THE TIME RATE
     2  OF DOING WORK. IN CONNECTION WITH THE TRANSMISSION OF ENERGY OF
     3  ALL TYPES, POWER REFERS TO THE RATE AT WHICH ENERGY IS
     4  TRANSMITTED; IN CUSTOMARY UNITS, IT IS MEASURED IN WATTS (W) OR
     5  BRITISH THERMAL UNITS PER HOUR (BTUH) AND IN SI UNITS IS
     6  MEASURED IN WATTS (W).
     7     "REFLECTANCE."  THE RATIO OF THE LIGHT REFLECTED BY A SURFACE
     8  TO THE LIGHT FALLING UPON IT.
     9     "REHEAT."  THE APPLICATION OF SENSIBLE HEAT TO SUPPLY AIR
    10  THAT HAS BEEN PREVIOUSLY COOLED BELOW THE TEMPERATURE OF THE
    11  CONDITIONED SPACE BY EITHER MECHANICAL REFRIGERATION OR THE
    12  INTRODUCTION OF OUTDOOR AIR TO PROVIDE COOLING.
    13     "RESIDENTIAL BUILDINGS."  ALL BUILDINGS AND STRUCTURES OR
    14  PARTS THEREOF SHALL BE CLASSIFIED IN THE RESIDENTIAL (R) USE
    15  GROUP IN WHICH FAMILIES OR HOUSEHOLDS LIVE, OR IN WHICH SLEEPING
    16  ACCOMMODATIONS ARE PROVIDED FOR INDIVIDUALS WITH OR WITHOUT
    17  DINING FACILITIES, EXCLUDING THOSE THAT ARE CLASSIFIED AS
    18  INSTITUTIONAL BUILDINGS. RESIDENTIAL BUILDINGS SHALL BE
    19  CLASSIFIED AS FOLLOWS:
    20     (1)  USE GROUP R-1 STRUCTURES.  THIS USE GROUP SHALL INCLUDE
    21  ALL HOTEL AND MOTEL BUILDINGS, LODGING HOUSES, BOARDING HOUSES
    22  AND DORMITORY BUILDINGS ARRANGED FOR THE SHELTER AND SLEEPING
    23  ACCOMMODATION OF MORE THAN 20 INDIVIDUALS.
    24     (2)  USE GROUP R-2 STRUCTURES.  THIS USE GROUP SHALL INCLUDE
    25  ALL MULTIPLE-FAMILY DWELLINGS HAVING MORE THAN TWO DWELLING
    26  UNITS; AND SHALL ALSO INCLUDE ALL DORMITORIES, BOARDING AND
    27  LODGING HOUSES ARRANGED FOR SHELTER AND SLEEPING ACCOMMODATION
    28  BY MORE THAN FIVE AND NOT MORE THAN 20 INDIVIDUALS.
    29     (3) USE GROUP R-3 STRUCTURES.  THIS USE GROUP SHALL INCLUDE
    30  ALL BUILDINGS ARRANGED FOR THE USE OF ONE OR TWO FAMILY DWELLING
    19770S0583B2188                 - 12 -

     1  UNITS INCLUDING NOT MORE THAN FIVE LODGERS OR BOARDERS PER
     2  FAMILY.
     3     "RESISTANCE, THERMAL" (R).  A MEASURE OF THE ABILITY TO
     4  RETARD THE FLOW OF HEAT. THE R VALUE IS THE RECIPROCAL OF A HEAT
     5  TRANSFER COEFFICIENT, AS EXPRESSED BY U.  (R = 1/U).
     6     "THERMAL TRANSMITTANCE" (U).  OVERALL COEFFICIENT OF HEAT
     7  TRANSMISSION OR THERMAL TRANSMITTANCE (AIR TO AIR) EXPRESSED IN
     8  UNITS OF BTU PER HOUR PER SQUARE FOOT PER DEGREE F.  IT IS THE
     9  TIME RATE OF HEAT FLOW. THE U VALUE APPLIES TO COMBINATIONS OF
    10  DIFFERENT MATERIALS USED IN SERIES ALONG THE HEAT FLOW PATH AND
    11  ALSO TO SINGLE MATERIALS THAT COMPRISE A BUILDING SECTION AND
    12  INCLUDE CAVITY AIR SPACES AND SURFACE AIR FILMS ON BOTH SIDES.
    13     "THERMAL TRANSMITTANCE" (UO).  OVERALL (AVERAGE) HEAT
    14  TRANSMISSION OR THERMAL TRANSMITTANCE OF A GROSS AREA OF THE
    15  EXTERIOR BUILDING ENVELOPE, EXPRESSED IN UNITS OF BTU PER HOUR
    16  PER SQUARE FOOT PER DEGREE F.
    17     THE UO VALUE APPLIES TO THE COMBINED EFFECT OF THE TIME RATE
    18  OF HEAT FLOWS THROUGH THE VARIOUS PARALLEL PATHS, SUCH AS
    19  WINDOWS, DOORS AND OPAQUE CONSTRUCTION AREAS, COMPRISING THE
    20  GROSS AREA OF ONE OR MORE EXTERIOR BUILDING COMPONENTS, SUCH AS
    21  WALLS, FLOOR OR ROOF/CEILING.
    22     "THERMOSTAT."  AN INSTRUMENT WHICH MEASURES CHANGES IN
    23  TEMPERATURE AND CONTROLS DEVICES FOR MAINTAINING A DESIRED
    24  TEMPERATURE.
    25     "VEILING REFLECTIONS."  REGULAR REFLECTIONS SUPERIMPOSED UPON
    26  DIFFUSE REFLECTIONS FROM AN OBJECT THAT PARTIALLY OR TOTALLY
    27  OBSCURE THE DETAILS TO BE SEEN BY REDUCING THE CONTRAST. THIS
    28  SOMETIMES IS CALLED "REFLECTED GLARE."
    29     "WINDOW MANAGEMENT."  ANY ONE OR COMBINATION OF ACTS AND
    30  ACTIVITIES WHOSE PURPOSE IS TO TAKE MAXIMUM ADVANTAGE OF THE
    19770S0583B2188                 - 13 -

     1  ENERGY CONSERVING ASPECTS OF UTILIZING SOLAR ENERGY TO HEAT A
     2  BUILDING AND/OR UTILIZE SOLAR ILLUMINATION WITHIN A BUILDING TO
     3  AUGMENT ENERGY-CONSUMING LIGHTING SYSTEMS. SUCH ACTS AND
     4  ACTIVITIES INCLUDE, BUT ARE NOT LIMITED TO, BUILDING-WINDOW
     5  SITING AND ORIENTATION, SELECTION OF GLAZING MATERIALS, DESIGN
     6  OF OVERHANGS, SUN SCREENS OR PLACEMENT OF SHRUBBERY.
     7     "WORK PLANE."  THE PLANE AT WHICH WORK USUALLY IS DONE AND AT
     8  WHICH THE ILLUMINATION IS SPECIFIED AND MEASURED. UNLESS
     9  OTHERWISE INDICATED, THIS IS ASSUMED TO BE A HORIZONTAL PLANE 30
    10  IN. (0.76 M) ABOVE THE FLOOR.
    11     "ZONE."  A SPACE OR GROUP OF SPACES WITHIN A BUILDING WITH
    12  HEATING OR COOLING REQUIREMENTS SUFFICIENTLY SIMILAR SO THAT
    13  COMFORT CONDITIONS CAN BE MAINTAINED THROUGHOUT BY A SINGLE
    14  CONTROLLING DEVICE.
    15                            SUBCHAPTER D
    16                         BUILDING ENVELOPE
    17  SECTION 205.  GENERAL PROVISIONS.
    18     (A)  PURPOSE OF SUBCHAPTER.--THE INTENT OF THIS SUBCHAPTER IS
    19  TO PROVIDE MINIMUM REQUIREMENTS FOR EXTERIOR ENVELOPE
    20  CONSTRUCTION IN THE INTEREST OF ENERGY CONSERVATION.
    21     IN ADDITION TO THE CRITERIA SET FORTH IN THIS SUBCHAPTER
    22  PROVISIONS SHALL BE MADE TO MAXIMIZE THE ENERGY CONSERVING
    23  BENEFITS OF SOLAR DAYLIGHT AND PASSIVE SOLAR HEAT GAIN THROUGH
    24  WINDOW MANAGEMENT. THE PROPOSED DESIGN MAY ALSO TAKE INTO
    25  CONSIDERATION THE THERMAL MASS OF THE BUILDING IN CONSIDERING
    26  ENERGY CONSERVATION. THE ADMINISTERING AGENCY SHALL PROVIDE THE
    27  GUIDELINES NECESSARY TO IMPLEMENT THESE PROVISIONS.
    28     (B)  THERMAL PERFORMANCE.--ALL BUILDINGS AND STRUCTURES THAT
    29  ARE HEATED OR MECHANICALLY COOLED SHALL BE CONSTRUCTED SO AS TO
    30  PROVIDE THE REQUIRED THERMAL PERFORMANCE OF THE VARIOUS
    19770S0583B2188                 - 14 -

     1  COMPONENTS.
     2     THE REQUIRED THERMAL TRANSMITTANCE VALUE (UO) OF ANY ONE
     3  COMPONENT, SUCH AS ROOF/CEILING, WALL OR FLOOR MAY BE INCREASED
     4  AND THE UO VALUE FOR OTHER COMPONENTS DECREASED PROVIDED THAT
     5  THE OVERALL HEAT GAIN OR LOSS FOR THE ENTIRE BUILDING ENVELOPE
     6  DOES NOT EXCEED THE TOTAL RESULTING FROM CONFORMANCE TO THE
     7  REQUIRED UO VALUES.
     8     (C)  DIFFERENT REQUIREMENTS.--A BUILDING THAT IS DESIGNED TO
     9  BE BOTH HEATED AND COOLED SHALL MEET THE MORE STRINGENT OF THE
    10  HEATING OR COOLING REQUIREMENTS OF THE EXTERIOR ENVELOPE AS
    11  PROVIDED IN THIS SUBCHAPTER WHEN REQUIREMENTS DIFFER.
    12     (D)  EXTERIOR WALLS.--FOR THE PURPOSE OF THIS SUBCHAPTER THE
    13  GROSS AREA OF EXTERIOR WALLS CONSISTS OF ALL OPAQUE WALL AREAS,
    14  INCLUDING FOUNDATION WALLS ABOVE GRADE, PERIPHERAL EDGES OF
    15  FLOORS, WINDOW AREAS INCLUDING SASH, AND DOOR AREAS, WHERE SUCH
    16  SURFACES ARE EXPOSED TO OUTDOOR AIR AND ENCLOSE A HEATED OR
    17  MECHANICALLY COOLED SPACE.
    18     (E)  ROOF ASSEMBLY.--FOR THE PURPOSE OF THIS SUBCHAPTER A
    19  ROOF ASSEMBLY SHALL BE CONSIDERED AS ALL COMPONENTS OF THE
    20  ROOF/CEILING ENVELOPE THROUGH WHICH HEAT FLOWS, THEREBY CREATING
    21  A BUILDING TRANSMISSION HEAT LOSS OR GAIN, WHERE SUCH ASSEMBLY
    22  IS EXPOSED TO OUTDOOR AIR AND ENCLOSES A HEATED OR MECHANICALLY
    23  COOLED SPACE.
    24     THE GROSS AREA OF A ROOF ASSEMBLY CONSISTS OF THE TOTAL
    25  INTERIOR SURFACE OF SUCH ASSEMBLY, INCLUDING SKYLIGHTS, EXPOSED
    26  TO THE HEATED OR MECHANICALLY COOLED SPACE.
    27     WHERE AIR CEILING PLENUMS ARE EMPLOYED, THE ROOF OR CEILING
    28  ASSEMBLY SHALL:
    29         (1)  FOR THERMAL TRANSMITTANCE PURPOSES NOT INCLUDE THE
    30     CEILING PROPER NOR THE PLENUM SPACE AS PART OF THE ASSEMBLY.
    19770S0583B2188                 - 15 -

     1         (2)  FOR GROSS AREA PURPOSES BE BASED UPON THE INTERIOR
     2     FACE OF THE UPPER PLENUM SURFACE.
     3  SECTION 206.  CRITERIA FOR RESIDENTIAL BUILDINGS.
     4     (A)  APPLICABILITY.--THE REQUIREMENTS HEREIN SHALL APPLY TO
     5  ALL BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OF USE GROUPS
     6  R-1 AND R-2 AND R-3 THAT ARE HEATED OR MECHANICALLY COOLED WHEN   <--
     7  NOT MORE THAN 3 STORIES OR 40 FEET IN HEIGHT.
     8     (B)  WALLS.--THE GROSS AREA OF EXTERIOR WALLS ABOVE GRADE,
     9  INCLUDING FOUNDATION WALLS, SHALL HAVE A COMBINED THERMAL
    10  TRANSMITTANCE VALUE (UO) NOT EXCEEDING THOSE SPECIFIED IN TABLE
    11  1.
    12                              TABLE 1
    13                 MAXIMUM ALLOWABLE "UO" VALUES FOR
    14                   GROSS EXTERIOR WALL ASSEMBLIES
    15                                       DETACHED         ALL OTHER
    16     ANNUAL HEATING DEGREE DAYS*   ONE & TWO FAMILY    RESIDENTIAL
    17                 4000                    0.25             0.31
    18                 5000                    0.23             0.29
    19                 6000                    0.22             0.27
    20                 7000                    0.20             0.26
    21     *AS SPECIFIED IN CHAPTER 43 ASHRAE HANDBOOK-SYSTEMS.
    22     (C)  ROOF/CEILING.--THE ROOF/CEILING ASSEMBLIES SHALL HAVE A
    23  COMBINED THERMAL TRANSMITTANCE VALUE (UO) NOT TO EXCEED 0.05
    24  EXCEPT THAT ROOF/CEILING ASSEMBLIES IN WHICH THE FINISHED
    25  INTERIOR SURFACE IS ESSENTIALLY THE UNDERSIDE OF THE ROOF DECK,
    26  SUCH AS A WOODEN CATHEDRAL CEILING, MAY HAVE A "UO" VALUE NOT TO
    27  EXCEED 0.08. THESE VALUES PRESUME NO SIGNIFICANT THERMAL
    28  TRANSMISSION THROUGH FRAMING MEMBERS, SKYLIGHTS OR OTHER
    29  INTERRUPTIONS IN THE ROOF ENVELOPE. IF SUCH INTERRUPTIONS OCCUR,
    30  CALCULATIONS MUST BE MADE SHOWING CONFORMANCE TO THE REQUIRED
    19770S0583B2188                 - 16 -

     1  "UO" VALUES.
     2     (D)  FLOORS OVER UNHEATED SPACES.--THE FLOOR OF A HEATED OR
     3  MECHANICALLY COOLED SPACE LOCATED OVER AN UNHEATED SPACE SHALL
     4  HAVE A COMBINED THERMAL TRANSMITTANCE VALUE (UO) NOT TO EXCEED
     5  0.08.
     6     (E)  SLAB-ON GRADE FLOORS.--
     7         (1)  FOR SLAB-ON GRADE FLOORS, THE PERIMETER OF THE FLOOR
     8     SHALL BE INSULATED WITH A MATERIAL HAVING A THERMAL
     9     RESISTANCE VALUE (R) NOT LESS THAN THOSE SPECIFIED IN TABLE
    10     2.
    11                              TABLE 2
    12             MINIMUM ALLOWABLE "R" VALUES OF PERIMETER
    13                INSULATION FOR SLAB-ON GRADE FLOORS
    14     ANNUAL HEATING DEGREE DAYS      HEATED SLAB     UNHEATED SLAB
    15                 4000*                   5.5             3.5
    16                 5000                    6.3             4.2
    17                 6000                    7.0             4.9
    18                 7000                    7.8             5.5
    19     *TABLE VALUES MAY BE INTERPOLATED.
    20         (2)  THE INSULATION SHALL EXTEND DOWNWARD FROM THE TOP OF
    21     THE SLAB FOR A MINIMUM DISTANCE OF 24 INCHES OR DOWNWARD TO
    22     THE BOTTOM OF THE SLAB THEN HORIZONTALLY BENEATH THE SLAB FOR
    23     A MINIMUM TOTAL DISTANCE OF 24 INCHES.
    24  SECTION 207.  OTHER BUILDINGS.
    25     (A)  COVERAGE.--THE HEATING AND COOLING REQUIREMENTS HEREIN
    26  SHALL GOVERN ALL BUILDINGS AND STRUCTURES OR PORTIONS THEREOF
    27  OTHER THAN DEFINED BY SECTION 206.
    28     (B)  HEATING CRITERIA FOR WALLS.--ALL BUILDINGS AND
    29  STRUCTURES THAT ARE HEATED SHALL HAVE A COMBINED THERMAL
    30  TRANSMITTANCE VALUE (UO) FOR THE GROSS AREA OF EXTERIOR WALLS
    19770S0583B2188                 - 17 -

     1  NOT EXCEEDING THOSE SPECIFIED IN TABLE 3.
     2                              TABLE 3
     3                   MAXIMUM ALLOWABLE "UO" VALUES
     4                 FOR GROSS EXTERIOR WALL ASSEMBLIES
     5                                     3 STORIES OR    MORE THAN
     6     ANNUAL HEATING DEGREE DAYS     40 FT. OR LESS  3 STORIES OR
     7                                                       40 FT.
     8                 4000                    0.31            0.38
     9                 5000                    0.29            0.36
    10                 6000                    0.27            0.33
    11                 7000                    0.26            0.31
    12     (C)  HEATING CRITERIA FOR ROOF/CEILING.--ALL BUILDINGS AND
    13  STRUCTURES THAT ARE HEATED SHALL HAVE COMBINED THERMAL
    14  TRANSMITTANCE VALUE (UO) FOR ROOF/CEILING ASSEMBLIES NOT
    15  EXCEEDING THOSE SPECIFIED IN TABLE 4.
    16                              TABLE 4
    17                   MAXIMUM ALLOWABLE "UO" VALUES
    18                    FOR ROOF/CEILING ASSEMBLIES
    19     ANNUAL HEATING DEGREE DAYS              MAXIMUM UO
    20             4000*                              0.092
    21             5000                               0.084
    22             6000                               0.076
    23             7000                               0.068
    24     *TABLE VALUES MAY BE INTERPOLATED.
    25     (D)  HEATING CRITERIA FOR FLOORS OVER UNHEATED SPACES.--THE
    26  FLOOR OF A HEATED SPACE LOCATED OVER AN UNHEATED SPACE SHALL
    27  HAVE A THERMAL TRANSMITTANCE VALUE (UO) NOT EXCEEDING 0.08.
    28     (E)  HEATING CRITERIA FOR SLAB-ON GRADE FLOORS.--FOR SLAB-ON
    29  GRADE FLOORS, THE PERIMETER OF THE FLOOR SHALL BE INSULATED WITH
    30  A MATERIAL HAVING A THERMAL RESISTANCE VALUE (R) NOT LESS THAN
    19770S0583B2188                 - 18 -

     1  THOSE SPECIFIED IN TABLE 5.
     2     THE INSULATION SHALL EXTEND DOWNWARD FROM THE TOP OF THE SLAB
     3  FOR A MINIMUM DISTANCE OF 24 INCHES OR DOWNWARD TO THE BOTTOM OF
     4  THE SLAB THEN HORIZONTALLY BENEATH THE SLAB FOR A MINIMUM TOTAL
     5  DISTANCE OF 24 INCHES.
     6                              TABLE 5
     7             MINIMUM ALLOWABLE "R" VALUES OF PERIMETER
     8                INSULATION FOR SLAB-ON GRADE FLOORS
     9     ANNUAL HEATING DEGREE DAYS      HEATED SLAB    UNHEATED SLAB
    10                 4000*                   5.5             3.5
    11                 5000                    6.3             4.2
    12                 6000                    7.0             4.9
    13                 7000                    7.8             5.5
    14     *TABLE VALUES MAY BE INTERPOLATED.
    15     (F)  COOLING CRITERIA FOR WALLS.--ALL BUILDINGS AND
    16  STRUCTURES THAT ARE MECHANICALLY COOLED SHALL HAVE AN OVERALL
    17  THERMAL TRANSFER VALUE FOR THE GROSS AREA OF EXTERIOR WALLS NOT
    18  EXCEEDING 33.5 BTU'S PER HOUR PER SQUARE FOOT BASED ON THE
    19  FOLLOWING EQUATION:
    20  OTTV = (UW X AW X TDEQ) + (AF X SF X SC) + (UF X AF X DELTA T)
    21                                     AO
    22  OTTV = OVERALL THERMAL TRANSFER VALUE WHERE:
    23    UW = THE THERMAL TRANSMITTANCE OF ALL ELEMENTS OF THE OPAQUE
    24          WALL AREA BTU/H. FT2.F (W/M2K)
    25    AW = OPAQUE WALL AREA, FT2 (M2)
    26    UF = THE THERMAL TRANSMITTANCE OF THE FENESTRATION AREA
    27          BTU/H. FT2.F (W/M2K)
    28    AF = FENESTRATION AREA, FT2 (M2)
    29  TDEQ = VALUE GIVEN IN THE FOLLOWING TABLE,F, (C):
    30                  TABLE FOR TEMPERATURE DIFFERENCE
    19770S0583B2188                 - 19 -

     1     WALL CONSTRUCTION-MASS PER UNIT AREA      TDEQ
     2             LB/FT2          KG/M2           F     C
     3             0-25            0-125           44  24.5
     4            26-40          126-195           37  21.0
     5            41-70          196-345           30  17.0
     6            71 AND ABOVE   346 AND ABOVE     23  13.0
     7     WEIGHT OF WALL CONSTRUCTION SHALL BE DETERMINED FROM THE
     8     1972 ASHRAE HANDBOOK OF FUNDAMENTALS, CHAPTER 22.
     9    SC = SHADING COEFFICIENT OF THE FENESTRATION
    10  DELTA T = TEMPERATURE DIFFERENCE BETWEEN EXTERIOR AND INTERIOR
    11         DESIGN CONDITIONS, F, FOR WHICH THE FOLLOWING
    12         TEMPERATURES SHALL APPLY:
    13                             INDOOR          OUTDOOR
    14                               F  C
    15             WINTER           72  22.0       97 1/2%*
    16             SUMMER           78  25.5        2 1/2%*
    17     * VALUES FROM 1972 ASHRAE HANDBOOK OF
    18  FUNDAMENTALS, CHAPTER 33.
    19    SF = SOLAR FACTOR VALUE GIVEN BTU/H.FT2 (W/M2).
    20         (USE 127 BTU/H.FT2)
    21    AO = GROSS AREA OF EXTERIOR WALLS, FT2 (M2).  THE GROSS
    22         AREA OF EXTERIOR WALLS CONSISTS OF ALL OPAQUE WALL
    23         AREAS (INCLUDING FOUNDATION WALLS, BETWEEN FLOOR SPAN-
    24         DRELS, PERIPHERAL EDGES OF FLOORS, ETC.), WINDOW
    25         AREAS (INCLUDING SASH), AND DOOR AREAS, WHERE SUCH
    26         SURFACES ARE EXPOSED TO OUTDOOR AIR AND ENCLOSE A
    27         HEATED AND/OR MECHANICALLY COOLED SPACE (INCLUDING
    28         INTERSTICIAL AREAS BETWEEN TWO SUCH SPACES).
    29  NOTE:  WHERE MORE THAN ONE TYPE OF WALL AND/OR FENESTRATION
    30         IS USED, THE RESPECTIVE TERM OR TERMS SHALL BE EXPANDED
    19770S0583B2188                 - 20 -

     1         INTO SUB-ELEMENTS, AS:
     2         (UW X AW X TDEQ) + (UW2 X AW2 X TDEQ2), ETC.
     3     (G)  COOLING CRITERIA FOR ROOF/CEILINGS.--ALL BUILDINGS AND
     4  STRUCTURES THAT ARE MECHANICALLY COOLED SHALL HAVE A COMBINED
     5  THERMAL TRANSMITTANCE VALUE (UO) FOR ROOF/CEILING ASSEMBLIES THE
     6  SAME AS SPECIFIED IN TABLE 4 FOR HEATING.
     7  SECTION 208.  AIR LEAKAGE.
     8     (A)  APPLICATION.--THE REQUIREMENTS OF THIS SECTION SHALL
     9  APPLY TO ALL BUILDINGS AND STRUCTURES AND APPLY ONLY TO THOSE
    10  LOCATIONS SEPARATING OUTDOOR AMBIENT CONDITIONS FROM INTERIOR
    11  SPACES THAT ARE HEATED OR MECHANICALLY COOLED AND ARE NOT
    12  APPLICABLE TO SEPARATION OF INTERIOR SPACES FROM EACH OTHER.
    13     (B)  STANDARD.--COMPLIANCE WITH THE CRITERIA FOR AIR LEAKAGE
    14  SHALL BE DETERMINED BY ASTM E-283, STANDARD METHOD OF TEST FOR
    15  RATE OF AIR LEAKAGE THROUGH EXTERIOR WINDOWS, CURTAIN WALLS AND
    16  DOORS, AT A PRESSURE DIFFERENTIAL OF 1.567 LB/FT2 WHICH IS
    17  EQUIVALENT TO THE EFFECT OF A 25 M.P.H. WIND.
    18     (C)  ACCEPTANCE CRITERIA.--THE FOLLOWING CRITERIA SHALL
    19  REPRESENT THE MAXIMUM ALLOWABLE AIR LEAKAGE:
    20         (1)  THE AIR INFILTRATION RATE FOR WINDOWS SHALL NOT
    21     EXCEED 0.5 CFM PER FOOT OF SASH CRACK.
    22         (2)  THE AIR INFILTRATION RATE FOR SLIDING GLASS DOORS IN
    23     RESIDENTIAL BUILDINGS SHALL NOT EXCEED 0.5 CFM PER SQUARE
    24     FOOT OF DOOR AREA.
    25         (3)  THE AIR INFILTRATION RATE FOR SWINGING DOORS IN
    26     RESIDENTIAL BUILDINGS SHALL NOT EXCEED 1.25 CFM PER SQUARE
    27     FOOT OF DOOR AREA.
    28         (4)  THE AIR INFILTRATION RATE FOR SWINGING, REVOLVING OR
    29     SLIDING DOORS IN OTHER THAN RESIDENTIAL BUILDINGS SHALL NOT
    30     EXCEED 11 CFM PER LINEAL FOOT OF DOOR CRACK.
    19770S0583B2188                 - 21 -

     1     (D)  CAULKING AND SEALANTS.--EXTERIOR JOINTS AROUND WINDOWS
     2  AND DOOR FRAMES, BETWEEN WALL CAVITIES AND WINDOW OR DOOR
     3  FRAMES, BETWEEN WALL AND FOUNDATION, BETWEEN WALL AND ROOF,
     4  BETWEEN WALL PANELS, AT PENETRATIONS OR UTILITY SERVICES THROUGH
     5  WALLS, FLOORS AND ROOFS, AND ALL OTHER OPENINGS IN THE EXTERIOR
     6  ENVELOPE SHALL BE CAULKED, GASKETED, WEATHERSTRIPPED, OR
     7  OTHERWISE SEALED.
     8                            SUBCHAPTER E
     9         WARM AIR HEATING, VENTILATING AND AIR CONDITIONING
    10                       SYSTEMS AND EQUIPMENT
    11  SECTION 209.  GENERAL PROVISIONS.
    12     THIS SUBCHAPTER APPLIES TO AIR DUCT SYSTEMS EMPLOYING
    13  MECHANICAL MEANS FOR THE MOVEMENT OF AIR USED FOR WARM AIR
    14  HEATING, VENTILATING, AIR CONDITIONING SYSTEMS, EXHAUST SYSTEMS
    15  AND COMBINATION HEATING AND AIR CONDITIONING SYSTEMS, EXCEPT
    16  THAT THIS SUBCHAPTER SHALL NOT APPLY TO SYSTEMS FOR THE REMOVAL
    17  OF FLAMMABLE VAPORS OR RESIDUES OR TO SYSTEMS FOR CONVEYING
    18  DUST, STOCK OR REFUSE BY MEANS OF AIR CURRENTS. HEATING,
    19  VENTILATING AND AIR CONDITIONING SYSTEMS OF ALL BUILDINGS AND
    20  STRUCTURES OR PORTIONS THEREOF SHALL BE DESIGNED AND INSTALLED
    21  FOR EFFICIENT USE OF ENERGY AS HEREIN PROVIDED. FOR SPECIAL
    22  APPLICATIONS SUCH AS HOSPITALS, LABORATORIES, THERMALLY
    23  SENSITIVE EQUIPMENT, COMPUTER ROOMS, AND MANUFACTURING
    24  PROCESSES, THE DESIGN CONCEPTS AND PARAMETERS SHALL CONFORM TO
    25  THE REQUIREMENTS OF THE APPLICATION AT MINIMUM ENERGY LEVELS.
    26  SECTION 210.  DESIGN REQUIREMENTS.
    27     IN DETERMINING DESIGN CONDITIONS FOR CALCULATIONS UNDER THIS
    28  SECTION THE FOLLOWING DESIGN TEMPERATURES SHALL APPLY:
    29         (1)  OUTDOOR DESIGN TEMPERATURE SHALL BE SELECTED FOR
    30     LISTED LOCATIONS IN CHAPTER 33 OF THE ASHRAE HANDBOOK OF
    19770S0583B2188                 - 22 -

     1     FUNDAMENTALS, FROM COLUMNS OF 97 1/2% VALUES FOR HEATING AND
     2     2 1/2% VALUES FOR COOLING.
     3         (2)  INDOOR DESIGN TEMPERATURE SHALL BE 70 DEGREES F. FOR
     4     HEATING AND 78 DEGREES F. FOR COOLING.
     5         (3)  INDOOR DESIGN RELATIVE HUMIDITY FOR HEATING SHALL
     6     NOT EXCEED 30%. FOR COOLING, THE ACTUAL DESIGN RELATIVE
     7     HUMIDITY WITHIN THE COMFORT ENVELOPE AS DEFINED IN ASHRAE
     8     STANDARD 55-74 "THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN
     9     OCCUPANCY" SHALL BE SELECTED FOR THE MINIMUM TOTAL HEATING,
    10     VENTILATING, AND AIR CONDITIONING SYSTEM ENERGY USE.
    11  SECTION 211.  COOLING WITH OUTDOOR AIR.
    12     (A)  FAN SYSTEM DESIGN.--EACH FAN SYSTEM SHALL BE DESIGNED TO
    13  USE UP TO AND INCLUDING 100% OF THE FAN SYSTEM CAPACITY FOR
    14  COOLING WITH OUTDOOR AIR AUTOMATICALLY WHENEVER ITS USE WILL
    15  RESULT IN LOWER USAGE OF ENERGY THAN WOULD BE REQUIRED UNDER ITS
    16  NORMAL OPERATION.
    17     (B)  EXCEPTIONS.--COOLING WITH OUTDOOR AIR IS NOT REQUIRED
    18  UNDER ANY ONE OR MORE OF THE FOLLOWING CONDITIONS:
    19         (1)  FAN SYSTEM CAPACITY LESS THAN 5,000 CFM OR 134,000
    20     BTU/HR TOTAL COOLING CAPACITY.
    21         (2)  THE QUALITY OF THE OUTDOOR AIR IS SO POOR AS TO
    22     REQUIRE EXTENSIVE TREATMENT OF THE AIR.
    23         (3)  THE NEED FOR HUMIDIFICATION OR DEHUMIDIFICATION
    24     REQUIRES THE USE OF MORE ENERGY THAN IS CONSERVED BY OUTDOOR
    25     AIR COOLING.
    26         (4)  THE USE OF OUTDOOR AIR COOLING MAY AFFECT THE
    27     OPERATION OF OTHER SYSTEMS (SUCH AS RETURN OR EXHAUST AIR
    28     FANS OR SUPERMARKET REFRIGERATION) SO AS TO INCREASE THE
    29     OVERALL ENERGY CONSUMPTION OF THE BUILDING.
    30         (5)  INTERNAL/EXTERNAL ZONE HEAT RECOVERY OR OTHER ENERGY
    19770S0583B2188                 - 23 -

     1     RECOVERY IS USED.
     2         (6)  WHEN ALL SPACE COOLING IS ACCOMPLISHED BY A
     3     CIRCULATING LIQUID WHICH TRANSFERS SPACE HEAT DIRECTLY OR
     4     INDIRECTLY TO A HEAT REJECTION DEVICE SUCH AS A COOLING TOWER
     5     WITHOUT THE USE OF A REFRIGERATION SYSTEM.
     6  SECTION 212.  MECHANICAL VENTILATION.
     7     EACH MECHANICAL VENTILATION SYSTEM SHALL BE EQUIPPED WITH A
     8  READILY ACCESSIBLE MEANS FOR EITHER SHUT-OFF OR VOLUME REDUCTION
     9  AND SHUT-OFF WHEN VENTILATION IS NOT REQUIRED.
    10  SECTION 213.  SIMULTANEOUS HEATING AND COOLING.
    11     SYSTEMS THAT EMPLOY BOTH HEATING AND COOLING SIMULTANEOUSLY
    12  IN ORDER TO ACHIEVE COMFORT CONDITIONS WITHIN A SPACE SHALL BE
    13  LIMITED TO THOSE SITUATIONS WHERE MORE EFFICIENT METHODS OF
    14  HEATING AND AIR CONDITIONING CANNOT BE EFFECTIVELY UTILIZED TO
    15  MEET SYSTEM OBJECTIVES. SIMULTANEOUS HEATING AND COOLING BY
    16  REHEATING OR RECOOLING SUPPLY AIR OR BY CONCURRENT OPERATION OR
    17  INDEPENDENT HEATING AND COOLING SYSTEMS SERVING A COMMON ZONE
    18  SHALL BE RESTRICTED AS SPECIFIED HEREIN.
    19  SECTION 214.  RECOVERED ENERGY.
    20     RECOVERED ENERGY, PROVIDED THE NEW ENERGY EXPENDED IN THE
    21  RECOVERY PROCESS IS LESS THAN THE AMOUNT RECOVERED, MAY BE USED
    22  FOR CONTROL OF TEMPERATURE AND HUMIDITY. NEW ENERGY IS DEFINED
    23  AS ENERGY, OTHER THAN RECOVERED, UTILIZED FOR THE PURPOSE OF
    24  HEATING OR COOLING.
    25  SECTION 215.  NEW ENERGY.
    26     (A)  PREVENTION OF EXCESS HUMIDITY.--NEW ENERGY MAY BE USED,
    27  WHEN NECESSARY, TO PREVENT RELATIVE HUMIDITY FROM RISING ABOVE
    28  60% FOR COMFORT CONTROL OR TO PREVENT CONDENSATION ON TERMINAL
    29  UNITS OR OUTLETS.
    30     (B)  CONTROL OF TEMPERATURE.--NEW ENERGY MAY BE USED FOR
    19770S0583B2188                 - 24 -

     1  CONTROL OF TEMPERATURE IF MINIMIZED AS SPECIFIED IN SECTIONS 216
     2  THROUGH 220.
     3  SECTION 216.  REHEAT SYSTEMS.
     4     SYSTEMS EMPLOYING REHEAT AND SERVING MULTIPLE ZONES, OTHER
     5  THAN THOSE EMPLOYING VARIABLE AIR VOLUME FOR TEMPERATURE
     6  CONTROL, SHALL BE PROVIDED WITH CONTROL THAT WILL AUTOMATICALLY
     7  RESET THE SYSTEM COLD AIR SUPPLY TO THE HIGHEST TEMPERATURE
     8  LEVEL THAT WILL SATISFY THE ZONE REQUIRING THE COOLEST AIR.
     9  SINGLE ZONE REHEAT SYSTEMS SHALL BE CONTROLLED TO SEQUENCE
    10  REHEAT AND COOLING.
    11  SECTION 217.  DUAL DUCT AND MULTIZONE SYSTEMS.
    12     THESE SYSTEMS SHALL BE PROVIDED WITH CONTROL THAT WILL
    13  AUTOMATICALLY RESET THE COLD DECK AIR SUPPLY TO THE HIGHEST
    14  TEMPERATURE THAT WILL SATISFY THE ZONE REQUIRING THE COOLEST AIR
    15  AND THE HOT DECK AIR SUPPLY TO THE LOWEST TEMPERATURE THAT WILL
    16  SATISFY THE ZONE REQUIRING THE WARMEST AIR.
    17  SECTION 218.  RECOOLING SYSTEMS.
    18     SYSTEMS IN WHICH HEATED AIR IS RECOOLED DIRECTLY OR
    19  INDIRECTLY, TO MAINTAIN SPACE TEMPERATURE, SHALL BE PROVIDED
    20  WITH CONTROL THAT WILL AUTOMATICALLY RESET THE TEMPERATURE TO
    21  WHICH THE SUPPLY AIR IS HEATED TO THE LOWEST LEVEL THAT WILL
    22  SATISFY THE ZONE REQUIRING THE WARMEST AIR.
    23  SECTION 219.  MULTIPLE ZONES.
    24     FOR SYSTEMS WITH MULTIPLE ZONES, ONE OR MORE ZONES MAY BE
    25  CHOSEN TO REPRESENT A NUMBER OF ZONES WITH SIMILAR HEATING OR
    26  COOLING CHARACTERISTICS. A MULTIPLE ZONE HEATING, VENTILATING
    27  AND AIR CONDITIONING SYSTEM THAT EMPLOYS REHEATING OR RECOOLING
    28  FOR CONTROL OF NOT MORE THAN 5,000 CFM OR 20% OF THE TOTAL
    29  SUPPLY AIR OF THE SYSTEM, WHICHEVER IS LESS, SHALL BE EXEMPT
    30  FROM THE SUPPLY AIR TEMPERATURE RESET REQUIREMENTS OF SECTIONS
    19770S0583B2188                 - 25 -

     1  216 THROUGH 218.
     2  SECTION 220.  CONCURRENT OPERATION.
     3     CONCURRENT OPERATION OF INDEPENDENT HEATING AND COOLING
     4  SYSTEMS SERVING COMMON SPACES, AND REQUIRING THE USE OF NEW
     5  ENERGY FOR HEATING OR COOLING SHALL BE MINIMIZED BY ONE OR BOTH
     6  OF THE FOLLOWING:
     7         (1)  BY PROVIDING SEQUENTIAL TEMPERATURE CONTROL OF BOTH
     8     HEATING AND COOLING CAPACITY IN EACH ZONE.
     9         (2)  BY LIMITING THE HEATING ENERGY INPUT, THROUGH
    10     AUTOMATIC RESET CONTROL OF THE HEATING MEDIUM TEMPERATURE (OR
    11     ENERGY INPUT RATE), TO ONLY THAT NECESSARY TO OFFSET HEAT
    12     LOSS DUE TO TRANSMISSION AND INFILTRATION AND, WHERE
    13     APPLICABLE, TO HEAT THE VENTILATION AIR SUPPLY TO THE SPACE.
    14  SECTION 221.  EQUIPMENT PERFORMANCE REQUIREMENTS.
    15     (A)  APPLICATION.--THE REQUIREMENTS OF THIS SECTION APPLY TO
    16  EQUIPMENT AND COMPONENT PERFORMANCE FOR HEATING, VENTILATING AND
    17  AIR CONDITIONING SYSTEMS. WHERE EQUIPMENT EFFICIENCY LEVELS ARE
    18  SPECIFIED, DATA FURNISHED BY THE EQUIPMENT SUPPLIER OR CERTIFIED
    19  UNDER A NATIONALLY RECOGNIZED CERTIFICATION PROGRAM OR RATING
    20  PROCEDURE SHALL BE USED TO SATISFY THESE REQUIREMENTS.
    21     (B)  SYSTEMS EQUIPMENT - ELECTRICAL.--HEATING VENTILATING AND
    22  AIR CONDITIONING SYSTEMS EQUIPMENT WHOSE ENERGY INPUT IN THE
    23  COOLING MODE IS ENTIRELY ELECTRIC SHALL SHOW A COEFFICIENT OF
    24  PERFORMANCE (COP) AND ENERGY EFFICIENCY RATIO (EER) NOT LESS
    25  THAN THE VALUES SPECIFIED IN TABLE 6. THESE REQUIREMENTS APPLY
    26  TO, BUT ARE NOT LIMITED TO, UNITARY COOLING EQUIPMENT (AIR AND
    27  WATER SOURCE); PACKAGED AIR CONDITIONERS; AND ROOM AIR
    28  CONDITIONERS. THESE REQUIREMENTS DO NOT APPLY TO EQUIPMENT USED
    29  IN AREAS HAVING OPEN REFRIGERATED FOOD DISPLAY CASES. FOR
    30  DETERMINING COEFFICIENT OF PERFORMANCE (COP), THE RATE OF NET
    19770S0583B2188                 - 26 -

     1  HEAT REMOVAL SHALL BE DEFINED AS THE CHANGE IN THE TOTAL HEAT
     2  CONTENTS OF THE AIR ENTERING AND LEAVING THE EQUIPMENT (WITHOUT
     3  REHEAT). TOTAL ENERGY INPUT SHALL BE DETERMINED BY COMBINING THE
     4  ENERGY INPUTS TO ALL ELEMENTS OF THE EQUIPMENT, INCLUDING BUT
     5  NOT LIMITED TO, COMPRESSORS, PUMPS, SUPPLY-AIR FANS, COOLING
     6  TOWER FANS AND THE SYSTEM EQUIPMENT CONTROL CIRCUIT.
     7                              TABLE 6
     8       MINIMUM EER AND COP FOR ELECTRIC HEATING, VENTILATING
     9               AND AIR CONDITIONING SYSTEM EQUIPMENT
    10  STANDARD RATING CAPACITY                       EER     COP
    11  UNDER 65,000 BTU/HR (19,050 WATTS)             6.1     1.8
    12  65,000 BTU/HR (19,050 WATTS) AND OVER          6.8     2.0
    13     (C)  OTHER SYSTEM EQUIPMENT.--HEAT OPERATED COOLING EQUIPMENT
    14  SHALL SHOW A COEFFICIENT OF PERFORMANCE (COP) IN THE COOLING
    15  MODE NOT LESS THAN THE VALUES SPECIFIED IN TABLE 7. THESE
    16  REQUIREMENTS APPLY TO, BUT ARE NOT LIMITED TO, ABSORPTION,
    17  ENGINE-DRIVEN AND TURBINE-DRIVEN EQUIPMENT. THE COEFFICIENT OF
    18  PERFORMANCE (COP) IS DETERMINED EXCLUDING THE ELECTRICAL
    19  AUXILIARY INPUTS.
    20                              TABLE 7
    21     MINIMUM COP FOR HEATING, VENTILATING AND AIR CONDITIONING
    22               SYSTEM HEAT OPERATED COOLING EQUIPMENT
    23         HEAT SOURCE                             MINIMUM COP
    24  DIRECT FIRED (GAS, OIL)                            0.40
    25  INDIRECT FIRED (STEAM, HOT WATER)                  0.65
    26     (D)  SYSTEM COMPONENTS.--HEATING, VENTILATING AND AIR
    27  CONDITIONING SYSTEM COMPONENTS WHOSE ENERGY INPUT IN THE COOLING
    28  MODE IS ENTIRELY ELECTRIC SHALL SHOW A COEFFICIENT OF
    29  PERFORMANCE (COP) AND ENERGY EFFICIENCY RATIO (EER) NOT LESS
    30  THAN THE VALUES SPECIFIED IN TABLE 8. FOR DETERMINING
    19770S0583B2188                 - 27 -

     1  COEFFICIENT OF PERFORMANCE (COP), THE RATE OF HEAT REMOVAL IS
     2  DEFINED AS THE DIFFERENCE IN TOTAL HEAT CONTENTS OF THE WATER OR
     3  REFRIGERANT ENTERING OR LEAVING THE COMPONENT. TOTAL ENERGY
     4  INPUT SHALL BE DETERMINED BY COMBINING THE ENERGY INPUTS TO ALL
     5  ELEMENTS AND ACCESSORIES OF THE COMPONENT, INCLUDING BUT NOT
     6  LIMITED TO, COMPRESSORS, INTERNAL CIRCULATING PUMPS, CONDENSER-
     7  AIR FANS, EVAPORATIVE-CONDENSER COOLING HEATER PUMPS, PURGE, AND
     8  THE COMPONENT CONTROL CIRCUIT.
     9                              TABLE 8
    10      MINIMUM COP FOR ELECTRICALLY DRIVEN HEATING, VENTILATING
    11               AND AIR CONDITIONING SYSTEM COMPONENTS
    12     COMPONENT    CONDENSING MEANS   AIR     WATER     EVAPORATION
    13                                   ERR COP  EER COP     EER COP
    14  SELF-CONTAINED    CENTRIFUGAL    7.5 2.2  12.9 3.8
    15  WATER CHILLERS
    16                     POSITIVE
    17                   DISPLACEMENT    7.2 2.1  10.9 3.2
    18  CONDENSERLESS      POSITIVE
    19  WATER CHILLERS   DISPLACEMENT    8.9 2.6  10.9 3.2
    20  COMPRESSOR AND
    21  CONDENSER UNITS    POSITIVE
    22  65,000 BTU/HR.   DISPLACEMENT    7.8 2.3  11.3 3.3   11.3 3.3
    23  (19,050 WATTS)
    24  AND OVER
    25     (E)  HEAT PUMPS.--HEAT PUMPS WHOSE ENERGY INPUT IS ENTIRELY
    26  ELECTRIC SHALL SHOW A COEFFICIENT OF PERFORMANCE (COP), HEATING,
    27  NOT LESS THAN THE VALUES SPECIFIED IN TABLE 9.
    28                              TABLE 9
    29              MINIMUM COP FOR HEAT PUMPS, HEATING MODE
    30  SOURCE AND OUTDOOR TEMPERATURE (DEGREE F.)         MINIMUM COP
    19770S0583B2188                 - 28 -

     1  AIR SOURCE--47 DB/43 WB                               2.2
     2  AIR SOURCE--17 DB/15 WB                               1.2
     3  WATER SOURCE--60 ENTERING                             2.2
     4     (F)  SUPPLEMENTARY HEATER.--THE HEAT PUMP SHALL BE INSTALLED
     5  WITH A CONTROL TO PREVENT SUPPLEMENTARY HEATER OPERATION WHEN
     6  THE HEATING LOAD CAN BE MET BY THE HEAT PUMP ALONE.
     7  SUPPLEMENTARY HEATER OPERATION IS PERMITTED DURING TRANSIENT
     8  PERIODS, SUCH AS START-UPS, FOLLOWING ROOM THERMOSTAT SETPOINT
     9  ADVANCE, AND DURING DEFROST. A TWO-STAGE ROOM THERMOSTAT, WHICH
    10  CONTROLS THE SUPPLEMENTARY HEAT ON ITS SECOND STAGE, SHALL BE
    11  ACCEPTED AS MEETING THIS REQUIREMENT. THE CUT-ON TEMPERATURE FOR
    12  THE COMPRESSION HEATING SHALL BE HIGHER THAN THE CUT-ON
    13  TEMPERATURE FOR THE SUPPLEMENTARY HEAT, AND THE CUT-OFF
    14  TEMPERATURE FOR THE COMPRESSION HEATING SHALL BE HIGHER THAN THE
    15  CUT-OFF TEMPERATURE FOR THE SUPPLEMENTARY HEAT. SUPPLEMENTARY
    16  HEAT MAY BE DERIVED FROM ANY SOURCE OF ELECTRIC RESISTANCE
    17  HEATING OR COMBUSTION HEATING.
    18     (G)  COMBUSTION HEATING EQUIPMENT.--ALL GAS AND OILFIRED
    19  COMFORT HEATING EQUIPMENT SHALL SHOW A MINIMUM COMBUSTION
    20  EFFICIENCY OF 75% AT MAXIMUM RATED OUTPUT. COMBUSTION EFFICIENCY
    21  SHALL BE DETERMINED IN ACCORDANCE WITH THE ASHRAE STANDARD 90.
    22  SECTION 222.  DUCT INSULATION.
    23     (A)  INSULATION.--ALL DUCT SYSTEMS, OR PORTIONS THEREOF,
    24  EXPOSED TO NONCONDITIONED SPACES SHALL BE INSULATED TO PROVIDE A
    25  THERMAL RESISTANCE, EXCLUDING FILM RESISTANCE, OF
    26             TI - TO
    27         R = --------(HR) (SQ.FT) (F)/BTU
    28               15
    29  WHERE TI-TO IS THE DESIGN TEMPERATURE DIFFERENTIAL (ABSOLUTE
    30  VALUE) BETWEEN THE AIR IN THE DUCT AND THE SURROUNDING AIR WITH
    19770S0583B2188                 - 29 -

     1  THE FOLLOWING EXCEPTIONS. DUCT INSULATION, EXCEPT WHEN NEEDED TO
     2  PREVENT CONDENSATION, IS NOT REQUIRED IN ANY OF THE FOLLOWING
     3  CASES:
     4         (1)  WHERE TI-TO IS 25 DEGREES F. OR LESS.
     5         (2)  WHEN THE HEAT GAIN OR LOSS OF THE DUCTS, WITHOUT
     6     INSULATION, WILL NOT INCREASE THE ENERGY REQUIREMENTS OF THE
     7     BUILDING.
     8         (3)  EXHAUST AIR DUCTS.
     9         (4)  SUPPLY OR RETURN AIR DUCTS INSTALLED IN CRAWL SPACES
    10     WITH INSULATED WALLS, BASEMENTS OR CELLARS IN ONE AND TWO-
    11     FAMILY DWELLINGS.
    12     (B)  VAPOR BARRIERS.--WHERE REQUIRED TO PREVENT CONDENSATION,
    13  INSULATION WITH VAPOR BARRIERS SHALL BE INSTALLED IN ADDITION TO
    14  INSULATION REQUIRED ABOVE.
    15  SECTION 223.  SYSTEM CONTROLS.
    16     (A)  APPLICATION.--ALL HEATING, VENTILATING AND AIR
    17  CONDITIONING SYSTEMS SHALL BE PROVIDED CONTROLS AS SPECIFIED
    18  HEREIN.
    19     (B)  TEMPERATURE.--EACH HEATING, VENTILATING AND AIR
    20  CONDITIONING SYSTEM SHALL BE PROVIDED WITH AT LEAST ONE
    21  THERMOSTAT FOR THE REGULATION OF TEMPERATURE. EACH THERMOSTAT
    22  SHALL BE CAPABLE OF BEING SET FROM 55 DEGREES F. TO 75 DEGREES
    23  F. WHERE USED TO CONTROL HEATING ONLY AND FROM 70 DEGREES F. TO
    24  85 DEGREES F. WHERE USED TO CONTROL COOLING ONLY. WHERE USED TO
    25  CONTROL BOTH HEATING AND COOLING IT SHALL BE CAPABLE OF BEING
    26  SET FROM 55 DEGREES F. TO 85 DEGREES F. AND SHALL BE CAPABLE OF
    27  OPERATING THE SYSTEM HEATING AND COOLING IN SEQUENCE. IT SHALL
    28  BE ADJUSTABLE TO PROVIDE A TEMPERATURE RANGE OF UP TO 10 DEGREES
    29  F. BETWEEN FULL HEATING AND FULL COOLING, EXCEPT AS ALLOWED IN
    30  SECTION 220.
    19770S0583B2188                 - 30 -

     1     (C)  HUMIDITY.--IF A HEATING, VENTILATING AND AIR
     2  CONDITIONING SYSTEM IS EQUIPPED WITH A MEANS FOR ADDING MOISTURE
     3  TO MAINTAIN SPECIFIC SELECTED RELATIVE HUMIDITIES IN SPACES OR
     4  ZONES, A HUMIDISTAT SHALL BE PROVIDED. THIS DEVICE SHALL BE
     5  CAPABLE OF BEING SET TO PREVENT NEW ENERGY FROM BEING USED TO
     6  PRODUCE SPACE RELATIVE HUMIDITY ABOVE 30% R.H.  WHERE A
     7  HUMIDISTAT IS USED IN A HEATING, VENTILATING AND AIR
     8  CONDITIONING SYSTEM FOR CONTROLLING MOISTURE REMOVAL TO MAINTAIN
     9  SPECIFIC SELECTED RELATIVE HUMIDITIES IN SPACES OR ZONES, IT
    10  SHALL BE CAPABLE OF BEING SET TO PREVENT NEW ENERGY FROM BEING
    11  USED TO PRODUCE A SPACE RELATIVE HUMIDITY BELOW 60%.
    12     (D)  TEMPERATURE ZONING.--
    13         (1)  IN ALL BUILDINGS AND STRUCTURES OF USE GROUP R-3, AT
    14     LEAST ONE THERMOSTAT FOR REGULATION OF SPACE TEMPERATURE
    15     SHALL BE PROVIDED FOR EACH SEPARATE HEATING, VENTILATING AND
    16     AIR CONDITIONING SYSTEM. IN ADDITION, A READILY ACCESSIBLE
    17     MANUAL OR AUTOMATIC MEANS SHALL BE PROVIDED TO PARTIALLY
    18     RESTRICT OR SHUT-OFF THE HEATING OR COOLING INPUT TO EACH
    19     ZONE OR FLOOR, EXCLUDING UNHEATED OR UNCOOLED BASEMENTS AND
    20     GARAGES.
    21         (2)  IN ALL BUILDINGS AND STRUCTURES OF USE GROUP R-2,
    22     EACH INDIVIDUAL DWELLING UNIT SHALL BE CONSIDERED SEPARATELY
    23     AND SHALL MEET THE REQUIREMENTS FOR ONE AND TWO-FAMILY
    24     DWELLINGS ABOVE.
    25         (3)  IN ALL BUILDINGS AND STRUCTURES OTHER THAN USE GROUP
    26     R-3 AND IN SPACES OTHER THAN DWELLING UNITS IN USE GROUP R-2,
    27     AT LEAST ONE THERMOSTAT FOR REGULATION OF SPACE TEMPERATURE
    28     SHALL BE PROVIDED FOR EACH SEPARATE HEATING, VENTILATING AND
    29     AIR CONDITIONING SYSTEM AND FOR EACH FLOOR OF THE BUILDING.
    30     (E)  SET-BACK AND SHUT-OFF.--
    19770S0583B2188                 - 31 -

     1         (1)  IN ALL BUILDINGS AND STRUCTURES, OR PORTIONS THEREOF
     2     OF USE GROUP R-3, THE THERMOSTAT, OR AN ALTERNATE MEANS SUCH
     3     AS A SWITCH OR A CLOCK, SHALL PROVIDE A READILY ACCESSIBLE,
     4     MANUAL OR AUTOMATIC MEANS FOR REDUCING THE ENERGY REQUIRED
     5     FOR HEATING AND COOLING DURING PERIODS OF NONUSE OR REDUCED
     6     NEED.
     7         (2)  IN ALL OTHER BUILDINGS AND STRUCTURES, OR PORTIONS
     8     THEREOF EACH HEATING, VENTILATING AND AIR CONDITIONING SYSTEM
     9     SHALL BE EQUIPPED WITH A READILY ACCESSIBLE MEANS OF REDUCING
    10     THE ENERGY USED FOR HEATING, VENTILATING AND AIR CONDITIONING
    11     DURING PERIODS OF NONUSE OR ALTERNATE USES OF THE BUILDING
    12     SPACES OR ZONES SERVED BY THE SYSTEM, SUCH AS WITH MANUALLY
    13     ADJUSTABLE AUTOMATIC TIMING DEVICES, MANUAL DEVICES FOR USE
    14     BY OPERATING PERSONNEL, OR AUTOMATIC CONTROL SYSTEMS.
    15         (3)  LOWERING THERMOSTAT SET POINTS TO REDUCE ENERGY
    16     CONSUMPTION OF HEATING SYSTEMS SHALL NOT CAUSE ENERGY TO BE
    17     EXPENDED TO REACH THE REDUCED SETTING.
    18  SECTION 224.  STEAM AND HOT WATER HEATING PIPING.
    19     (A)  PIPING INSULATION.--ALL PIPING SERVING AS PART OF A
    20  HEATING OR COOLING SYSTEM INSTALLED TO SERVE BUILDINGS AND
    21  WITHIN BUILDINGS SHALL BE THERMALLY INSULATED AS SHOWN IN TABLE
    22  10.
    23                              TABLE 10
    24                      MINIMUM PIPE INSULATION
    25                                 INSULATION THICKNESS IN INCHES
    26             FLUID                       FOR PIPE SIZES
    27  PIPING  TEMPERATURE
    28  SYSTEM     RANGE,   RUNOUTS  1" AND  1 1/4-  2 1/2-  5&   8" AND
    29  TYPES        F.     UP TO 2"  LESS     2       4     6    LARGER
    30  HEATING SYSTEMS
    19770S0583B2188                 - 32 -

     1     STEAM &
     2     HOT WATER
     3  HIGH PRESSURE/
     4  TEMP       306-450   1 1/2     1 1/2    2    2 1/2  3 1/2  3 1/2
     5  MED. PRESSURE/
     6  TEMP       251-305   1 1/2     1 1/2    2    2 1/2  3      3
     7  LOW PRESSURE/
     8  TEMP       201-250   1         1       1 1/2 1 1/2  2      2
     9  LOW TEM-
    10  PERATURE   120-200    1/2       3/4     1    1      1      1 1/2
    11  STEAM CON-
    12  DENSATE      ANY     1         1        1    1 1/2  1 1/2  2
    13  (FOR FEED
    14  WATER)
    15  COOLING SYSTEMS
    16  CHILLED
    17  WATER,      40-55     1/2       1/2      3/4 1      1      1
    18  REFRIGERANT,
    19  OR BRINE  BELOW 40   1         1       1 1/2  1 1/2 1 1/2  1 1/2
    20  INSULATION THICKNESSES ARE BASED ON INSULATION HAVING THERMAL
    21  RESISTANCES IN THE RANGE OF 4.0 TO 4.6 PER INCH OF THICKNESS ON
    22  A FLAT SURFACE AT A MEAN TEMPERATURE OF 75 DEGREES F. MINIMUM
    23  INSULATION THICKNESS SHALL BE INCREASED FOR MATERIALS HAVING R
    24  VALUES LESS THAN 4.0 OR MAY BE REDUCED FOR MATERIALS HAVING R
    25  VALUES GREATER THAN 4.6 PER INCH OF THICKNESS AS FOLLOWS:
    26     (B)  HIGH THERMAL RESISTANCE.--FOR MATERIALS WITH THERMAL
    27  RESISTANCE GREATER THAN R=4.6, THE MINIMUM INSULATION THICKNESS
    28  MAY BE REDUCED AS FOLLOWS:
    29         4.6 X TABLE 10 THICKNESS    =   NEW MINIMUM THICKNESS
    30               ACTUAL R
    19770S0583B2188                 - 33 -

     1     (C)  LOW THERMAL RESISTANCE.--FOR MATERIALS WITH THERMAL
     2  RESISTANCE LESS THAN R=4.0 THE MINIMUM INSULATION THICKNESS
     3  SHALL BE INCREASED AS FOLLOWS:
     4         4.0 X TABLE 10 THICKNESS    =   NEW MINIMUM THICKNESS
     5               ACTUAL R
     6  PIPING INSULATION, EXCEPT WHEN NEEDED TO PREVENT CONDENSATION,
     7  IS NOT REQUIRED IN ANY OF THE FOLLOWING CASES:
     8         (1)  PIPING INSTALLED WITHIN HEATING, VENTILATING AND AIR
     9     CONDITIONING EQUIPMENT.
    10         (2)  PIPING AT TEMPERATURES BETWEEN 55 DEGREES F. AND 120
    11     DEGREES F.
    12         (3)  WHEN THE HEAT LOSS OR HEAT GAIN OF THE PIPING,
    13     WITHOUT INSULATION, DOES NOT INCREASE THE ENERGY REQUIREMENTS
    14     OF THE BUILDING.
    15         (4)  PIPING INSTALLED IN BASEMENTS OR CELLARS IN ONE AND
    16     TWO-FAMILY DWELLINGS.
    17     (D)  VAPOR BARRIERS.--WHERE REQUIRED TO PREVENT CONDENSATION,
    18  INSULATION WITH VAPOR BARRIERS SHALL BE INSTALLED IN ADDITION TO
    19  INSULATION REQUIRED ABOVE.
    20                            SUBCHAPTER F
    21                          PLUMBING SYSTEMS
    22  SECTION 225.  PURPOSE.
    23     THIS SUBCHAPTER SETS FORTH PROVISIONS FOR DESIGN AND
    24  EQUIPMENT SELECTION FOR ENERGY CONSERVATION IN SERVICE WATER
    25  HEATING SYSTEMS.
    26  SECTION 226.  FIXTURES.
    27     (A)  LAVATORIES.--LAVATORIES IN RESTROOMS OF PUBLIC
    28  FACILITIES SHALL BE EQUIPPED WITH SELF-CLOSING OUTLET DEVICES
    29  WHICH LIMIT THE FLOW OF HOT WATER TO A MAXIMUM OF 0.5 GPM,
    30  DEVICES WHICH LIMIT THE OUTLET TEMPERATURE TO A MAXIMUM OF 110
    19770S0583B2188                 - 34 -

     1  DEGREES F. AND SELFCLOSING VALVES WHICH LIMIT THE QUANTITY OF
     2  HOT WATER TO A MAXIMUM OF 0.25 GALLONS.
     3     (B)  SHOWERS.--SHOWERS USED FOR OTHER THAN SAFETY REASONS
     4  SHALL BE EQUIPPED WITH FLOW CONTROL DEVICES TO LIMIT TOTAL FLOW
     5  TO A MAXIMUM OF 3 GPM PER SHOWER HEAD.
     6  SECTION 227.  INSULATION.
     7     (A)  PIPING INSULATION.--PIPING IN REQUIRED RETURN
     8  CIRCULATION SYSTEMS SHALL BE INSULATED SO THAT HEAT LOSS IS
     9  LIMITED TO A MAXIMUM OF 25 BTUH PER SQUARE FOOT OF EXTERNAL PIPE
    10  SURFACE FOR ABOVE GROUND PIPING AND A MAXIMUM OF 35 BTUH PER
    11  SQUARE FOOT OF EXTERNAL PIPE SURFACE FOR UNDERGROUND PIPING.
    12  MAXIMUM HEAT LOSS SHALL BE DETERMINED AT A TEMPERATURE
    13  DIFFERENTIAL EQUAL TO THE MAXIMUM WATER TEMPERATURE MINUS A
    14  DESIGN AMBIENT TEMPERATURE NO HIGHER THAN 65 DEGREES F. EXCEPT
    15  THAT CONFORMANCE WITH TABLE 10 FOR "LOW TEMPERATURE PIPING
    16  SYSTEM" SHALL BE DEEMED AS COMPLYING WITH THIS SECTION.
    17     (B)  TANKS.--UNFIRED HOT WATER STORAGE TANKS SHALL BE
    18  INSULATED SO THAT HEAT LOSS IS LIMITED TO A MAXIMUM OF 15 BTUH
    19  PER SQUARE FOOT OF EXTERNAL TANK SURFACE AREA. FOR PURPOSES OF
    20  DETERMINING THIS HEAT LOSS, THE DESIGN AMBIENT TEMPERATURE SHALL
    21  BE NO HIGHER THAN 65 DEGREES F.
    22  SECTION 228.  EQUIPMENT.
    23     (A)  PUMP OPERATION.--CIRCULATING HOT WATER SYSTEMS SHALL BE
    24  ARRANGED SO THAT THE CIRCULATING PUMP CAN BE CONVENIENTLY TURNED
    25  OFF EITHER AUTOMATICALLY OR MANUALLY WHEN THE HOT WATER SYSTEM
    26  IS NOT IN OPERATION.
    27     (B)  ELECTRIC WATER HEATERS.--ALL AUTOMATIC ELECTRIC STORAGE
    28  WATER HEATERS SHALL HAVE A STAND-BY LOSS NOT EXCEEDING 4 WATTS
    29  PER SQUARE FOOT OF TANK SURFACE AREA. THE METHOD OF TEST OF
    30  STAND-BY LOSS SHALL BE AS DESCRIBED IN SECTION 4.3.1 OF ANSI
    19770S0583B2188                 - 35 -

     1  C72.1 HOUSEHOLD AUTOMATIC ELECTRICAL STORAGE-TYPE WATER HEATERS.
     2     (C)  GAS AND OIL-FIRED WATER HEATERS.--ALL GAS AND OIL-FIRED
     3  AUTOMATIC STORAGE HEATERS SHALL HAVE A RECOVERY EFFICIENCY, ER,
     4  NOT LESS THAN 75% AND A STAND-BY LOSS PERCENTAGE S, NOT
     5  EXCEEDING S=2.3+67/V WHERE V=RATED VOLUME IN GALLONS. THE METHOD
     6  OF TEST OF ER AND S SHALL BE AS DESCRIBED IN SECTION 2.7 OF ANSI
     7  Z21.10.3 CIRCULATING TANK, INSTANTANEOUS AND LARGE AUTOMATIC
     8  STORAGE TYPE WATER HEATERS, APPROVAL REQUIREMENTS FOR GAS WATER
     9  HEATERS.
    10  SECTION 229.  CONTROLS.
    11     (A)  TEMPERATURE CONTROLS.--ALL HOT WATER SUPPLY SYSTEMS
    12  SHALL BE EQUIPPED WITH AUTOMATIC TEMPERATURE CONTROLS CAPABLE OF
    13  ADJUSTMENTS FROM THE LOWEST TO THE HIGHEST ACCEPTABLE
    14  TEMPERATURE SETTINGS FOR THE INTENDED USE.
    15     (B)  SHUT DOWN.--A SEPARATE SWITCH SHALL BE PROVIDED TO
    16  TERMINATE THE ENERGY SUPPLIED TO ELECTRIC HOT WATER SUPPLY
    17  SYSTEMS. A SEPARATE VALVE SHALL BE PROVIDED TO TURN OFF THE
    18  ENERGY SUPPLIED TO THE MAIN BURNER OF ALL OTHER TYPES OF HOT
    19  WATER SUPPLY SYSTEMS.
    20                            SUBCHAPTER G
    21                         ELECTRICAL SYSTEMS
    22  SECTION 230.  SYSTEM REQUIREMENTS.
    23     (A)  POWER FACTOR.--THE POWER FACTOR OF THE OVERALL
    24  ELECTRICAL DISTRIBUTION SYSTEM IN A BUILDING SHALL BE NOT LESS
    25  THAN 90% UNDER RATED DESIGN INSTALLED LOAD OF THE BUILDING,
    26  EITHER BY UTILIZATION EQUIPMENT DESIGN OR BY THE USE OF POWER
    27  FACTOR CORRECTIVE DEVICES. THE POWER FACTOR CORRECTIVE DEVICES
    28  MAY BE INSTALLED ON INDIVIDUAL EQUIPMENT, RATED GREATER THAN
    29  1,000 WATTS AND SWITCHED THEREWITH, REGIONALLY GROUPED, LOCATED
    30  AT THE SERVICE EQUIPMENT OR POWER FACTOR CORRECTION ACHIEVED BY
    19770S0583B2188                 - 36 -

     1  OTHER EQUIVALENT MEANS. THE CHOICE AMONG THESE CORRECTIVE
     2  METHODS SHOULD BE MADE BASED UPON AN ENGINEERING EVALUATION OF
     3  EACH DISTRIBUTION SYSTEM.
     4     (B)  SERVICE VOLTAGE.--WHERE A CHOICE OF SERVICE VOLTAGE IS
     5  AVAILABLE, THE VOLTAGE RESULTING IN THE LEAST ENERGY LOSS SHALL
     6  BE USED.
     7     (C)  VOLTAGE DROP.--IN ANY BUILDING, THE MAXIMUM TOTAL
     8  VOLTAGE DROP SHALL NOT EXCEED 3% IN BRANCH CIRCUITS OR FEEDERS,
     9  FOR A TOTAL OF 5% TO THE FARTHEST OUTLET BASED ON STEADY STATE
    10  DESIGN LOAD CONDITIONS.
    11     (D)  LIGHTING SWITCHING.--SWITCHING SHALL BE PROVIDED FOR
    12  EACH LIGHTING CIRCUIT, OR FOR PORTIONS OF EACH CIRCUIT, SO THAT
    13  THE PARTIAL LIGHTING REQUIRED FOR CUSTODIAL OR FOR EFFECTIVE
    14  COMPLEMENTARY USE WITH NATURAL LIGHTING MAY BE OPERATED
    15  SELECTIVELY.
    16     (E)  SEPARATE METERING.--IN ALL MULTI-FAMILY DWELLINGS
    17  PROVISIONS SHALL BE MADE TO DETERMINE THE ELECTRICAL ENERGY
    18  CONSUMED BY EACH TENANT.
    19                            SUBCHAPTER H
    20                              LIGHTING
    21  SECTION 231.  LIGHT POWER BUDGET.
    22     A LIGHTING POWER BUDGET IS THE UPPER LIMIT OF THE POWER TO BE
    23  AVAILABLE TO PROVIDE THE LIGHTING NEEDS IN ACCORDANCE WITH A
    24  GIVEN SET OF CRITERIA AND GIVEN CALCULATION PROCEDURE.
    25  SECTION 232.  CALCULATION METHODS.
    26     THE CRITERIA SPECIFIED BELOW SHALL BE UTILIZED FOR
    27  COMPUTATION OF THE LIGHTING POWER BUDGET. ALL CALCULATIONS SHALL
    28  BE IN ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICE. WHEN
    29  INSUFFICIENT INFORMATION IS KNOWN ABOUT THE SPECIFIC USE OF THE
    30  BUILDING SPACE (E.G., NUMBER OF OCCUPANTS, SPACE FUNCTION,
    19770S0583B2188                 - 37 -

     1  LOCATION OF PARTITIONS), THE BUDGET SHALL BE BASED ON THE
     2  APPARENT INTENDED USE OF THE BUILDING SPACE.
     3  SECTION 233.  BUILDING INTERIORS.
     4     (A)  PROCEDURE.--THE ALLOWABLE ELECTRIC POWER FOR LIGHTING
     5  SHALL BE ESTABLISHED BY USING THE CRITERIA AND THE CALCULATION
     6  PROCEDURES SPECIFIED IN SECTION 236. THE VALUE SHALL BE BASED ON
     7  THE USE FOR WHICH THE SPACE WITHIN THE BUILDING IS INTENDED AND
     8  ON EFFICIENT ENERGY UTILIZATION.
     9     (B)  ILLUMINATION LEVEL CRITERIA.--FOR THE PURPOSE OF
    10  ESTABLISHING A BUDGET, LEVELS OF ILLUMINATION SHALL BE THOSE
    11  LISTED IN FIG. 9-80 OF THE IES LIGHTING HANDBOOK, AND THOSE
    12  LEVELS SHALL BE USED AS FOLLOWS:
    13         (1)  FOR TASK LIGHTING, THE LEVELS OF ILLUMINATION LISTED
    14     ARE FOR SPECIFIC TASKS. THESE LEVELS ARE FOR THE TASK AREAS
    15     DEFINED IN THE IES LIGHTING HANDBOOK OR, WHERE NOT DEFINED,
    16     AT ALL USABLE PORTIONS OF TASK SURFACES. IN SOME CASES, THE
    17     LEVELS OF ILLUMINATION ARE LISTED FOR LOCATIONS (E.G.,
    18     AUDITORIUMS). THESE LEVELS ARE TO BE CONSIDERED AS AVERAGE
    19     LEVELS.
    20         (2)  FOR GENERAL LIGHTING, IN AREAS SURROUNDING TASK
    21     LOCATIONS, THE AVERAGE LEVEL OF GENERAL LIGHTING, FOR BUDGET
    22     PURPOSES ONLY, SHALL BE ONE-THIRD THE LEVEL FOR THE TASKS
    23     PERFORMED IN THE AREA BUT IN NO CASE LESS THAN 20-FOOT
    24     CANDLES. WHERE MORE THAN ONE TASK LEVEL OCCURS IN A SPACE,
    25     THE GENERAL LEVEL SHALL BE ONE-THIRD THE WEIGHTED AVERAGE OF
    26     THE SPECIFIC TASK LEVELS.
    27         (3)  FOR NONCRITICAL LIGHTING, IN CIRCULATION AND SEATING
    28     AREAS, WHERE NO SPECIFIC VISUAL TASKS OCCUR, THE AVERAGE
    29     LEVEL OF ILLUMINATION SHALL BE ONE-THIRD OF THE AVERAGE
    30     GENERAL LIGHTING IN THE ADJACENT TASK SPACES BUT IN NO CASE
    19770S0583B2188                 - 38 -

     1     LESS THAN TEN-FOOT CANDLES.
     2         (4)  FOR THE PURPOSE OF ESTABLISHING A POWER BUDGET, ONLY
     3     LAMP EFFICACIES AND COEFFICIENTS OF UTILIZATION (CU)
     4     SPECIFIED IN TABLE 11, SHALL BE ASSUMED.
     5  SECTION 234.  BUILDING EXTERIORS.
     6     (A)  BASIS ON USE.--IN EXTERIOR SPACES, THE LIGHTING POWER
     7  BUDGET SHALL BE BASED ON THE USE OF WHICH THE SPACE IS INTENDED
     8  (FOR TASK PERFORMANCE, SAFETY, OR SECURITY) AND ON EFFICIENT
     9  ENERGY UTILIZATION.
    10     (B)  CRITERIA.--THE SAME CRITERIA AS THOSE FOR INTERIOR
    11  SPACES APPLY FOR ILLUMINATION LEVELS AND LIGHTING SYSTEMS WITH
    12  THE ADDITION OF LUMINAIRES FOR FLOOD LIGHTING. FOR POWER BUDGET
    13  PURPOSES FLOODLIGHTING SHALL BE SELECTED WITH LUMINAIRES HAVING
    14  A GREATER PERCENTAGE OF THEIR BEAM LUMENS RESTRICTED TO THE AREA
    15  TO BE LIGHTED. SUCH LUMINAIRES ARE DEFINED AS THOSE WITH AT
    16  LEAST THE MINIMUM EFFICIENCIES LISTED IN THE IES LIGHTING
    17  HANDBOOK.
    18     (C)  FACADE LIGHTING.--FACADE LIGHTING FOR BUDGET PURPOSES
    19  SHALL BE NO GREATER THAN 2% OF THE TOTAL INTERIOR LOAD OF THE
    20  BUILDING.
    21     (D)  CALCULATION PROCEDURE.--IN ESTABLISHING A LIGHTING POWER
    22  BUDGET THE FOLLOWING PROCEDURES SHALL BE USED:
    23         (1)  FOR OVERHEAD LIGHTING THE PROCEDURE SPECIFIED IN
    24     SECTION 236 SHALL BE FOLLOWED, BUT USING REFLECTANCES AS
    25     FOUND.
    26         (2)  FOR FLOOD LIGHTING THE BEAM LUMEN METHOD, AS SHOWN
    27     IN THE IES LIGHTING HANDBOOK AND A COEFFICIENT OF BEAM
    28     UTILIZATION (CBU) OF 0.75 SHALL BE USED FOR FLOODLIGHTING
    29     CALCULATIONS.
    30  SECTION 235.  EXCEPTIONS TO CRITERIA.
    19770S0583B2188                 - 39 -

     1     (A)  INTERIORS.--THE CRITERIA OF SECTION 233 SHALL NOT APPLY
     2  TO THE FOLLOWING AREAS WHEN CALCULATING THE LOAD:
     3         (1)  PORTIONS OF RESIDENTIAL OCCUPANCIES EXCEPT FOR
     4     KITCHENS, BATHROOMS, AND LAUNDRY AREAS AND PUBLIC SPACES
     5     INCLUDING LOBBIES, HALLS, STAIRWAYS, BASEMENT AREAS, AND
     6     UTILITY ROOMS.
     7         (2)  RESIDENTIAL TYPE SPACES SIMILAR TO THOSE STATED IN
     8     PARAGRAPH (1) IN INSTITUTIONS, SUCH AS HOSPITALS, HOTELS,
     9     FUNERAL HOMES, CHURCHES, MUSEUMS, ETC.
    10         (3)  THEATER AUDITORIUMS, ENTERTAINMENT AND AUDIOVISUAL
    11     PRESENTATIONS WHERE THE LIGHTING IS AN ESSENTIAL TECHNICAL
    12     ELEMENT FOR THE FUNCTION PERFORMED.
    13     (B)  EXTERIORS.--THE CRITERIA OF SECTION 234 SHALL NOT APPLY
    14  TO THE FOLLOWING LAMPS AND LUMINARIES; HOWEVER, THEIR USE SHALL
    15  BE ACCOUNTED FOR IN THE CALCULATION OF TASK LIGHTING LOADS FOR
    16  SPECIFIC TASKS. THE ALLOWABLE LOAD SHALL BE BASED ON THE
    17  LUMINARY WATTAGE TO ACHIEVE THE LEVELS OF ILLUMINATION AS
    18  COVERED IN SECTION 233 USING A POINT CALCULATION METHOD GIVEN IN
    19  THE IES LIGHTING HANDBOOK. THE EXCEPTED LAMPS AND LUMINAIRES ARE
    20  AS FOLLOWS:
    21         (1)  LUMINAIRES FOR MEDICAL AND DENTAL PURPOSES.
    22         (2)  LUMINAIRES FOR HIGHLIGHTING APPLICATIONS, SUCH AS
    23     SCULPTURE EXHIBITS, ART EXHIBITS, AND INDIVIDUAL ITEMS OF
    24     DISPLAY MERCHANDISE.
    25         (3)  LUMINAIRES FOR SPECIALIZED LIGHTING APPLICATIONS
    26     (COLOR MATCHING, WHERE ELECTRICAL INTERFERENCE CANNOT BE
    27     TOLERATED, ETC.).
    28     (C)  CONTROL OF REFLECTANCES.--THE CRITERIA OF TABLE 11 SHALL
    29  NOT APPLY IN SPACES WHERE IT IS IMPRACTICAL TO CONTROL
    30  REFLECTANCES AND WHERE A DIRTY ATMOSPHERE CANNOT BE AVOIDED.
    19770S0583B2188                 - 40 -

     1  WHERE THIS CONDITION EXISTS, THE VALUES FOR REFLECTANCES AND
     2  LIGHT LOSS FACTORS SHALL BE THOSE EXPECTED TO BE FOUND AND SHALL
     3  BE APPROVED BY THE DEPARTMENT. THE CALCULATION SHALL MAKE A NOTE
     4  OF THIS DEVIATION.
     5  SECTION 236.  CALCULATION PROCEDURE.
     6     (A)  ILLUMINATION LEVELS AND AREAS.--TO ESTABLISH
     7  ILLUMINATION LEVELS AND AREAS, THE FOLLOWING PROCEDURE SHALL BE
     8  USED:
     9         (1)  DETERMINE THE VISUAL TASKS THAT ARE EXPECTED TO BE
    10     PERFORMED IN EACH SPACE AND THE NUMBER OF PLANNED WORK
    11     LOCATIONS WHERE TASKS WILL BE PERFORMED. IF ASSUMPTIONS ARE
    12     MADE, THEIR BASES SHALL BE INDICATED.
    13         (2)  SELECT THE ILLUMINATION LEVEL, IN FOOT-CANDLES FOR
    14     THOSE EXPECTED TASKS IN ACCORDANCE WITH SECTION 233(B)(1).
    15         (3)  CALCULATE TOTAL TASK AREAS TO BE ILLUMINATED TO THE
    16     SAME LEVEL BY MULTIPLYING THE NUMBER OF WORK LOCATIONS BY 50
    17     SQUARE FEET PER WORK LOCATION. (TOTAL TASK AREAS SHALL NOT
    18     EXCEED ACTUAL TOTAL SPACE AREA). IF ACTUAL TASK AREA IS
    19     GREATER THAN 50 SQUARE FEET THE ACTUAL AREA SHALL BE USED. IF
    20     SPECIAL TASK LIGHTING OR LOCALIZED LIGHTING IS TO BE
    21     EMPLOYED, USE THE ACTUAL TASK AREAS AND POINT CALCULATION
    22     PROCEDURES.
    23         (4)  CALCULATE THE LEVEL OF GENERAL LIGHTING BY
    24     MULTIPLYING THE TASK LIGHTING LEVEL BY ONE-THIRD, WHERE THERE
    25     IS ONLY ONE TASK LEVEL, OR BY TAKING ONE-THIRD OF THE SUM OF
    26     THE PRODUCTS OF THE TASK LEVELS AS PROVIDED FOR IN PARAGRAPH
    27     (2) AND THEIR AREAS AS PROVIDED FOR IN PARAGRAPH (3) DIVIDED
    28     BY THE TOTAL TASK AREAS.
    29         (5)  CALCULATE THE LEVEL OF NONCRITICAL LIGHTING.
    30     (B)  LIGHTING SYSTEM DATA.--TO ESTABLISH LIGHTING SYSTEM
    19770S0583B2188                 - 41 -

     1  DATA, THE FOLLOWING SHALL BE USED:
     2         (1)  LIGHT SOURCE AND LUMINAIRE TYPES TO USE.
     3         (2)  LAMP LUMENS PER WATT AND LUMINAIRE COEFFICIENTS OF
     4     UTILIZATION FOR ROOM AND LUMINAIRE MOUNTING HEIGHT
     5     DIMENSIONS. LUMINAIRE CUS SHALL BE SELECTED FROM THE IES
     6     LIGHTING HANDBOOK. IN ALL CASES, NO LUMINAIRE SHALL HAVE A CU
     7     FOR RCR = 1 OF LESS THAN THAT GIVEN IN TABLE 11 LAMP
     8     EFFICACIES FOR THE APPROPRIATE SPACE.
     9     (C)  ALLOWABLE WATTAGE.--TO ESTABLISH ALLOWABLE WATTAGE, THE
    10  FOLLOWING SHALL BE USED:
    11         (1)  USING DATA FROM SUBSECTION (B), THE ILLUMINATION
    12     LEVELS AND AREAS DETERMINED IN SUBSECTION (A), AND THE
    13     CRITERIA OF TABLE 11 ON REFLECTANCE, CALCULATE THE ALLOWABLE
    14     WATTAGES USING THE LUMEN METHOD.
    15         (2)  CALCULATE THE TOTAL SPACE WATTAGE BY ADDING THE
    16     TASK, GENERAL AND NONCRITICAL LIGHTING LOADS.
    17         (3)  ADD THE WATTAGE OF LUMINAIRES ALLOWED IN SECTION
    18     235(B).
    19                              TABLE 11
    20     (A)  LAMP EFFICACIES.--THE FOLLOWING ARE INITIAL LUMEN OUTPUT
    21  PER WATT INPUT, INCLUDING BALLAST LOSSES:
    22                 APPLICATION                             LUMENS
    23                                                        PER WATT
    24     WHERE MODERATE COLOR RENDITION IS APPROPRIATE         55
    25     WHERE GOOD COLOR RENDITION IS APPROPRIATE             40
    26     WHERE HIGH COLOR RENDITION IS APPROPRIATE,
    27     SPACES ARE LESS THAN 50 SQUARE FEET OR WHERE
    28     USE OF LOW WATTAGE HIGH INTENSITY DISCHARGE
    29     (HID) LAMPS UNDER 250 W OR FLUORESCENT
    30     LAMPS UNDER 40 W IS APPROPRIATE                       25
    19770S0583B2188                 - 42 -

     1     (B)  LUMINARY COEFFICIENTS OF UTILIZATION (CU).--COEFFICIENTS
     2  OF UTILIZATION (CUS) ARE TO BE FOR LUMINAIRES FOR USE IN THE
     3  TYPES OF SPACES LISTED BELOW, AND THOSE LUMINAIRES SHALL HAVE A
     4  CU OF NO LESS THAN THAT LISTED BELOW (FOR EACH TYPE SPACE) FOR A
     5  ROOM CAVITY RATIO (RCR) OF 1 AND REFLECTANCES AS IN (C).
     6                 SPACE USE                           MINIMUM CU
     7                                                    (AT RCR = 1)
     8     FOR SPACES WITH TASKS SUBJECTED TO VEILING
     9     REFLECTIONS WHERE DESIGN LEVELS OF
    10     ILLUMINATION ARE LISTED IN TERMS OF
    11     EQUIVALENT SPHERE ILLUMINATION (ESI) AND
    12     WHERE VISUAL COMFORT IS IMPORTANT.                  0.55
    13     FOR SPACES WITHOUT TASKS, OR WITH TASKS
    14     NOT SUBJECTED TO VEILING REFLECTIONS, BUT
    15     WHERE VISUAL COMFORT IS IMPORTANT.                  0.63
    16     FOR SPACES WITHOUT TASKS AND WHERE VISUAL
    17     COMFORT IS NOT A CRITERION                          0.70
    18     (C)  OTHER CRITERIA; REFLECTANCES.--FOR INTERIOR SPACES, THE
    19  FOLLOWING INITIAL CAVITY AND SURFACE REFLECTANCES SHALL BE
    20  ASSUMED:
    21     CEILING CAVITY REFLECTANCE              80%
    22     WALL REFLECTANCE                        50%
    23     FLOOR CAVITY REFLECTANCE                20%
    24  LIGHT LOSS FACTOR.  A LIGHT LOSS FACTOR (LLF) OF 0.70 SHALL BE
    25  USED.
    26                            SUBCHAPTER I
    27                        ALTERNATIVE SYSTEMS
    28  SECTION 237.  PERFORMANCE ALTERNATIVE.
    29     ALTERNATIVE BUILDING SYSTEMS AND EQUIPMENT DESIGN MAY BE
    30  APPROVED BY THE DEPARTMENT WHEN THEY CAN BE SHOWN TO HAVE ENERGY
    19770S0583B2188                 - 43 -

     1  CONSUMPTION NOT GREATER THAN THAT OF A SIMILAR BUILDING WITH
     2  SIMILAR FORMS OF ENERGY REQUIREMENTS, DESIGNED IN ACCORDANCE
     3  WITH THE PROVISIONS OF THIS ACT OR WHEN THEY CAN BE SHOWN TO
     4  HAVE ENERGY CONSUMPTION NOT GREATER THAN THAT WHICH SHALL BE
     5  ESTABLISHED BY THE DEPARTMENT WITH THE APPROVAL OF THE BUILDING
     6  ENERGY CONSERVATION COMMITTEE, FOR THE PURPOSES OF THIS SECTION:
     7  PROVIDED, HOWEVER, THAT FOR ALL BUILDINGS CLASSIFIED AS USE
     8  GROUP R-3 ALTERNATE BUILDING SYSTEMS AND EQUIPMENT DESIGN WHICH
     9  SATISFY THE CRITERIA OF THIS SECTION SHALL NOT REQUIRE THE
    10  APPROVAL OF THE DEPARTMENT BUT THE USE OF SUCH AN ALTERNATE
    11  BUILDING SYSTEM OR EQUIPMENT DESIGN SHALL BE INDICATED IN THE
    12  WARRANTY PROVIDED IN SECTION 306.
    13  SECTION 238.  NONDEPLETABLE SOURCES.
    14     WHEN SUCH ALTERNATIVE SYSTEMS UTILIZE SOLAR, GEOTHERMAL, WIND
    15  OR OTHER NONDEPLETABLE ENERGY SOURCES FOR ALL OR PART OF THEIR
    16  ENERGY SOURCES, SUCH NONDEPLETABLE ENERGY SUPPLIED TO THE
    17  BUILDING SHALL BE EXCLUDED FROM THE TOTAL ENERGY CHARGEABLE TO
    18  THE PROPOSED ALTERNATIVE DESIGN.
    19  SECTION 239.  DOCUMENTATION.
    20     PROPOSED ALTERNATIVE DESIGNS, SUBMITTED TO THE DEPARTMENT AS
    21  REQUESTS FOR EXCEPTION TO THE STANDARD DESIGN CRITERIA, MUST BE
    22  ACCOMPANIED BY AN ENERGY ANALYSIS PREPARED IN ACCORDANCE WITH
    23  THE ASHRAE STANDARD 90-75.
    24                            SUBCHAPTER J
    25                USE GROUP R-3 PRESCRIPTIVE STANDARDS
    26  SECTION 240.  MINIMUM INSULATION REQUIREMENTS FOR USE GROUP R-3.
    27     USE GROUP R-3 BUILDINGS SHALL BE CONSTRUCTED UTILIZING THE
    28  FOLLOWING MINIMUM INSULATION STANDARDS:
    29  CEILINGS                                           R - 19
    30  EXTERIOR WALLS                                     R - 13
    19770S0583B2188                 - 44 -

     1  FLOORS OVER UNHEATED BASEMENTS
     2     AND CRAWL SPACES *                              R - 11
     3     * BASEMENTS CONTAINING A FURNACE
     4       AND/OR HOT WATER HEATER MAY BE
     5       CONSIDERED HEATED
     6  EDGE INSULATION FOR:
     7     HEATED SLABS                                    R - 6.3
     8     UNHEATED SLABS                                  R - 4.2
     9  WINDOWS                                        MULTIGLAZING
    10  ENTRANCE DOORS                                     R - 2.5
    11  SLIDING GLASS DOORS (IF APPLICABLE)            MULTIGLAZING
    12  DUCTS IN UNHEATED AREAS                            R - 3
    13                             CHAPTER 3
    14              APPLICATION OF STANDARDS: ESTABLISHMENT
    15                     OF COMMITTEE AND PENALTIES
    16  SECTION 301.  MODIFICATION OF STANDARDS; CRITERIA.
    17     THE DEPARTMENT, WITH THE APPROVAL OF THE BUILDING ENERGY
    18  CONSERVATION COMMITTEE ESTABLISHED PURSUANT TO SECTION 304,
    19  AFTER ONE OR MORE PUBLIC HEARINGS, MAY RECOMMEND TO THE GENERAL
    20  ASSEMBLY MODIFICATIONS TO THE ENERGY CONSERVATION STANDARDS
    21  CONTAINED IN CHAPTER 2 HEREOF. ANY RECOMMENDED MODIFICATION TO
    22  THE ENERGY CONSERVATION STANDARDS SHALL MEET THE FOLLOWING
    23  CRITERIA:
    24         (1)  IT SHALL BE CONSISTENT WITH THE LATEST AND MOST
    25     EFFECTIVE TECHNOLOGY.
    26         (2)  IT SHALL NOT BE IN CONFLICT WITH EXISTING SAFEGUARDS
    27     FOR PUBLIC HEALTH AND SAFETY.
    28         (3)  IT SHALL BE ECONOMICALLY FEASIBLE AS DETERMINED BY
    29     LIFE-CYCLE-COST PROCEDURES.
    30         (4)  IT SHALL BE SUFFICIENTLY STRINGENT TO EFFECT A
    19770S0583B2188                 - 45 -

     1     SIGNIFICANT SAVINGS OF ENERGY RESOURCES.
     2         (5)  IT SHALL BE A PERFORMANCE STANDARD FOR THE DESIGN OF
     3     BUILDINGS AND SYSTEMS WITHIN BUILDINGS TO ASSURE MAXIMUM
     4     PRACTICAL CONSERVATION OF ENERGY.
     5         (6)  CONSIDERATION SHALL BE GIVEN TO BUILDING AND ENERGY
     6     STANDARDS PROMULGATED BY NATIONAL AND OTHER STATE
     7     GOVERNMENTAL AGENCIES, PRIVATE ORGANIZATIONS AND ANY OTHER
     8     AVAILABLE ENERGY DATA, AS WELL AS THE TOTAL ENERGY ALLOCATION
     9     APPROACH.
    10  SECTION 302.  APPLICATION OF ENERGY CONSERVATION STANDARDS.
    11     THE ENERGY CONSERVATION STANDARDS CONTAINED HEREIN OR AS
    12  PROMULGATED BY THE DEPARTMENT WITH THE APPROVAL OF THE BUILDING
    13  ENERGY CONSERVATION COMMITTEE SHALL APPLY TO NEW BUILDINGS OR TO
    14  RENOVATIONS ON WHICH ACTUAL CONSTRUCTION AND/OR DESIGN HAS NOT
    15  COMMENCED PRIOR TO THEIR EFFECTIVE DATES. NO DEPARTMENT, BOARD,
    16  AGENCY OR COMMISSION OTHER THAN AS PROVIDED HEREIN, SHALL
    17  PROMULGATE OR ADOPT ANY RULES OR REGULATIONS WHICH DEAL WITH ANY
    18  SUBJECT MATTER CONTAINED IN THIS ACT.
    19  SECTION 303.  ENERGY CONSERVATION MANUAL FOR BUILDINGS.
    20     (A)  PRODUCTION OF MANUAL.--CONCURRENT WITH THE ADOPTION OF
    21  THE ENERGY CONSERVATION CODES REQUIRED BY THIS ACT, THE
    22  DEPARTMENT SHALL PRODUCE AN ENERGY CONSERVATION MANUAL FOR USE
    23  BY DESIGNERS, BUILDERS, CONTRACTORS OF RESIDENTIAL AND
    24  NONRESIDENTIAL BUILDINGS, AND MUNICIPALITIES OF THE
    25  COMMONWEALTH. THIS MANUAL SHALL CONTAIN THE ESTABLISHED
    26  STANDARDS AND ACCEPTED PRACTICES. THE MANUAL SHALL FURTHER
    27  CONTAIN PRESCRIPTIVE STANDARDS WHICH, IF COMPLIED WITH, WILL
    28  RESULT IN CONFORMANCE WITH THE PERFORMANCE STANDARDS CONTAINED
    29  HEREIN OR AS PROMULGATED BY THE DEPARTMENT AND SHALL BE WRITTEN
    30  IN SUCH MANNER AS TO BE EASILY UNDERSTOOD BY PERSONS POSSESSING
    19770S0583B2188                 - 46 -

     1  A MINIMAL TECHNICAL BACKGROUND. THE MANUAL SHALL BE FURNISHED
     2  UPON REQUEST TO MEMBERS OF THE PUBLIC AT A PRICE SUFFICIENT TO
     3  COVER THE COST OF PRINTING.
     4     (B)  REVIEW OF MANUAL.--THE MANUAL SHALL BE REVIEWED BY THE
     5  DEPARTMENT AND THE BUILDING ENERGY CONSERVATION COMMITTEE AT
     6  LEAST ANNUALLY AND SHALL BE UPDATED AS SIGNIFICANT NEW ENERGY
     7  CONSERVATION INFORMATION BECOMES AVAILABLE.
     8     (C)  EDUCATIONAL PROGRAMS.--THE DEPARTMENT SHALL PROVIDE
     9  SEMINARS AND OTHER EDUCATIONAL PROGRAMS THROUGHOUT THE
    10  COMMONWEALTH TO PROVIDE INFORMATION AND COUNSELING TO BUILDERS,
    11  ARCHITECTS, OTHER LICENSED DESIGN PROFESSIONALS, LOCAL BUILDING
    12  OFFICIALS AND OTHER PERSONS AFFECTED BY THIS ACT ON THE
    13  STANDARDS CONTAINED HEREIN OR AS PROMULGATED BY THE DEPARTMENT.
    14  SECTION 304.  BUILDING ENERGY CONSERVATION COMMITTEE.
    15     (A)  COMPOSITION OF COMMITTEE.--IN ORDER TO FURTHER THE
    16  COORDINATED AND EFFECTIVE ADMINISTRATION OF THIS ACT, THERE IS
    17  HEREBY ESTABLISHED A BUILDING ENERGY CONSERVATION COMMITTEE. IT
    18  SHALL CONSIST OF AT LEAST 30 MEMBERS AND NO MORE THAN 40
    19  MEMBERS, THE MEMBERSHIP OF WHICH SHALL BE APPOINTED BY THE
    20  GOVERNOR AND SHALL INCLUDE A REPRESENTATIVE OF EACH OF THE
    21  FOLLOWING ENTITIES OR THEIR SUCCESSORS:
    22         (1)  DEPARTMENT OF EDUCATION.
    23         (2)  GOVERNOR'S ENERGY COUNCIL.
    24         (3)  DEPARTMENT OF GENERAL SERVICES.
    25         (4)  DEPARTMENT OF LABOR AND INDUSTRY.
    26         (5)  DEPARTMENT OF COMMUNITY AFFAIRS.
    27         (6)  PENNSYLVANIA BUILDERS ASSOCIATION.
    28         (7)  PENNSYLVANIA ASSOCIATED BUILDERS AND CONTRACTORS,
    29     INC.
    30         (8)  PENNSYLVANIA BUILDING OFFICIALS CONFERENCE.
    19770S0583B2188                 - 47 -

     1         (9)  MECHANICAL CONTRACTORS ASSOCIATION OF AMERICA.
     2         (10)  PENNSYLVANIA CHAMBER OF COMMERCE.
     3         (11)  GENERAL CONTRACTORS ASSOCIATION OF PENNSYLVANIA.
     4         (12)  PENNSYLVANIA SOCIETY OF ARCHITECTS.
     5         (13)  PENNSYLVANIA SOCIETY OF PROFESSIONAL ENGINEERS.
     6         (14)  AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR
     7     CONDITIONING ENGINEERS, INC..
     8         (15)  PENNSYLVANIA GAS ASSOCIATION.
     9         (16)  PENNSYLVANIA ELECTRIC ASSOCIATION.
    10         (17)  INDUSTRIALIZED HOUSING MANUFACTURERS ASSOCIATION.
    11         (18)  THERMAL INSULATION MANUFACTURERS ASSOCIATION.
    12         (19)  PENNSYLVANIA BUILDING TRADES COUNCIL.
    13         (20)  CONSULTING ENGINEERS COUNCIL OF PENNSYLVANIA.
    14         (21)  PENNSYLVANIA LEAGUE OF CITIES.
    15         (22)  PENNSYLVANIA STATE ASSOCIATION OF BOROUGHS.
    16         (23)  PENNSYLVANIA STATE ASSOCIATION OF TOWNSHIP
    17     COMMISSIONERS.
    18         (24)  PENNSYLVANIA STATE ASSOCIATION OF TOWNSHIP
    19     SUPERVISORS.
    20         (25)  PUBLIC UTILITY COMMISSION.
    21         (26)  NATIONAL ASSOCIATION OF INDUSTRIAL AND OFFICE
    22     PARKS.
    23         (27)  PENNSYLVANIA UTILITIES, RAILROAD AND AREA
    24     DEVELOPMENT ASSOCIATION.
    25         (28)  REPRESENTATIVES OF SUCH OTHER AGENCIES AND
    26     ORGANIZATIONS OR INDIVIDUALS AS THE GOVERNOR MAY FIND ARE
    27     NECESSARY AND PROPER TO CARRY OUT THE PURPOSES OF THE
    28     COMMITTEE INCLUDING, BUT NOT LIMITED TO, LABOR ORGANIZATIONS,
    29     FINANCIAL AND LENDING INSTITUTIONS, AND CONSUMER GROUPS.
    30     (B)  POWERS AND DUTIES.--IN ADDITION TO THE POWERS AND DUTIES
    19770S0583B2188                 - 48 -

     1  ENUMERATED IN THIS ACT, THE BUILDING ENERGY CONSERVATION
     2  COMMITTEE SHALL:
     3         (1)  BE RESPONSIBLE FOR THE REGULAR EXCHANGE OF
     4     INFORMATION AND PLANS REGARDING BUILDING ENERGY CONSERVATION,
     5     FOR THE DEVELOPMENT, REVIEW AND APPROVAL OF PROPOSED AND
     6     EXISTING STANDARDS, GUIDELINES, REGULATIONS, AND MANUALS.
     7         (2)  ELECT FROM ITS MEMBERS A BOARD ON VARIANCES.
     8     (C)  EXPENSES.--THE MEMBERS OF THE COMMITTEE SHALL NOT
     9  RECEIVE ANY COMPENSATION FOR THEIR SERVICES BUT SHALL BE
    10  REIMBURSED FOR THEIR ACTUAL AND NECESSARY EXPENSES INCURRED IN
    11  THE PERFORMANCE OF THEIR DUTIES. PROVIDED, HOWEVER, WHEN ACTING
    12  ON MATTERS CONCERNING VARIANCES MEMBERS OF THE BOARD ON
    13  VARIANCES SHALL RECEIVE $50 PER DAY PLUS THEIR ACTUAL AND
    14  NECESSARY EXPENSES.
    15  SECTION 305.  CERTIFICATION.
    16     (A)  APPLICABILITY.--THE PROVISIONS OF THIS SECTION SHALL
    17  APPLY TO ALL BUILDINGS SUBJECT TO THIS ACT EXCEPT THOSE
    18  CLASSIFIED AS USE GROUP R-3.
    19     (B)  COMPLIANCE WITH ACT.--IT SHALL BE THE DUTY OF THE
    20  LICENSED DESIGN PROFESSIONAL RETAINED IN CONNECTION WITH THE
    21  DESIGN OR CONSTRUCTION OF A BUILDING TO CERTIFY THE DRAWINGS,
    22  SPECIFICATIONS AND OTHER DATA SHOWING COMPLIANCE WITH THE
    23  PROVISIONS OF THIS ACT, EXCEPT AS PROVIDED IN SUBSECTION (E). IF
    24  THE BUILDING IS SUBJECT TO THE PROVISIONS OF THE ACT OF APRIL
    25  27, 1927 (P.L.465, NO.299), REFERRED TO AS THE FIRE AND PANIC
    26  ACT, THE CERTIFICATION REQUIRED HEREUNDER SHALL BE SUBMITTED ON
    27  A FORM WITH THE APPLICATION FOR PLAN APPROVAL UNDER THE SAID
    28  FIRE AND PANIC ACT.
    29     (C)  INSPECTION.--EACH LICENSED DESIGN PROFESSIONAL RETAINED
    30  BY THE OWNER OR HIS DESIGNEE, WHERE ANY OF SUCH ARE RETAINED
    19770S0583B2188                 - 49 -

     1  DURING THE CONSTRUCTION OF A BUILDING, SHALL MAKE PERIODIC
     2  INSPECTIONS OF THE BUILDING PROGRESSION TO INSURE COMPLIANCE
     3  WITH THIS ACT, EXCEPT AS PROVIDED IN SUBSECTION (E).
     4     (D)  FINAL CERTIFICATION.--EACH LICENSED DESIGN PROFESSIONAL
     5  RETAINED BY THE OWNER SHALL MAKE A FINAL CERTIFICATION OF EVERY
     6  COMPLETED BUILDING SHOWING COMPLIANCE WITH THE PROVISIONS OF
     7  THIS ACT, EXCEPT AS PROVIDED IN SUBSECTION (E).
     8     (E)  CERTIFICATION BY BUILDER.--IF A LICENSED DESIGN
     9  PROFESSIONAL IS NOT RETAINED IN CONNECTION WITH THE DESIGN AND
    10  CONSTRUCTION OF A BUILDING, IT SHALL BE THE RESPONSIBILITY OF
    11  THE BUILDER OR OWNER, IF HE IS THE BUILDER, TO PERFORM THE
    12  INSPECTIONS AND CERTIFICATION REQUIRED BY THIS SECTION.
    13  SECTION 306.  USE GROUP R-3; NOTICE; WARRANTY.
    14     (A)  NOTICE.--PRIOR TO CONSTRUCTION OF ANY BUILDING
    15  CLASSIFIED AS USE GROUP R-3, THE BUILDER SHALL NOTIFY THE
    16  DEPARTMENT BY CERTIFIED MAIL OF HIS INTENT TO BEGIN
    17  CONSTRUCTION. SUCH NOTICE SHALL CONTAIN THE NAME OF THE OWNER OF
    18  THE BUILDING AND ITS LOCATION.
    19     (B)  WARRANTY.--AT THE TIME A CONTRACT FOR THE CONSTRUCTION
    20  OF ANY BUILDING CLASSIFIED AS USE GROUP R-3 IS ENTERED INTO, THE
    21  BUILDER SHALL WARRANT TO THE OWNER IN WRITING THAT THE BUILDING
    22  SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS OF THIS
    23  ACT. SUCH WARRANTY SHALL BE A DOCUMENT SEPARATE FROM THE
    24  CONTRACT AND SHALL BE IN THE FOLLOWING FORM:
    25     I,  (BUILDER)  , HEREBY WARRANT TO  (OWNER)  THAT THE
    26  PREMISES KNOWN AS  (DESCRIPTION)
    27  SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS OF THE
    28  ACT OF __________, 19__, NO.____, KNOWN AS THE "BUILDING ENERGY
    29  CONSERVATION ACT."  THIS LAW PROVIDES BUILDING AND EQUIPMENT
    30  STANDARDS TO MAKE YOUR HOME ENERGY EFFICIENT AND ALSO PROVIDES
    19770S0583B2188                 - 50 -

     1  YOU WITH LEGAL REMEDIES IF YOUR HOME IS NOT BUILT ACCORDING TO
     2  THE STATE STANDARDS.  IF YOU WOULD LIKE THE STATE TO DO AN
     3  ENERGY AUDIT OF YOUR HOME TO DETERMINE IF IT CONFORMS TO STATE
     4  STANDARDS, YOU MAY CALL THE PENNSYLVANIA DEPARTMENT OF
     5  COMMUNITY AFFAIRS AT  (TELEPHONE)  , AND THEY WILL PERFORM AN
     6  INSPECTION OF YOUR HOME FOR A FEE OF $25.
     7     INDICATE IF ALTERNATE BUILDING SYSTEM OR EQUIPMENT DESIGN IS
     8  BEING EMPLOYED.
     9     (C)  IF THE BUILDER IS ALSO THE OWNER OF THE BUILDING AT THE
    10  TIME OF CONSTRUCTION, HE SHALL PROVIDE THE WARRANTY REQUIRED BY
    11  SUBSECTION (B) AT THE TIME OF ITS INITIAL SALE TO A NEW OWNER.
    12  SUCH WARRANTY SHALL BE IN SUBSTANTIALLY THE SAME FORM AS
    13  PROVIDED IN SUBSECTION (B).
    14     (D)  FAILURE TO PROVIDE NOTICE.--THE DEPARTMENT OF COMMUNITY
    15  AFFAIRS, AFTER HEARING, MAY ASSESS A CIVIL PENALTY PAYABLE TO
    16  THE COMMONWEALTH OF PENNSYLVANIA NOT TO EXCEED $100 UPON ANY
    17  BUILDER WHO FAILS TO GIVE THE NOTICE REQUIRED BY SUBSECTION (A).
    18  IN DETERMINING THE AMOUNT OF THE CIVIL PENALTY, THE DEPARTMENT
    19  OF COMMUNITY AFFAIRS SHALL CONSIDER THE WILLFULNESS OF THE
    20  VIOLATION AND THE COST INCURRED BY THE DEPARTMENT IN DISCOVERING
    21  THE VIOLATION.
    22     (E)  FAILURE TO PROVIDE WARRANTY.--WHENEVER A BUILDER FAILS
    23  TO PROVIDE THE WARRANTY REQUIRED BY SUBSECTIONS (B) OR (C) SUCH
    24  REQUIRED WARRANTY SHALL CONSTITUTE AN IMPLIED WARRANTY AND THE
    25  OWNER'S RIGHT TO PROCEED UNDER SECTION 315(A) SHALL NOT BE
    26  AFFECTED. IF IT IS ESTABLISHED BY A PREPONDERANCE OF THE
    27  EVIDENCE THAT THE BUILDER'S FAILURE TO PROVIDE THE WARRANTY WAS
    28  WILLFUL, THEN DAMAGES IN TWICE THE AMOUNT PROVIDED IN SECTION
    29  315 MAY BE AWARDED.
    30  SECTION 307.  VARIANCES.
    19770S0583B2188                 - 51 -

     1     (A)  REQUESTS.--ANY REQUEST FOR A VARIANCE FROM THE ENERGY
     2  CONSERVATION STANDARDS CONTAINED HEREIN SHALL BE MADE TO THE
     3  BOARD ON VARIANCES OF THE BUILDING ENERGY CONSERVATION COMMITTEE
     4  AND A DECISION ON SUCH REQUEST SHALL BE MADE WITHIN 30 DAYS OF
     5  ITS FILING.
     6     (B)  CRITERIA.--A VARIANCE SHALL BE GRANTED ONLY IF IT IS
     7  FOUND THAT:
     8         (1)  COMPLIANCE WITH THE PROVISIONS OF THIS ACT WOULD
     9     RESULT IN EXTREME HARDSHIP TO THE OWNER; AND
    10         (2)  THE GRANTING OF SUCH VARIANCE WOULD NOT RESULT IN A
    11     SIGNIFICANT INCREASE IN THE ENERGY USAGE OF THE BUILDING.
    12  SECTION 308.  BUILDING PERMITS.
    13     ANY BUILDING PERMIT ISSUED BY THE COMMONWEALTH OR ANY OF ITS
    14  POLITICAL SUBDIVISIONS SHALL HAVE PRINTED UPON ITS FACE NOTICE
    15  THAT THE PROVISIONS OF THIS ACT MUST BE COMPLIED WITH.
    16  SECTION 309.  PERMITS FOR USE OR OCCUPANCY.
    17     BEFORE ANY BUILDING OR STRUCTURE HEREAFTER CONSTRUCTED, OTHER
    18  THAN A BUILDING CLASSIFIED AS USE GROUP R-3, SHALL BE USED OR
    19  OPENED FOR OCCUPANCY, THE OWNER THEREOF SHALL NOTIFY THE
    20  DEPARTMENT OF THE COMPLETION OF THE BUILDING FOR THE PURPOSES OF
    21  THIS ACT AND SUBMIT THE NECESSARY CERTIFICATION THEREWITH:
    22  PROVIDED, HOWEVER, THAT IF A MUNICIPALITY ELECTS TO ADMINISTER
    23  THE PROVISIONS OF THIS ACT UNDER CHAPTER 5 SUCH NOTICE AND
    24  CERTIFICATION SHALL BE SUBMITTED TO THE MUNICIPALITY WHICH SHALL
    25  FORWARD A COPY OF THE NOTICE TO THE DEPARTMENT. NO PERMIT FOR
    26  USE OR OCCUPANCY SHALL BE GRANTED UNTIL SUCH SUBMISSION HAS BEEN
    27  MADE. NO BUILDING OFFICIAL OF THE COMMONWEALTH OR ANY OF ITS
    28  POLITICAL SUBDIVISIONS SHALL ISSUE A PERMIT UNTIL HE HAS
    29  RECEIVED PROOF OF SUCH COMPLIANCE. WHERE THE CERTIFICATE HAS
    30  BEEN SUBMITTED TO THE DEPARTMENT, PRESENTATION TO THE BUILDING
    19770S0583B2188                 - 52 -

     1  OFFICIAL OF THE MAILING RECEIPT TOGETHER WITH A COPY OF THE
     2  CERTIFICATION REQUIRED BY SECTION 305 SHALL ESTABLISH PROOF OF
     3  COMPLIANCE FOR THE PURPOSES OF THIS SECTION. UPON SUCH
     4  PRESENTATION ANY BUILDING OFFICIAL OF THE COMMONWEALTH OR ANY OF
     5  ITS POLITICAL SUBDIVISIONS SHALL ISSUE A PERMIT FOR USE OR
     6  OCCUPANCY, PROVIDED ALL OTHER CRITERIA FOR SUCH A PERMIT HAVE
     7  BEEN SATISFIED AND SAID BUILDING OFFICIAL SHALL NOTIFY THE
     8  DEPARTMENT THAT HE HAS ISSUED THE SAME.
     9  SECTION 310.  FAILURE TO SUBMIT CERTIFICATION.
    10     WHENEVER THE OWNER OF ANY BUILDING, OTHER THAN A BUILDING
    11  CLASSIFIED AS USE GROUP R-3, SHALL FAIL TO GIVE THE NOTICE AND
    12  SUBMIT THE NECESSARY CERTIFICATION IN ACCORDANCE WITH SECTION
    13  309 AND SHALL NEVERTHELESS PROCEED WITH THE USE OR OCCUPANCY OF
    14  THE BUILDING, THE DEPARTMENT OR THE MUNICIPALITY SHALL SERVE
    15  NOTICE ON THE SAID OWNER THAT HE IS IN VIOLATION OF THIS ACT AND
    16  ORDER HIM TO COMPLY THEREWITH.
    17  SECTION 311.  INSPECTIONS.
    18     THE DEPARTMENT MAY PERFORM A NONDESTRUCTIVE INSPECTION WITHIN
    19  TWO YEARS OF THE DATE OF COMPLETION OF CONSTRUCTION OF ANY
    20  BUILDING CONSTRUCTED AFTER THE EFFECTIVE DATE OF THIS ACT TO
    21  DETERMINE COMPLIANCE WITH THE PROVISIONS OF THIS ACT, PROVIDED
    22  AT LEAST 30 DAYS NOTICE HAS BEEN GIVEN TO THE OWNER. THE
    23  DEPARTMENT MAY ALSO PERFORM SUCH INSPECTIONS AT THE REQUEST OF
    24  THE OWNER OF ANY BUILDING SUBJECT TO THIS ACT FOR A FEE OF $25.
    25  SECTION 312.  APPEALS.
    26     REVIEW OF ANY DECISIONS RENDERED UNDER THE PROVISIONS OF THIS
    27  ACT SHALL BE BROUGHT IN THE COURT OF COMMON PLEAS OF THE COUNTY
    28  WHEREIN THE BUILDING IS SITUATED. SUCH REVIEW SHALL BE LIMITED
    29  TO DETERMINING WHETHER ANY SUCH DECISION WAS ARBITRARY AND
    30  CAPRICIOUS.
    19770S0583B2188                 - 53 -

     1  SECTION 313.  PENALTIES.
     2     (A)  APPLICABILITY.--THE PROVISIONS OF THIS SECTION SHALL
     3  APPLY TO ALL BUILDINGS SUBJECT TO THIS ACT EXCEPT THOSE
     4  CLASSIFIED AS USE GROUP R-3.
     5     (B)  VIOLATIONS OF ACT.--ANY PERSON WHO SHALL WILLFULLY OR
     6  NEGLIGENTLY VIOLATE ANY OF THE PROVISIONS OF THIS ACT, OR THE
     7  RULES AND REGULATIONS OR THE ORDERS FOR THE ENFORCEMENT OF THE
     8  SAID PROVISIONS OR RULES AND REGULATIONS ISSUED BY DULY
     9  AUTHORIZED OFFICERS OF THE DEPARTMENT OR WHO SHALL HINDER, DELAY
    10  OR INTERFERE WITH ANY OFFICER CHARGED WITH THE ENFORCEMENT OF
    11  THIS ACT IN THE PERFORMANCE OF HIS DUTY, SHALL, UPON CONVICTION
    12  THEREOF, BE PUNISHED BY A FINE OF NOT MORE THAN $300 AND COSTS.
    13  IN THE EVENT OF VIOLATION OF MORE THAN ONE PROVISION OF THIS
    14  ACT, THE VIOLATION OF EACH PROVISION SHALL BE DEEMED A SEPARATE
    15  AND DISTINCT OFFENSE FOR THE PURPOSES OF THIS SECTION.
    16     (C)  INSTITUTION OF PROCEEDINGS.--PROSECUTIONS FOR VIOLATIONS
    17  OF THIS ACT OR THE RULES AND REGULATIONS OF THE DEPARTMENT MAY
    18  BE INSTITUTED BY THE SECRETARY OF LABOR AND INDUSTRY OR UNDER
    19  HIS DIRECTIONS BY AN AUTHORIZED REPRESENTATIVE OF THE
    20  DEPARTMENT. UPON CONVICTION AFTER A HEARING IN A COURT OF
    21  COMPETENT JURISDICTION, THE SENTENCES PROVIDED IN THIS ACT SHALL
    22  BE IMPOSED AND SHALL BE FINAL UNLESS AN APPEAL BE TAKEN IN THE
    23  MANNER PRESCRIBED BY LAW.
    24     (D)  DISPOSITION OF FINES.--ALL FINES COLLECTED UNDER THIS
    25  ACT SHALL BE FORWARDED TO THE DEPARTMENT WHO SHALL PAY THE SAME
    26  INTO THE STATE TREASURY FOR THE USE OF THE COMMONWEALTH.
    27     (E)  FALSE CERTIFICATION.--ANY ARCHITECT OR OTHER LICENSED
    28  DESIGN PROFESSIONAL WHO WILLFULLY PROVIDES A FALSE CERTIFICATION
    29  FOR ANY BUILDING SUBJECT TO THE PROVISIONS OF THIS ACT SHALL BE
    30  SUBJECT TO THE SUSPENSION OR REVOCATION OF HIS LICENSE BY THE
    19770S0583B2188                 - 54 -

     1  STATE BOARD OF EXAMINERS OF ARCHITECTS OR OTHER APPLICABLE STATE
     2  LICENSING BOARD.
     3  SECTION 314.  ENFORCEMENT.
     4     (A)  APPLICABILITY.--THE PROVISIONS OF THIS ACT SHALL APPLY
     5  TO EVERY BUILDING ENUMERATED IN THIS ACT, INCLUDING BUILDINGS
     6  OWNED IN WHOLE OR IN PART BY THE COMMONWEALTH OR ANY POLITICAL
     7  SUBDIVISION THEREOF, AND FOR ALL BUILDINGS, OTHER THAN THOSE
     8  CLASSIFIED AS USE GROUP R-3 SHALL BE ENFORCED BY THE SECRETARY
     9  OF LABOR AND INDUSTRY, BY AND THROUGH HIS AUTHORIZED
    10  REPRESENTATIVES.
    11     (B)  POWERS OF OFFICERS.--FOR THE PURPOSE OF ENFORCING THE
    12  PROVISIONS OF THIS ACT, ALL THE OFFICERS CHARGED WITH ITS
    13  ENFORCEMENT SHALL HAVE THE POWER TO ENTER ANY OF THE BUILDINGS
    14  ENUMERATED IN THIS ACT, AND NO PERSON SHALL HINDER OR DELAY, OR
    15  INTERFERE WITH ANY OF THE SAID OFFICERS IN THE PERFORMANCE OF
    16  HIS DUTY, NOR REFUSE ANY PERTINENT INFORMATION NECESSARY TO
    17  DETERMINE WHETHER THE PROVISIONS OF THIS ACT AND THE RULES AND
    18  REGULATIONS HEREIN PROVIDED FOR, ARE OR WILL BE COMPLIED WITH.
    19  SECTION 315.  CIVIL ACTION.
    20     (A)  USE GROUP R-3.--THE OWNER OF ANY BUILDING SUBJECT TO THE
    21  REQUIREMENTS OF SECTION 306 WHO IS AGGRIEVED AS THE RESULT OF
    22  SUCH BUILDING NOT BEING PROPERLY DESIGNED OR CONSTRUCTED IN
    23  CONFORMANCE WITH THIS ACT SHALL HAVE A RIGHT OF ACTION FOR
    24  BREACH OF WARRANTY. REMEDIES MAY INCLUDE SPECIFIC PERFORMANCE OR
    25  AN AWARD OF DAMAGES IN AN AMOUNT NOT LESS THAN $300. ATTORNEY'S
    26  FEES SHALL BE RECOVERABLE IN ANY ACTION IN WHICH THE OWNER
    27  PREVAILS. ANY SUCH AWARD SHALL FURTHER PROVIDE FOR PAYMENT OF
    28  THE ACTUAL COSTS IN EXCESS OF $25 INCURRED BY THE DEPARTMENT IF
    29  IT INSPECTED THE BUILDING FOR THE OWNER AND THE OWNER SHALL
    30  REMIT SUCH AMOUNT TO THE DEPARTMENT.
    19770S0583B2188                 - 55 -

     1     (B)  OTHER BUILDINGS.--THE OWNER OF ANY BUILDING, OTHER THAN
     2  A BUILDING CLASSIFIED AS USE GROUP R-3, AT THE TIME OF ITS
     3  DESIGN OR CONSTRUCTION UNDER THE PROVISIONS OF THIS ACT WHO IS
     4  AGGRIEVED AS THE RESULT OF SUCH BUILDING NOT BEING PROPERLY
     5  DESIGNED OR CONSTRUCTED IN CONFORMANCE WITH THIS ACT SHALL HAVE
     6  A RIGHT OF ACTION AGAINST ANY PERSON WHO IS REQUIRED TO SUBMIT
     7  THE CERTIFICATE REQUIRED BY SECTION 305.
     8     (C)  LIMITATION OF ACTION.--NO ACTION BROUGHT UNDER THIS
     9  SECTION SHALL BE MAINTAINED UNLESS BROUGHT WITHIN THREE YEARS
    10  FROM THE DATE OF COMPLETION OF THE BUILDING.
    11                             CHAPTER 4
    12                    ADOPTION OF FUTURE STANDARDS
    13  SECTION 401.  ADOPTION AND PROMULGATION OF STANDARDS.
    14     THE DEPARTMENT, WITH THE APPROVAL OF THE BUILDING ENERGY
    15  CONSERVATION COMMITTEE, SHALL, AFTER ONE OR MORE PUBLIC
    16  HEARINGS, ADOPT AND PUBLISH ENERGY CONSERVATION STANDARDS FOR
    17  ALL BUILDINGS COVERED BY THIS ACT IN ACCORDANCE WITH THE
    18  PROVISIONS OF THE ACT OF JULY 31, 1968 (P.L.769, NO.240), KNOWN
    19  AS THE "COMMONWEALTH DOCUMENTS LAW." THE PURPOSE OF SUCH
    20  STANDARDS IS TO REDUCE WASTEFUL OR UNECONOMIC CONSUMPTION OF
    21  ENERGY BY BALANCING THE COST OF ENERGY PROCUREMENT AGAINST THE
    22  COST OF ENERGY-CONSERVING BUILDING PRACTICES. THE ENERGY
    23  CONSERVATION STANDARDS SHALL MEET THE FOLLOWING CRITERIA:
    24         (1)  THEY SHALL BE CONSISTENT WITH THE LATEST AND MOST
    25     EFFECTIVE TECHNOLOGY.
    26         (2)  THEY SHALL NOT BE IN CONFLICT WITH EXISTING
    27     SAFEGUARDS FOR PUBLIC HEALTH AND SAFETY.
    28         (3)  THEY SHALL BE ECONOMICALLY FEASIBLE AS DETERMINED BY
    29     LIFE-CYCLE-COST PROCEDURES.
    30         (4)  THEY SHALL BE SUFFICIENTLY STRINGENT TO EFFECT A
    19770S0583B2188                 - 56 -

     1     SIGNIFICANT SAVINGS OF ENERGY RESOURCES.
     2         (5)  THEY SHALL BE A PERFORMANCE STANDARD FOR THE DESIGN
     3     OF BUILDINGS AND SYSTEMS WITHIN BUILDINGS TO ASSURE MAXIMUM
     4     PRACTICAL CONSERVATION OF ENERGY.
     5         (6)  CONSIDERATION SHALL BE GIVEN TO BUILDING AND ENERGY
     6     STANDARDS PROMULGATED BY NATIONAL AND OTHER STATE
     7     GOVERNMENTAL AGENCIES, PRIVATE ORGANIZATIONS AND ANY OTHER
     8     AVAILABLE ENERGY DATA, AS WELL AS THE TOTAL ENERGY ALLOCATION
     9     APPROACH.
    10                             CHAPTER 5
    11                           LOCAL ELECTION
    12  SECTION 501.  ELECTION; USE GROUP R-3.
    13     ANY MUNICIPALITY OF THIS COMMONWEALTH MAY ELECT TO ADMINISTER
    14  THE PROVISIONS OF THIS ACT RELATING TO USE GROUP R-3 BUILDINGS,
    15  AS DEFINED IN SECTION 103, EXCEPT FOR UNITS SUBJECT TO THE ACT
    16  OF MAY 11, 1972 (P.L.286, NO.70), KNOWN AS THE "INDUSTRIALIZED
    17  HOUSING ACT" AND THE ACT OF MAY 11, 1972 (P.L.281, NO.69), KNOWN
    18  AS THE "UNIFORM STANDARDS CODE FOR MOBILE HOMES." SUCH ELECTION
    19  SHALL BE MADE BY RESOLUTION OF THE GOVERNING BODY OF SUCH
    20  MUNICIPALITY WHICH SHALL BE IN SUBSTANTIALLY THE FOLLOWING FORM:
    21     THE (CITY, BOROUGH, TOWN, OR TOWNSHIP) OF____________________
    22  HEREBY ELECTS TO ADMINISTER THE PROVISIONS OF THE ACT
    23  OF____________, 1978, NO._______ KNOWN AS THE "BUILDING ENERGY
    24  CONSERVATION ACT" FOR USE GROUP R-3 BUILDINGS AS DEFINED
    25  THEREIN.
    26  SECTION 502.  ELECTION; CITIES OF THE FIRST, SECOND AND SECOND
    27                CLASS A.
    28     ANY CITY OF THE FIRST CLASS, SECOND CLASS AND SECOND CLASS A
    29  MAY ELECT TO ADMINISTER THE PROVISIONS OF THIS ACT FOR ALL
    30  BUILDINGS SUBJECT HERETO, EXCEPT FOR UNITS SUBJECT TO THE ACT OF
    19770S0583B2188                 - 57 -

     1  MAY 11, 1972 (P.L.286, NO.70), KNOWN AS THE "INDUSTRIALIZED
     2  HOUSING ACT" AND THE ACT OF MAY 11, 1972 (P.L.281, NO.69), KNOWN
     3  AS THE "UNIFORM STANDARDS CODE FOR MOBILE HOMES." SUCH ELECTION
     4  SHALL BE MADE BY RESOLUTION OF THE GOVERNING BODY OF SUCH CITY
     5  WHICH SHALL BE IN SUBSTANTIALLY THE FOLLOWING FORM:
     6     THE CITY OF________________HEREBY ELECTS TO ADMINISTER THE
     7  PROVISIONS OF THE ACT OF _________, 1978, NO._______ KNOWN AS
     8  THE "BUILDING ENERGY CONSERVATION ACT."
     9  SECTION 503.  POWERS OF MUNICIPALITIES.
    10     ANY MUNICIPALITY ELECTING TO ADMINISTER THE PROVISIONS OF
    11  THIS ACT UNDER SECTION 501 OR 502 SHALL EXERCISE THE SAME POWERS
    12  CONFERRED UPON THE DEPARTMENT BY THIS ACT, INCLUDING THE POWER
    13  TO INSTITUTE PROCEEDINGS FOR VIOLATIONS OF THE ACT, WITH THE
    14  EXCEPTION OF THOSE POWERS SPECIFIED IN SECTIONS 301, 303 AND IN
    15  CHAPTER 4. IN ADDITION, ANY SUCH MUNICIPALITY MAY EXERCISE SUCH
    16  OTHER ADMINISTRATIVE AND ENFORCEMENT PROCEDURES AS IT SHALL DEEM
    17  NECESSARY TO EFFECT THE PURPOSES OF THIS ACT INCLUDING, BUT NOT
    18  LIMITED TO, PRIOR PLAN APPROVAL, BUILDING PERMIT REQUIREMENTS,
    19  USE OR OCCUPANCY PERMIT REQUIREMENTS AND INSPECTIONS DURING THE
    20  COURSE OF CONSTRUCTION.
    21  SECTION 504.  VARIANCES.
    22     ANY MUNICIPALITY ELECTING TO ADMINISTER THE PROVISIONS OF
    23  THIS ACT UNDER SECTION 501 OR 502 SHALL ESTABLISH A BOARD ON
    24  VARIANCES TO MAKE DETERMINATIONS ON REQUEST FOR VARIANCE FROM
    25  THE ENERGY CONSERVATION STANDARDS CONTAINED HEREIN OR AS
    26  PROMULGATED BY THE DEPARTMENT WITH THE APPROVAL OF THE BUILDING
    27  ENERGY CONSERVATION COMMITTEE, AND IS AUTHORIZED EXCLUSIVE
    28  JURISDICTION TO GRANT SUCH VARIANCES, SECTION 307(A)
    29  NOTWITHSTANDING. A VARIANCE SHALL ONLY BE GRANTED IF THE
    30  CRITERIA OF SECTION 307(B) HAVE BEEN SATISFIED.
    19770S0583B2188                 - 58 -

     1  SECTION 505.  DISPOSITION OF FINES.
     2     ANY FINES COLLECTED UNDER THIS ACT BY ANY MUNICIPALITY
     3  ELECTING TO ADMINISTER THE PROVISIONS OF THIS ACT UNDER SECTION
     4  501 OR 502 SHALL BE RETAINED BY THE MUNICIPALITY, SECTION 313(C)
     5  NOTWITHSTANDING.
     6                             CHAPTER 6
     7                     REPORT TO GENERAL ASSEMBLY
     8  SECTION 601.  REPORT TO GENERAL ASSEMBLY.
     9     THIRTY MONTHS AFTER THE EFFECTIVE DATE OF THIS ACT, THE
    10  DEPARTMENT SHALL REPORT TO THE GENERAL ASSEMBLY THE RESULTS OF
    11  THE INSPECTIONS IT HAS PERFORMED UNDER THIS ACT TOGETHER WITH A
    12  REPORT ON PUBLIC COMPLIANCE WITH THIS ACT.
    13  SECTION 602.  EFFECTIVE DATE.
    14     THIS ACT SHALL TAKE EFFECT AS FOLLOWS:
    15         (1)  CHAPTER 2 SHALL TAKE EFFECT IN SIX MONTHS JANUARY 1,  <--
    16     1980 AND SHALL REMAIN IN FULL FORCE AND EFFECT FOR A PERIOD
    17     OF ONE YEAR AFTER WHICH TIME THE PROVISIONS OF CHAPTER 2
    18     SHALL HAVE NO LEGAL EFFECT.
    19         (2)  SECTION 301 SHALL TAKE EFFECT IMMEDIATELY JULY 1,     <--
    20     1979 AND ITS PROVISIONS SHALL REMAIN IN FULL FORCE AND EFFECT
    21     FOR A PERIOD OF 18 MONTHS AFTER WHICH TIME SAID PROVISIONS
    22     SHALL HAVE NO LEGAL EFFECT.
    23         (3)  CHAPTER 4 SHALL TAKE EFFECT IN 18 MONTHS JANUARY 1,   <--
    24     1981.
    25         (4)  ALL OTHER PROVISIONS OF THIS ACT SHALL TAKE EFFECT
    26     IMMEDIATELY JULY 1, 1979.                                      <--



    C14L54JLW/19770S0583B2188       - 59 -