PRIOR PRINTER'S NOS. 600, 1775, 2328, PRINTER'S NO. 3369 2464, 2503, 2905
No. 552 Session of 1977
INTRODUCED BY MESSRS. ITKIN, B. F. O'BRIEN, TRELLO, GAMBLE, McCALL, LEHR, SWEET AND J. L. WRIGHT, MARCH 7, 1977
AS AMENDED ON THIRD CONSIDERATION, HOUSE OF REPRESENTATIVES, JUNE 7, 1978
AN ACT 1 Providing for the regulation for energy conservation purposes of 2 the construction of buildings, the establishment of a 3 Building Energy Conservation Committee and a Board on 4 Variances, appeals and for penalties. 5 TABLE OF CONTENTS 6 Chapter 1. General Provisions 7 Section 101. Short title. 8 Section 102. Legislative findings and declaration of 9 purpose. 10 Section 103. Definitions. 11 Chapter 2. Energy Conservation Standards 12 Subchapter A. General Provisions 13 Section 201. Provisions. 14 Subchapter B. Plans and Specifications 15 Section 202. Submission. 16 Section 203. Contents. 17 Subchapter C. Definitions Relating to Energy Conservation 18 Standards
1 Section 204. Definitions relating to standards. 2 Subchapter D. Building Envelope 3 Section 205. General provisions. 4 Section 206. Criteria for residential buildings. 5 Section 207. Other buildings. 6 Section 208. Air leakage. 7 Subchapter E. Warm Air Heating, Ventilating and Air 8 Conditioning Systems and Equipment 9 Section 209. General provisions. 10 Section 210. Design requirements. 11 Section 211. Cooling with outdoor air. 12 Section 212. Mechanical ventilation. 13 Section 213. Simultaneous heating and cooling. 14 Section 214. Recovered energy. 15 Section 215. New energy. 16 Section 216. Reheat systems. 17 Section 217. Dual duct and multizone systems. 18 Section 218. Recooling systems. 19 Section 219. Multiple zones. 20 Section 220. Concurrent operation. 21 Section 221. Equipment performance requirements. 22 Section 222. Duct insulation. 23 Section 223. System controls. 24 Section 224. Steam and hot water heating piping. 25 Subchapter F. Plumbing Systems 26 Section 225. Purpose. 27 Section 226. Fixtures. 28 Section 227. Insulation. 29 Section 228. Equipment. 30 Section 229. Controls. 19770H0552B3369 - 2 -
1 Subchapter G. Electrical Systems 2 Section 230. System requirements. 3 Subchapter H. Lighting 4 Section 231. Light power budget. 5 Section 232. Calculation methods. 6 Section 233. Building interiors. 7 Section 234. Building exteriors. 8 Section 235. Exceptions to criteria. 9 Section 236. Calculation procedure. 10 Subchapter I. Alternative Systems 11 Section 237. Performance alternative. 12 Section 238. Nondepletable sources. 13 Section 239. Documentation. 14 SUBCHAPTER J. USE GROUP R-3 PRESCRIPTIVE STANDARDS <-- 15 SECTION 240. MINIMUM INSULATION REQUIREMENTS FOR USE 16 GROUP R-3. 17 Chapter 3. Application of Standards: Establishment of 18 Committee and Penalties 19 Section 301. Modification of standards; criteria. 20 Section 302. Application of energy conservation standards. 21 Section 303. Energy conservation manual for buildings. 22 Section 304. Building Energy Conservation Committee. 23 Section 305. Certification. 24 Section 306. Use Group R-3; Notice; Warranty. 25 Section 307. Variances. 26 Section 308. Building permits. 27 Section 309. Permits for use or occupancy. 28 Section 310. Failure to submit certification. 29 Section 311. Inspections. 30 Section 312. Appeals. 19770H0552B3369 - 3 -
1 Section 313. Penalties. 2 Section 314. Enforcement. 3 Section 315. Civil action. 4 Chapter 4. Adoption of Future Standards 5 Section 401. Adoption and promulgation of standards. 6 Chapter 5. Local Election 7 Section 501. Election; Use Group R-3. 8 Section 502. Election; cities of the first, second and 9 second class A. 10 Section 503. Powers of municipalities. 11 Section 504. Variances. 12 Section 505. Disposition of fines. 13 Chapter 6. Report to General Assembly 14 Section 601. Report to General Assembly 15 Section 602. Effective date. 16 The General Assembly of the Commonwealth of Pennsylvania 17 hereby enacts as follows: 18 CHAPTER 1 19 GENERAL PROVISIONS 20 Section 101. Short title. 21 This act shall be known and may be cited as the "Building 22 Energy Conservation Act." 23 Section 102. Legislative findings and declaration of purpose. 24 (a) Findings.--The Legislature hereby determines that: 25 (1) Energy shortages in the domestic supply present far- 26 reaching problems that promise to persist. These energy 27 shortages affect the continued efficient operation of the 28 Commonwealth's economy and social structure. 29 (2) It is the Commonwealth's responsibility to provide 30 for energy conservation through regulation of design and 19770H0552B3369 - 4 -
1 construction standards. 2 (3) The Legislature intends, by this act, to respond to 3 these shortages by devising a specific responsible energy 4 conservation policy for building systems. 5 (b) Purpose.--The purpose of this act is to grant to the 6 Commonwealth of Pennsylvania and direct it to exercise specific 7 authority in building construction to assure that such 8 construction is performed using materials and techniques that 9 will provide for energy conservation in the future operation and 10 maintenance of said buildings. 11 Section 103. Definitions. 12 The following words and phrases when used in this act shall 13 have, unless the context clearly indicates otherwise, the 14 meanings given to them in this section: 15 "Building." Any structure that provides facilities or 16 shelter for public assembly or for educational, business, 17 mercantile, institutional, warehouse or residential occupancy, 18 or industrial use including, but not limited to, those portions 19 of factory and industrial occupancy such as office space except 20 for: 21 (1) Buildings and structures or portions thereof whose 22 peak design rate of energy usage is less than one watt per 23 square foot or 3.4 BTU/hr per square foot of floor area for 24 all purposes. 25 (2) Structures or those portions of structures used for 26 manufacturing or processing and whose manufacturing or 27 processing procedures require the use of substantial heat 28 producing energy or cooling to create their product. 29 (3) Buildings which are neither heated nor cooled. 30 (4) Historic buildings. 19770H0552B3369 - 5 -
1 (5) Buildings owned by the Federal Government. 2 "Construction." The erection, fabrication or renovation of a 3 building. 4 "Department." The Pennsylvania Department of Labor and 5 Industry except that for all units subject to the act of May 11, 6 1972 (P.L.286, No.70), known as the "Industrialized Housing 7 Act," all units subject to the act of May 11, 1972 (P.L.281, 8 No.69), known as the "Uniform Standards Code for Mobile Homes," 9 and all buildings classified as Use Group R-3, herein, 10 department means the Pennsylvania Department of Community 11 Affairs. 12 "Design." Calculations and resultant drawings and 13 specifications which are used for the construction of a 14 building. 15 "Historic building." Any building determined by the State 16 Historic Preservation Officer to meet the criteria for listing 17 on the National Register of Historic Places but only to the 18 extent that compliance with this act would prevent preservation 19 of the historic or architectural integrity of the building. 20 "Licensed design professional." A person licensed as an 21 architect or professional engineer pursuant to the appropriate 22 licensure act. 23 "Life-cycle cost." The cost of a building including its 24 initial cost, the cost of the energy consumed over its economic 25 life and the cost of its operation and maintenance. 26 "Municipality." A city, borough, incorporated town or 27 township. 28 "Performance standards." Parameters within which designers 29 of buildings shall work. The specific practices that a designer 30 employs shall not be prescribed as long as the result is within 19770H0552B3369 - 6 -
1 the parameters established by the standards. 2 "Renovation." (a) The rehabilitation of an existing 3 building which requires more than 25% of the gross floor area or 4 volume of the entire building to be rebuilt; or 5 (b) any addition to an existing building: Provided, however, 6 That the provisions of this act shall only apply to such portion 7 of the building being renovated and not to the entire building. 8 CHAPTER 2 9 ENERGY CONSERVATION STANDARDS 10 SUBCHAPTER A <-- 11 GENERAL PROVISIONS 12 Section 201. Provisions. 13 The EXCEPT FOR USE GROUP R-3, THE following provisions <-- 14 regulate the design and construction of the exterior envelopes 15 and selection of HVAC, service water heating, electrical 16 distribution, and illumination systems and equipment required 17 for the purpose of effective use of energy and shall govern the 18 construction of all buildings, or portions thereof, as provided 19 herein. 20 THE PROVISIONS REGULATING THE CONSTRUCTION OF BUILDINGS <-- 21 CLASSIFIED AS USE GROUP R-3 ARE CONTAINED IN SUBCHAPTER J, 22 SECTION 240. 23 SUBCHAPTER A B <-- 24 PLANS AND SPECIFICATIONS 25 Section 202. Submission. 26 (a) Plans.--Plans, specifications, computations where 27 necessary, and any changes thereto together with the necessary 28 certification required by section 305 shall be submitted for all 29 buildings except those classified as Use Group R-3 to indicate 30 conformance with this chapter and other applicable chapters of 19770H0552B3369 - 7 -
1 this act, except as provided in subsections (b) and (c). 2 (b) Standard design.--Whenever a person is constructing a 3 building in accordance with plans, specifications and 4 computations which he has submitted within the previous two 5 years, such plans need not be resubmitted but such person shall 6 indicate upon the certificate required by section 305 that they 7 meet the standards currently in effect and identify the 8 previously submitted plans, specifications and computations. 9 (c) Prescriptive standards.--When the prescriptive standards 10 provided in the Energy Conservation Manual established by 11 section 303 are employed in the construction of a building only 12 such information as shall be required by the department shall be 13 submitted. THE PRESCRIPTIVE STANDARDS APPLICABLE TO USE GROUP R- <-- 14 3, BUILDINGS ARE CONTAINED IN SECTION 240. 15 Section 203. Contents. 16 The plans and specifications, where required by section 202, 17 shall show in sufficient detail all pertinent data and features 18 of the building and the equipment and systems as herein 19 governed, including but not limited to: exterior envelope 20 component materials, U values of elements, R values of 21 insulating materials, size and type of apparatus and equipment, 22 equipment and system controls and other pertinent data to 23 indicate conformance with the requirements herein. 24 SUBCHAPTER C 25 DEFINITIONS RELATING TO 26 ENERGY CONSERVATION STANDARDS 27 Section 204. Definitions relating to standards. 28 The following words and phrases when used in this chapter 29 shall have, unless the context clearly indicates otherwise, the 30 meanings given to them in this section: 19770H0552B3369 - 8 -
1 "Coefficient of beam utilization" (CBU). The ratio of the 2 luminous flux (lumens) reaching a specified area directly from a 3 floodlight or projector to the total beam luminous flux. 4 "Coefficient of performance" (COP) - cooling. The ratio of 5 the rate of net heat removal to the rate of total energy input, 6 expressed in consistent units and under designated rating 7 conditions. 8 "Coefficient of performance" (COP) - heat pump, heating. The 9 ratio of the rate of net heat output to the rate of total energy 10 input, expressed in consistent units and under designated rating 11 conditions. 12 The rate of net heat output shall be defined as the change in 13 the total heat contents of the air entering and leaving the 14 equipment not including supplementary heat. 15 Total energy input shall be determined by combining the 16 energy inputs to all elements, except supplementary heaters, of 17 the heat pump, including, but not limited to, compressors, 18 pumps, supply air fans, return air fans, outdoor air fans, 19 cooling tower fans and the heating, ventilating and air 20 conditioning system equipment control circuit. 21 "Coefficient of utilization" (CU). The ratio of the luminous 22 flux (lumens) from a luminaire received on the work plane to the 23 lumens emitted by the luminaire's lamps alone. 24 "Color rendition." General expression for the effect of a 25 light source on the color. Appearance of objects in conscious or 26 subconscious comparison with their color appearance under a 27 reference light source. 28 "Degree day, heating." A unit, based upon temperature 29 difference and time, used in estimating fuel consumption and 30 specifying nominal heating load of a building in winter. For any 19770H0552B3369 - 9 -
1 one day, when the mean temperature is less than 65 F., there 2 exist as many degree days as there are Fahrenheit degrees 3 difference in temperature between the mean temperature for the 4 day and 65 F. 5 "Energy efficiency ratio" (EER). The ratio of net cooling 6 capacity in Btuh to total rate of electric input in watts under 7 designated operating conditions. 8 "Equivalent sphere illumination" (ESI). The level of sphere 9 illumination which would produce task visibility equivalent to 10 that produced by a specific lighting environment. 11 "Exterior envelope." The elements of a building which 12 enclose conditioned spaces through which thermal energy may be 13 transferred to or from the exterior. 14 "Floodlighting." A lighting system designated to light an 15 area using projector type luminaires usually capable of being 16 pointed in any direction. 17 "Floor area, gross." Gross floor area shall be the floor 18 area within the perimeter of the outside walls of the building 19 under consideration, without deduction for hallways, stairs, 20 closets, thickness of walls, columns or other features. 21 "Illumination." The density of the luminous flux incident on 22 a surface. It is the quotient of the luminous flux by the area 23 of the surface when the latter is uniformly illuminated. 24 "Light loss factor" (LLF). A factor used in calculating the 25 level of illumination after a given period of time and under 26 given conditions. It takes into account temperature and voltage 27 variations, dirt accumulation on luminaire and room surfaces, 28 lamp depreciation, maintenance procedures and atmosphere 29 conditions. 30 "Luminaire." A complete lighting unit consisting of a lamp 19770H0552B3369 - 10 -
1 or lamps together with the parts designed to distribute the 2 light, to position and protect the lamps and to connect the 3 lamps to the power supply. 4 "Packaged terminal air conditioner." A factory selected 5 combination of heating and cooling components, assemblies or 6 sections, intended to serve a room or zone. 7 "Power." In connection with machines, power is the time rate 8 of doing work. In connection with the transmission of energy of 9 all types, power refers to the rate at which energy is 10 transmitted; in customary units, it is measured in watts (W) or 11 British thermal units per hour (Btuh) and in SI units is 12 measured in watts (W). 13 "Reflectance." The ratio of the light reflected by a surface 14 to the light falling upon it. 15 "Reheat." The application of sensible heat to supply air 16 that has been previously cooled below the temperature of the 17 conditioned space by either mechanical refrigeration or the 18 introduction of outdoor air to provide cooling. 19 "Residential buildings." All buildings and structures or 20 parts thereof shall be classified in the residential (R) use 21 group in which families or households live, or in which sleeping 22 accommodations are provided for individuals with or without 23 dining facilities, excluding those that are classified as 24 institutional buildings. Residential buildings shall be 25 classified as follows: 26 (1) Use group R-1 structures. This use group shall include 27 all hotel and motel buildings, lodging houses, boarding houses 28 and dormitory buildings arranged for the shelter and sleeping 29 accommodation of more than 20 individuals. 30 (2) Use group R-2 structures. This use group shall include 19770H0552B3369 - 11 -
1 all multiple-family dwellings having more than two dwelling 2 units; and shall also include all dormitories, boarding and 3 lodging houses arranged for shelter and sleeping accommodation 4 by more than five and not more than 20 individuals. 5 (3) Use group R-3 structures. This use group shall include 6 all buildings arranged for the use of one or two family dwelling 7 units including not more than five lodgers or boarders per 8 family. 9 "Resistance, thermal" (R). A measure of the ability to 10 retard the flow of heat. The R value is the reciprocal of a heat 11 transfer coefficient, as expressed by U. (R = 1/U). 12 "Thermal transmittance" (U). Overall coefficient of heat 13 transmission or thermal transmittance (air to air) expressed in 14 units of BTU per hour per square foot per degree F. It is the 15 time rate of heat flow. The U value applies to combinations of 16 different materials used in series along the heat flow path and 17 also to single materials that comprise a building section and 18 include cavity air spaces and surface air films on both sides. 19 "Thermal transmittance" (Uo). Overall (average) heat 20 transmission or thermal transmittance of a gross area of the 21 exterior building envelope, expressed in units of BTU per hour 22 per square foot per degree F. 23 The Uo value applies to the combined effect of the time rate 24 of heat flows through the various parallel paths, such as 25 windows, doors and opaque construction areas, comprising the 26 gross area of one or more exterior building components, such as 27 walls, floor or roof/ceiling. 28 "Thermostat." An instrument which measures changes in 29 temperature and controls devices for maintaining a desired 30 temperature. 19770H0552B3369 - 12 -
1 "Veiling reflections." Regular reflections superimposed upon 2 diffuse reflections from an object that partially or totally 3 obscure the details to be seen by reducing the contrast. This 4 sometimes is called "reflected glare." 5 "Work plane." The plane at which work usually is done and at 6 which the illumination is specified and measured. Unless 7 otherwise indicated, this is assumed to be a horizontal plane 30 8 in. (0.76 m) above the floor. 9 "Zone." A space or group of spaces within a building with 10 heating or cooling requirements sufficiently similar so that 11 comfort conditions can be maintained throughout by a single 12 controlling device. 13 SUBCHAPTER D 14 BUILDING ENVELOPE 15 Section 205. General provisions. 16 (a) Purpose of subchapter.--The intent of this subchapter is 17 to provide minimum requirements for exterior envelope 18 construction in the interest of energy conservation. 19 In addition to the criteria set forth in this subchapter the 20 proposed design may take into consideration the thermal mass of 21 the building in considering energy conservation. 22 (b) Thermal performance.--All buildings and structures that 23 are heated or mechanically cooled shall be constructed so as to 24 provide the required thermal performance of the various 25 components. 26 The required thermal transmittance value (Uo) of any one 27 component, such as roof/ceiling, wall or floor may be increased 28 and the Uo value for other components decreased provided that 29 the overall heat gain or loss for the entire building envelope 30 does not exceed the total resulting from conformance to the 19770H0552B3369 - 13 -
1 required Uo values. 2 (c) Different requirements.--A building that is designed to 3 be both heated and cooled shall meet the more stringent of the 4 heating or cooling requirements of the exterior envelope as 5 provided in this subchapter when requirements differ. 6 (d) Exterior walls.--For the purpose of this subchapter the 7 gross area of exterior walls consists of all opaque wall areas, 8 including foundation walls above grade, peripheral edges of 9 floors, window areas including sash, and door areas, where such 10 surfaces are exposed to outdoor air and enclose a heated or 11 mechanically cooled space. 12 (e) Roof assembly.--For the purpose of this subchapter a 13 roof assembly shall be considered as all components of the 14 roof/ceiling envelope through which heat flows, thereby creating 15 a building transmission heat loss or gain, where such assembly 16 is exposed to outdoor air and encloses a heated or mechanically 17 cooled space. 18 The gross area of a roof assembly consists of the total 19 interior surface of such assembly, including skylights, exposed 20 to the heated or mechanically cooled space. 21 Where air ceiling plenums are employed, the roof or ceiling 22 assembly shall: 23 (1) For thermal transmittance purposes not include the 24 ceiling proper nor the plenum space as part of the assembly. 25 (2) For gross area purposes be based upon the interior 26 face of the upper plenum surface. 27 Section 206. Criteria for residential buildings. 28 (a) Applicability.--The requirements herein shall apply to 29 all buildings and structures or portions thereof of use groups 30 R-1, R-2 and R-3 that are heated or mechanically cooled when not 19770H0552B3369 - 14 -
1 more than 3 stories or 40 feet in height. 2 (b) Walls.--The gross area of exterior walls above grade, 3 including foundation walls, shall have a combined thermal 4 transmittance value (Uo) not exceeding those specified in Table 5 1. 6 Table 1 7 Maximum Allowable "Uo" Values for 8 Gross Exterior Wall Assemblies 9 Detached All other 10 Annual heating degree days* one & two family residential 11 4000 0.25 0.31 12 5000 0.23 0.29 13 6000 0.22 0.27 14 7000 0.20 0.26 15 *As specified in Chapter 43 ASHRAE Handbook-Systems. 16 (c) Roof/ceiling.--The roof/ceiling assemblies shall have a 17 combined thermal transmittance value (Uo) not to exceed 0.05 18 except that roof/ceiling assemblies in which the finished 19 interior surface is essentially the underside of the roof deck, 20 such as a wooden cathedral ceiling, may have a "Uo" value not to 21 exceed 0.08. These values presume no significant thermal 22 transmission through framing members, skylights or other 23 interruptions in the roof envelope. If such interruptions occur, 24 calculations must be made showing conformance to the required 25 "Uo" values. 26 (d) Floors over unheated spaces.--The floor of a heated or 27 mechanically cooled space located over an unheated space shall 28 have a combined thermal transmittance value (Uo) not to exceed 29 0.08. 30 (e) Slab-on grade floors.-- 19770H0552B3369 - 15 -
1 (1) For slab-on grade floors, the perimeter of the floor 2 shall be insulated with a material having a thermal 3 resistance value (R) not less than those specified in Table 4 2. 5 Table 2 6 Minimum Allowable "R" Values of Perimeter 7 Insulation for Slab-On Grade Floors 8 Annual heating degree days Heated slab Unheated slab 9 4000* 5.5 3.5 10 5000 6.3 4.2 11 6000 7.0 4.9 12 7000 7.8 5.5 13 *Table values may be interpolated. 14 (2) The insulation shall extend downward from the top of 15 the slab for a minimum distance of 24 inches or downward to 16 the bottom of the slab then horizontally beneath the slab for 17 a minimum total distance of 24 inches. 18 Section 207. Other buildings. 19 (a) Coverage.--The heating and cooling requirements herein 20 shall govern all buildings and structures or portions thereof 21 other than defined by section 206. 22 (b) Heating criteria for walls.--All buildings and 23 structures that are heated shall have a combined thermal 24 transmittance value (Uo) for the gross area of exterior walls 25 not exceeding those specified in Table 3. 26 Table 3 27 Maximum Allowable "Uo" Values 28 for Gross Exterior Wall Assemblies 29 3 stories or More than 30 Annual heating degree days 40 ft. or less 3 stories or 19770H0552B3369 - 16 -
1 40 ft. 2 4000 0.31 0.38 3 5000 0.29 0.36 4 6000 0.27 0.33 5 7000 0.26 0.31 6 (c) Heating criteria for roof/ceiling.--All buildings and 7 structures that are heated shall have combined thermal 8 transmittance value (Uo) for roof/ceiling assemblies not 9 exceeding those specified in Table 4. 10 Table 4 11 Maximum Allowable "Uo" Values 12 for Roof/Ceiling Assemblies 13 Annual heating degree days Maximum Uo 14 4000* 0.092 15 5000 0.084 16 6000 0.076 17 7000 0.068 18 *Table values may be interpolated. 19 (d) Heating criteria for floors over unheated spaces.--The 20 floor of a heated space located over an unheated space shall 21 have a thermal transmittance value (Uo) not exceeding 0.08. 22 (e) Heating criteria for slab-on grade floors.--For slab-on 23 grade floors, the perimeter of the floor shall be insulated with 24 a material having a thermal resistance value (R) not less than 25 those specified in Table 5. 26 The insulation shall extend downward from the top of the slab 27 for a minimum distance of 24 inches or downward to the bottom of 28 the slab then horizontally beneath the slab for a minimum total 29 distance of 24 inches. 30 Table 5 19770H0552B3369 - 17 -
1 Minimum Allowable "R" Values of Perimeter
2 Insulation for Slab-On Grade Floors
3 Annual heating degree days Heated slab Unheated slab
4 4000* 5.5 3.5
5 5000 6.3 4.2
6 6000 7.0 4.9
7 7000 7.8 5.5
8 *Table values may be interpolated.
9 (f) Cooling criteria for walls.--All buildings and
10 structures that are mechanically cooled shall have an overall
11 thermal transfer value for the gross area of exterior walls not
12 exceeding 33.5 BTU's per hour per square foot based on the
13 following equation:
14 OTTV = (Uw x Aw X TDEQ) + (Af x Sf x Sc) + (Uf x Af x Delta T)
15 Ao
16 OTTV = Overall thermal transfer value where:
17 Uw = The thermal transmittance of all elements of the opaque
18 wall area Btu/h. ft2.F (W/m2K)
19 Aw = Opaque wall area, ft2 (m2)
20 Uf = The thermal transmittance of the fenestration area
21 Btu/h. ft2.F (W/m2K)
22 Af = Fenestration area, ft2 (m2)
23 TDEQ = Value given in the following table,F, (c):
24 TABLE FOR TEMPERATURE DIFFERENCE
25 Wall Construction-mass per unit area TDEQ
26 LB/FT2 Kg/m2 F C
27 0-25 0-125 44 24.5
28 26-40 126-195 37 21.0
29 41-70 196-345 30 17.0
30 71 and above 346 and above 23 13.0
19770H0552B3369 - 18 -
1 Weight of wall construction shall be determined from the 2 1972 ASHRAE Handbook of Fundamentals, Chapter 22. 3 Sc = Shading coefficient of the fenestration 4 Delta T = Temperature difference between exterior and interior 5 design conditions, F, for which the following 6 temperatures shall apply: 7 Indoor Outdoor 8 F C 9 Winter 72 22.0 97 1/2%* 10 Summer 78 25.5 2 1/2%* 11 * Values from 1972 ASHRAE Handbook of 12 Fundamentals, Chapter 33. 13 SF = Solar factor value given Btu/h.ft2 (W/m2). 14 (use 127 Btu/h.ft2) 15 AO = Gross area of exterior walls, ft2 (m2). The gross 16 area of exterior walls consists of all opaque wall 17 areas (including foundation walls, between floor span- 18 drels, peripheral edges of floors, etc.), window 19 areas (including sash), and door areas, where such 20 surfaces are exposed to outdoor air and enclose a 21 heated and/or mechanically cooled space (including 22 intersticial areas between two such spaces). 23 Note: Where more than one type of wall and/or fenestration 24 is used, the respective term or terms shall be expanded 25 into sub-elements, as: 26 (Uw x Aw x TDEQ) + (Uw2 x Aw2 x TDEQ2), etc. 27 (g) Cooling criteria for roof/ceilings.--All buildings and 28 structures that are mechanically cooled shall have a combined 29 thermal transmittance value (Uo) for roof/ceiling assemblies the 30 same as specified in Table 4 for heating. 19770H0552B3369 - 19 -
1 Section 208. Air leakage. 2 (a) Application.--The requirements of this section shall 3 apply to all buildings and structures and apply only to those 4 locations separating outdoor ambient conditions from interior 5 spaces that are heated or mechanically cooled and are not 6 applicable to separation of interior spaces from each other. 7 (b) Standard.--Compliance with the criteria for air leakage 8 shall be determined by ASTM E-283, Standard Method of Test for 9 Rate of Air Leakage through Exterior Windows, Curtain Walls and 10 Doors, at a pressure differential of 1.567 lb/ft2 which is 11 equivalent to the effect of a 25 m.p.h. wind. 12 (c) Acceptance criteria.--The following criteria shall 13 represent the maximum allowable air leakage: 14 (1) The air infiltration rate for windows shall not 15 exceed 0.5 cfm per foot of sash crack. 16 (2) The air infiltration rate for sliding glass doors in 17 residential buildings shall not exceed 0.5 cfm per square 18 foot of door area. 19 (3) The air infiltration rate for swinging doors in 20 residential buildings shall not exceed 1.25 cfm per square 21 foot of door area. 22 (4) The air infiltration rate for swinging, revolving or 23 sliding doors in other than residential buildings shall not 24 exceed 11 cfm per lineal foot of door crack. 25 (d) Caulking and sealants.--Exterior joints around windows 26 and door frames, between wall cavities and window or door 27 frames, between wall and foundation, between wall and roof, 28 between wall panels, at penetrations or utility services through 29 walls, floors and roofs, and all other openings in the exterior 30 envelope shall be caulked, gasketed, weatherstripped, or 19770H0552B3369 - 20 -
1 otherwise sealed. 2 SUBCHAPTER E 3 WARM AIR HEATING, VENTILATING AND AIR CONDITIONING 4 SYSTEMS AND EQUIPMENT 5 Section 209. General provisions. 6 This subchapter applies to air duct systems employing 7 mechanical means for the movement of air used for warm air 8 heating, ventilating, air conditioning systems, exhaust systems 9 and combination heating and air conditioning systems, except 10 that this subchapter shall not apply to systems for the removal 11 of flammable vapors or residues or to systems for conveying 12 dust, stock or refuse by means of air currents. Heating, 13 ventilating and air conditioning systems of all buildings and 14 structures or portions thereof shall be designed and installed 15 for efficient use of energy as herein provided. For special 16 applications such as hospitals, laboratories, thermally 17 sensitive equipment, computer rooms, and manufacturing 18 processes, the design concepts and parameters shall conform to 19 the requirements of the application at minimum energy levels. 20 Section 210. Design requirements. 21 In determining design conditions for calculations under this 22 section the following design temperatures shall apply: 23 (1) Outdoor design temperature shall be selected for 24 listed locations in Chapter 33 of the ASHRAE Handbook of 25 Fundamentals, from columns of 97 1/2% values for heating and 26 2 1/2% values for cooling. 27 (2) Indoor design temperature shall be 70 degrees F. for 28 heating and 78 degrees F. for cooling. 29 (3) Indoor design relative humidity for heating shall 30 not exceed 30%. For cooling, the actual design relative 19770H0552B3369 - 21 -
1 humidity within the comfort envelope as defined in ASHRAE 2 Standard 55-74 "Thermal Environmental Conditions for Human 3 Occupancy" shall be selected for the minimum total heating, 4 ventilating, and air conditioning system energy use. 5 Section 211. Cooling with outdoor air. 6 (a) Fan system design.--Each fan system shall be designed to 7 use up to and including 100% of the fan system capacity for 8 cooling with outdoor air automatically whenever its use will 9 result in lower usage of energy than would be required under its 10 normal operation. 11 (b) Exceptions.--Cooling with outdoor air is not required 12 under any one or more of the following conditions: 13 (1) Fan system capacity less than 5,000 Cfm or 134,000 14 Btu/Hr total cooling capacity. 15 (2) The quality of the outdoor air is so poor as to 16 require extensive treatment of the air. 17 (3) The need for humidification or dehumidification 18 requires the use of more energy than is conserved by outdoor 19 air cooling. 20 (4) The use of outdoor air cooling may affect the 21 operation of other systems (such as return or exhaust air 22 fans or supermarket refrigeration) so as to increase the 23 overall energy consumption of the building. 24 (5) Internal/external zone heat recovery or other energy 25 recovery is used. 26 (6) When all space cooling is accomplished by a 27 circulating liquid which transfers space heat directly or 28 indirectly to a heat rejection device such as a cooling tower 29 without the use of a refrigeration system. 30 Section 212. Mechanical ventilation. 19770H0552B3369 - 22 -
1 Each mechanical ventilation system shall be equipped with a 2 readily accessible means for either shut-off or volume reduction 3 and shut-off when ventilation is not required. 4 Section 213. Simultaneous heating and cooling. 5 Systems that employ both heating and cooling simultaneously 6 in order to achieve comfort conditions within a space shall be 7 limited to those situations where more efficient methods of 8 heating and air conditioning cannot be effectively utilized to 9 meet system objectives. Simultaneous heating and cooling by 10 reheating or recooling supply air or by concurrent operation or 11 independent heating and cooling systems serving a common zone 12 shall be restricted as specified herein. 13 Section 214. Recovered energy. 14 Recovered energy, provided the new energy expended in the 15 recovery process is less than the amount recovered, may be used 16 for control of temperature and humidity. New energy is defined 17 as energy, other than recovered, utilized for the purpose of 18 heating or cooling. 19 Section 215. New energy. 20 (a) Prevention of excess humidity.--New energy may be used, 21 when necessary, to prevent relative humidity from rising above 22 60% for comfort control or to prevent condensation on terminal 23 units or outlets. 24 (b) Control of temperature.--New energy may be used for 25 control of temperature if minimized as specified in sections 216 26 through 220. 27 Section 216. Reheat systems. 28 Systems employing reheat and serving multiple zones, other 29 than those employing variable air volume for temperature 30 control, shall be provided with control that will automatically 19770H0552B3369 - 23 -
1 reset the system cold air supply to the highest temperature 2 level that will satisfy the zone requiring the coolest air. 3 Single zone reheat systems shall be controlled to sequence 4 reheat and cooling. 5 Section 217. Dual duct and multizone systems. 6 These systems shall be provided with control that will 7 automatically reset the cold deck air supply to the highest 8 temperature that will satisfy the zone requiring the coolest air 9 and the hot deck air supply to the lowest temperature that will 10 satisfy the zone requiring the warmest air. 11 Section 218. Recooling systems. 12 Systems in which heated air is recooled directly or 13 indirectly, to maintain space temperature, shall be provided 14 with control that will automatically reset the temperature to 15 which the supply air is heated to the lowest level that will 16 satisfy the zone requiring the warmest air. 17 Section 219. Multiple zones. 18 For systems with multiple zones, one or more zones may be 19 chosen to represent a number of zones with similar heating or 20 cooling characteristics. A multiple zone heating, ventilating 21 and air conditioning system that employs reheating or recooling 22 for control of not more than 5,000 Cfm or 20% of the total 23 supply air of the system, whichever is less, shall be exempt 24 from the supply air temperature reset requirements of sections 25 216 through 218. 26 Section 220. Concurrent operation. 27 Concurrent operation of independent heating and cooling 28 systems serving common spaces, and requiring the use of new 29 energy for heating or cooling shall be minimized by one or both 30 of the following: 19770H0552B3369 - 24 -
1 (1) By providing sequential temperature control of both 2 heating and cooling capacity in each zone. 3 (2) By limiting the heating energy input, through 4 automatic reset control of the heating medium temperature (or 5 energy input rate), to only that necessary to offset heat 6 loss due to transmission and infiltration and, where 7 applicable, to heat the ventilation air supply to the space. 8 Section 221. Equipment performance requirements. 9 (a) Application.--The requirements of this section apply to 10 equipment and component performance for heating, ventilating and 11 air conditioning systems. Where equipment efficiency levels are 12 specified, data furnished by the equipment supplier or certified 13 under a nationally recognized certification program or rating 14 procedure shall be used to satisfy these requirements. 15 (b) Systems equipment - electrical.--Heating ventilating and 16 air conditioning systems equipment whose energy input in the 17 cooling mode is entirely electric shall show a coefficient of 18 performance (COP) and energy efficiency ratio (EER) not less 19 than the values specified in Table 6. These requirements apply 20 to, but are not limited to, unitary cooling equipment (air and 21 water source); packaged air conditioners; and room air 22 conditioners. These requirements do not apply to equipment used 23 in areas having open refrigerated food display cases. For 24 determining coefficient of performance (COP), the rate of net 25 heat removal shall be defined as the change in the total heat 26 contents of the air entering and leaving the equipment (without 27 reheat). Total energy input shall be determined by combining the 28 energy inputs to all elements of the equipment, including but 29 not limited to, compressors, pumps, supply-air fans, cooling 30 tower fans and the system equipment control circuit. 19770H0552B3369 - 25 -
1 Table 6 2 Minimum EER and COP for Electric Heating, Ventilating 3 and Air Conditioning System Equipment 4 Standard rating capacity EER COP 5 Under 65,000 Btu/hr (19,050 watts) 6.1 1.8 6 65,000 Btu/hr (19,050 watts) and over 6.8 2.0 7 (c) Other system equipment.--Heat operated cooling equipment 8 shall show a coefficient of performance (COP) in the cooling 9 mode not less than the values specified in Table 7. These 10 requirements apply to, but are not limited to, absorption, 11 engine-driven and turbine-driven equipment. The coefficient of 12 performance (COP) is determined excluding the electrical 13 auxiliary inputs. 14 Table 7 15 Minimum COP for Heating, Ventilating and Air Conditioning 16 System Heat Operated Cooling Equipment 17 Heat source Minimum COP 18 Direct fired (gas, oil) 0.40 19 Indirect fired (steam, hot water) 0.65 20 (d) System components.--Heating, ventilating and air 21 conditioning system components whose energy input in the cooling 22 mode is entirely electric shall show a coefficient of 23 performance (COP) and energy efficiency ratio (EER) not less 24 than the values specified in Table 8. For determining 25 coefficient of performance (COP), the rate of heat removal is 26 defined as the difference in total heat contents of the water or 27 refrigerant entering or leaving the component. Total energy 28 input shall be determined by combining the energy inputs to all 29 elements and accessories of the component, including but not 30 limited to, compressors, internal circulating pumps, condenser- 19770H0552B3369 - 26 -
1 air fans, evaporative-condenser cooling heater pumps, purge, and 2 the component control circuit. 3 Table 8 4 Minimum COP for Electrically Driven Heating, Ventilating 5 and Air Conditioning System Components 6 Component Condensing means Air Water Evaporation 7 ERR COP EER COP EER COP 8 Self-contained Centrifugal 7.5 2.2 12.9 3.8 9 water chillers 10 Positive 11 displacement 7.2 2.1 10.9 3.2 12 Condenserless Positive 13 water chillers displacement 8.9 2.6 10.9 3.2 14 Compressor and 15 condenser units Positive 16 65,000 Btu/hr. displacement 7.8 2.3 11.3 3.3 11.3 3.3 17 (19,050 watts) 18 and over 19 (e) Heat pumps.--Heat pumps whose energy input is entirely 20 electric shall show a coefficient of performance (COP), heating, 21 not less than the values specified in Table 9. 22 Table 9 23 Minimum COP for Heat Pumps, Heating Mode 24 Source and outdoor temperature (degree F.) Minimum COP 25 Air source--47 DB/43 WB 2.2 26 Air source--17 DB/15 WB 1.2 27 Water source--60 entering 2.2 28 (f) Supplementary heater.--The heat pump shall be installed 29 with a control to prevent supplementary heater operation when 30 the heating load can be met by the heat pump alone. 19770H0552B3369 - 27 -
1 Supplementary heater operation is permitted during transient 2 periods, such as start-ups, following room thermostat setpoint 3 advance, and during defrost. A two-stage room thermostat, which 4 controls the supplementary heat on its second stage, shall be 5 accepted as meeting this requirement. The cut-on temperature for 6 the compression heating shall be higher than the cut-on 7 temperature for the supplementary heat, and the cut-off 8 temperature for the compression heating shall be higher than the 9 cut-off temperature for the supplementary heat. Supplementary 10 heat may be derived from any source of electric resistance 11 heating or combustion heating. 12 (g) Combustion heating equipment.--All gas and oilfired 13 comfort heating equipment shall show a minimum combustion 14 efficiency of 75% at maximum rated output. Combustion efficiency 15 shall be determined in accordance with the ASHRAE Standard 90. 16 Section 222. Duct insulation. 17 (a) Insulation.--All duct systems, or portions thereof, 18 exposed to nonconditioned spaces shall be insulated to provide a 19 thermal resistance, excluding film resistance, of 20 ti - to 21 R = --------(hr) (sq.ft) (F)/BTU 22 15 23 where ti-to is the design temperature differential (absolute 24 value) between the air in the duct and the surrounding air with 25 the following exceptions. Duct insulation, except when needed to 26 prevent condensation, is not required in any of the following 27 cases: 28 (1) Where ti-to is 25 degrees F. or less. 29 (2) When the heat gain or loss of the ducts, without 30 insulation, will not increase the energy requirements of the 19770H0552B3369 - 28 -
1 building. 2 (3) Exhaust air ducts. 3 (4) Supply or return air ducts installed in crawl spaces 4 with insulated walls, basements or cellars in one and two- 5 family dwellings. 6 (b) Vapor barriers.--Where required to prevent condensation, 7 insulation with vapor barriers shall be installed in addition to 8 insulation required above. 9 Section 223. System controls. 10 (a) Application.--All heating, ventilating and air 11 conditioning systems shall be provided controls as specified 12 herein. 13 (b) Temperature.--Each heating, ventilating and air 14 conditioning system shall be provided with at least one 15 thermostat for the regulation of temperature. Each thermostat 16 shall be capable of being set from 55 degrees F. to 75 degrees 17 F. where used to control heating only and from 70 degrees F. to 18 85 degrees F. where used to control cooling only. Where used to 19 control both heating and cooling it shall be capable of being 20 set from 55 degrees F. to 85 degrees F. and shall be capable of 21 operating the system heating and cooling in sequence. It shall 22 be adjustable to provide a temperature range of up to 10 degrees 23 F. between full heating and full cooling, except as allowed in 24 section 220. 25 (c) Humidity.--If a heating, ventilating and air 26 conditioning system is equipped with a means for adding moisture 27 to maintain specific selected relative humidities in spaces or 28 zones, a humidistat shall be provided. This device shall be 29 capable of being set to prevent new energy from being used to 30 produce space relative humidity above 30% R.H. Where a 19770H0552B3369 - 29 -
1 humidistat is used in a heating, ventilating and air 2 conditioning system for controlling moisture removal to maintain 3 specific selected relative humidities in spaces or zones, it 4 shall be capable of being set to prevent new energy from being 5 used to produce a space relative humidity below 60%. 6 (d) Temperature zoning.-- 7 (1) In all buildings and structures of use group R-3, at 8 least one thermostat for regulation of space temperature 9 shall be provided for each separate heating, ventilating and 10 air conditioning system. In addition, a readily accessible 11 manual or automatic means shall be provided to partially 12 restrict or shut-off the heating or cooling input to each 13 zone or floor, excluding unheated or uncooled basements and 14 garages. 15 (2) In all buildings and structures of use group R-2, 16 each individual dwelling unit shall be considered separately 17 and shall meet the requirements for one and two-family 18 dwellings above. 19 (3) In all buildings and structures other than use group 20 R-3 and in spaces other than dwelling units in use group R-2, 21 at least one thermostat for regulation of space temperature 22 shall be provided for each separate heating, ventilating and 23 air conditioning system and for each floor of the building. 24 (e) Set-back and shut-off.-- 25 (1) In all buildings and structures, or portions thereof 26 of use group R-3, the thermostat, or an alternate means such 27 as a switch or a clock, shall provide a readily accessible, 28 manual or automatic means for reducing the energy required 29 for heating and cooling during periods of nonuse or reduced 30 need. 19770H0552B3369 - 30 -
1 (2) In all other buildings and structures, or portions 2 thereof each heating, ventilating and air conditioning system 3 shall be equipped with a readily accessible means of reducing 4 the energy used for heating, ventilating and air conditioning 5 during periods of nonuse or alternate uses of the building 6 spaces or zones served by the system, such as with manually 7 adjustable automatic timing devices, manual devices for use 8 by operating personnel, or automatic control systems. 9 (3) Lowering thermostat set points to reduce energy 10 consumption of heating systems shall not cause energy to be 11 expended to reach the reduced setting. 12 Section 224. Steam and hot water heating piping. 13 (a) Piping insulation.--All piping serving as part of a 14 heating or cooling system installed to serve buildings and 15 within buildings shall be thermally insulated as shown in Table 16 10. 17 Table 10 18 Minimum Pipe Insulation 19 Insulation thickness in inches 20 Fluid for pipe sizes 21 Piping temperature 22 system range, Runouts 1" and 1 1/4- 2 1/2- 5& 8" and 23 types F. up to 2" less 2 4 6 larger 24 Heating systems 25 Steam & 26 hot water 27 High pressure/ 28 temp 306-450 1 1/2 1 1/2 2 2 1/2 3 1/2 3 1/2 29 Med. pressure/ 30 temp 251-305 1 1/2 1 1/2 2 2 1/2 3 3 19770H0552B3369 - 31 -
1 Low pressure/ 2 temp 201-250 1 1 1 1/2 1 1/2 2 2 3 Low tem- 4 perature 120-200 1/2 3/4 1 1 1 1 1/2 5 Steam con- 6 densate Any 1 1 1 1 1/2 1 1/2 2 7 (for feed 8 water) 9 Cooling systems 10 Chilled 11 water, 40-55 1/2 1/2 3/4 1 1 1 12 Refrigerant, 13 or brine Below 40 1 1 1 1/2 1 1/2 1 1/2 1 1/2 14 Insulation thicknesses are based on insulation having thermal 15 resistances in the range of 4.0 to 4.6 per inch of thickness on 16 a flat surface at a mean temperature of 75 degrees F. Minimum 17 insulation thickness shall be increased for materials having R 18 values less than 4.0 or may be reduced for materials having R 19 values greater than 4.6 per inch of thickness as follows: 20 (b) High thermal resistance.--For materials with thermal 21 resistance greater than R=4.6, the minimum insulation thickness 22 may be reduced as follows: 23 4.6 x Table 10 Thickness = New Minimum Thickness 24 Actual R 25 (c) Low thermal resistance.--For materials with thermal 26 resistance less than R=4.0 the minimum insulation thickness 27 shall be increased as follows: 28 4.0 x Table 10 Thickness = New Minimum Thickness 29 Actual R 30 Piping insulation, except when needed to prevent condensation, 19770H0552B3369 - 32 -
1 is not required in any of the following cases: 2 (1) Piping installed within heating, ventilating and air 3 conditioning equipment. 4 (2) Piping at temperatures between 55 degrees F. and 120 5 degrees F. 6 (3) When the heat loss or heat gain of the piping, 7 without insulation, does not increase the energy requirements 8 of the building. 9 (4) Piping installed in basements or cellars in one and 10 two-family dwellings. 11 (d) Vapor barriers.--Where required to prevent condensation, 12 insulation with vapor barriers shall be installed in addition to 13 insulation required above. 14 SUBCHAPTER F 15 PLUMBING SYSTEMS 16 Section 225. Purpose. 17 This subchapter sets forth provisions for design and 18 equipment selection for energy conservation in service water 19 heating systems. 20 Section 226. Fixtures. 21 (a) Lavatories.--Lavatories in restrooms of public 22 facilities shall be equipped with self-closing outlet devices 23 which limit the flow of hot water to a maximum of 0.5 Gpm, 24 devices which limit the outlet temperature to a maximum of 110 25 degrees F. and selfclosing valves which limit the quantity of 26 hot water to a maximum of 0.25 gallons. 27 (b) Showers.--Showers used for other than safety reasons 28 shall be equipped with flow control devices to limit total flow 29 to a maximum of 3 Gpm per shower head. 30 Section 227. Insulation. 19770H0552B3369 - 33 -
1 (a) Piping insulation.--Piping in required return 2 circulation systems shall be insulated so that heat loss is 3 limited to a maximum of 25 Btuh per square foot of external pipe 4 surface for above ground piping and a maximum of 35 Btuh per 5 square foot of external pipe surface for underground piping. 6 Maximum heat loss shall be determined at a temperature 7 differential equal to the maximum water temperature minus a 8 design ambient temperature no higher than 65 degrees F. except 9 that conformance with table 10 for "low temperature piping 10 system" shall be deemed as complying with this section. 11 (b) Tanks.--Unfired hot water storage tanks shall be 12 insulated so that heat loss is limited to a maximum of 15 Btuh 13 per square foot of external tank surface area. For purposes of 14 determining this heat loss, the design ambient temperature shall 15 be no higher than 65 degrees F. 16 Section 228. Equipment. 17 (a) Pump operation.--Circulating hot water systems shall be 18 arranged so that the circulating pump can be conveniently turned 19 off either automatically or manually when the hot water system 20 is not in operation. 21 (b) Electric water heaters.--All automatic electric storage 22 water heaters shall have a stand-by loss not exceeding 4 watts 23 per square foot of tank surface area. The method of test of 24 stand-by loss shall be as described in section 4.3.1 of ANSI 25 C72.1 Household Automatic Electrical Storage-Type Water Heaters. 26 (c) Gas and oil-fired water heaters.--All gas and oil-fired 27 automatic storage heaters shall have a recovery efficiency, ER, 28 not less than 75% and a stand-by loss percentage S, not 29 exceeding S=2.3+67/V where V=rated volume in gallons. The method 30 of test of ER and S shall be as described in section 2.7 of ANSI 19770H0552B3369 - 34 -
1 Z21.10.3 Circulating Tank, Instantaneous and Large Automatic 2 Storage Type Water Heaters, Approval Requirements for Gas Water 3 Heaters. 4 Section 229. Controls. 5 (a) Temperature controls.--All hot water supply systems 6 shall be equipped with automatic temperature controls capable of 7 adjustments from the lowest to the highest acceptable 8 temperature settings for the intended use. 9 (b) Shut down.--A separate switch shall be provided to 10 terminate the energy supplied to electric hot water supply 11 systems. A separate valve shall be provided to turn off the 12 energy supplied to the main burner of all other types of hot 13 water supply systems. 14 SUBCHAPTER G 15 ELECTRICAL SYSTEMS 16 Section 230. System requirements. 17 (a) Power factor.--The power factor of the overall 18 electrical distribution system in a building shall be not less 19 than 90% under rated design installed load of the building, 20 either by utilization equipment design or by the use of power 21 factor corrective devices. The power factor corrective devices 22 may be installed on individual equipment, rated greater than 23 1,000 watts and switched therewith, regionally grouped, located 24 at the service equipment or power factor correction achieved by 25 other equivalent means. The choice among these corrective 26 methods should be made based upon an engineering evaluation of 27 each distribution system. 28 (b) Service voltage.--Where a choice of service voltage is 29 available, the voltage resulting in the least energy loss shall 30 be used. 19770H0552B3369 - 35 -
1 (c) Voltage drop.--In any building, the maximum total 2 voltage drop shall not exceed 3% in branch circuits or feeders, 3 for a total of 5% to the farthest outlet based on steady state 4 design load conditions. 5 (d) Lighting switching.--Switching shall be provided for 6 each lighting circuit, or for portions of each circuit, so that 7 the partial lighting required for custodial or for effective 8 complementary use with natural lighting may be operated 9 selectively. 10 (e) Separate metering.--In all multi-family dwellings 11 provisions shall be made to determine the electrical energy 12 consumed by each tenant. 13 SUBCHAPTER H 14 LIGHTING 15 Section 231. Light power budget. 16 A lighting power budget is the upper limit of the power to be 17 available to provide the lighting needs in accordance with a 18 given set of criteria and given calculation procedure. 19 Section 232. Calculation methods. 20 The criteria specified below shall be utilized for 21 computation of the lighting power budget. All calculations shall 22 be in accordance with accepted engineering practice. When 23 insufficient information is known about the specific use of the 24 building space (e.g., number of occupants, space function, 25 location of partitions), the budget shall be based on the 26 apparent intended use of the building space. 27 Section 233. Building interiors. 28 (a) Procedure.--The allowable electric power for lighting 29 shall be established by using the criteria and the calculation 30 procedures specified in section 236. The value shall be based on 19770H0552B3369 - 36 -
1 the use for which the space within the building is intended and 2 on efficient energy utilization. 3 (b) Illumination level criteria.--For the purpose of 4 establishing a budget, levels of illumination shall be those 5 listed in fig. 9-80 of the IES Lighting Handbook, and those 6 levels shall be used as follows: 7 (1) For task lighting, the levels of illumination listed 8 are for specific tasks. These levels are for the task areas 9 defined in the IES Lighting Handbook or, where not defined, 10 at all usable portions of task surfaces. In some cases, the 11 levels of illumination are listed for locations (e.g., 12 auditoriums). These levels are to be considered as average 13 levels. 14 (2) For general lighting, in areas surrounding task 15 locations, the average level of general lighting, for budget 16 purposes only, shall be one-third the level for the tasks 17 performed in the area but in no case less than 20-foot 18 candles. Where more than one task level occurs in a space, 19 the general level shall be one-third the weighted average of 20 the specific task levels. 21 (3) For noncritical lighting, in circulation and seating 22 areas, where no specific visual tasks occur, the average 23 level of illumination shall be one-third of the average 24 general lighting in the adjacent task spaces but in no case 25 less than ten-foot candles. 26 (4) For the purpose of establishing a power budget, only 27 lamp efficacies and coefficients of utilization (CU) 28 specified in Table 11, shall be assumed. 29 Section 234. Building exteriors. 30 (a) Basis on use.--In exterior spaces, the lighting power 19770H0552B3369 - 37 -
1 budget shall be based on the use of which the space is intended 2 (for task performance, safety, or security) and on efficient 3 energy utilization. 4 (b) Criteria.--The same criteria as those for interior 5 spaces apply for illumination levels and lighting systems with 6 the addition of luminaires for flood lighting. For power budget 7 purposes floodlighting shall be selected with luminaires having 8 a greater percentage of their beam lumens restricted to the area 9 to be lighted. Such luminaires are defined as those with at 10 least the minimum efficiencies listed in the IES Lighting 11 Handbook. 12 (c) Facade lighting.--Facade lighting for budget purposes 13 shall be no greater than 2% of the total interior load of the 14 building. 15 (d) Calculation procedure.--In establishing a lighting power 16 budget the following procedures shall be used: 17 (1) For overhead lighting the procedure specified in 18 section 236 shall be followed, but using reflectances as 19 found. 20 (2) For flood lighting the beam lumen method, as shown 21 in the IES Lighting Handbook and a coefficient of beam 22 utilization (CBU) of 0.75 shall be used for floodlighting 23 calculations. 24 Section 235. Exceptions to criteria. 25 (a) Interiors.--The criteria of section 233 shall not apply 26 to the following areas when calculating the load: 27 (1) Portions of residential occupancies except for 28 kitchens, bathrooms, and laundry areas and public spaces 29 including lobbies, halls, stairways, basement areas, and 30 utility rooms. 19770H0552B3369 - 38 -
1 (2) Residential type spaces similar to those stated in 2 paragraph (1) in institutions, such as hospitals, hotels, 3 funeral homes, churches, museums, etc. 4 (3) Theater auditoriums, entertainment and audiovisual 5 presentations where the lighting is an essential technical 6 element for the function performed. 7 (b) Exteriors.--The criteria of section 234 shall not apply 8 to the following lamps and luminaries; however, their use shall 9 be accounted for in the calculation of task lighting loads for 10 specific tasks. The allowable load shall be based on the 11 luminary wattage to achieve the levels of illumination as 12 covered in section 233 using a point calculation method given in 13 the IES Lighting Handbook. The excepted lamps and luminaires are 14 as follows: 15 (1) Luminaires for medical and dental purposes. 16 (2) Luminaires for highlighting applications, such as 17 sculpture exhibits, art exhibits, and individual items of 18 display merchandise. 19 (3) Luminaires for specialized lighting applications 20 (color matching, where electrical interference cannot be 21 tolerated, etc.). 22 (c) Control of reflectances.--The criteria of Table 11 shall 23 not apply in spaces where it is impractical to control 24 reflectances and where a dirty atmosphere cannot be avoided. 25 Where this condition exists, the values for reflectances and 26 light loss factors shall be those expected to be found and shall 27 be approved by the department. The calculation shall make a note 28 of this deviation. 29 Section 236. Calculation procedure. 30 (a) Illumination levels and areas.--To establish 19770H0552B3369 - 39 -
1 illumination levels and areas, the following procedure shall be 2 used: 3 (1) Determine the visual tasks that are expected to be 4 performed in each space and the number of planned work 5 locations where tasks will be performed. If assumptions are 6 made, their bases shall be indicated. 7 (2) Select the illumination level, in foot-candles for 8 those expected tasks in accordance with section 233(b)(1). 9 (3) Calculate total task areas to be illuminated to the 10 same level by multiplying the number of work locations by 50 11 square feet per work location. (Total task areas shall not 12 exceed actual total space area). If actual task area is 13 greater than 50 square feet the actual area shall be used. If 14 special task lighting or localized lighting is to be 15 employed, use the actual task areas and point calculation 16 procedures. 17 (4) Calculate the level of general lighting by 18 multiplying the task lighting level by one-third, where there 19 is only one task level, or by taking one-third of the sum of 20 the products of the task levels as provided for in paragraph 21 (2) and their areas as provided for in paragraph (3) divided 22 by the total task areas. 23 (5) Calculate the level of noncritical lighting. 24 (b) Lighting system data.--To establish lighting system 25 data, the following shall be used: 26 (1) Light source and luminaire types to use. 27 (2) Lamp lumens per watt and luminaire coefficients of 28 utilization for room and luminaire mounting height 29 dimensions. Luminaire CUs shall be selected from the IES 30 Lighting Handbook. In all cases, no luminaire shall have a CU 19770H0552B3369 - 40 -
1 for RCR = 1 of less than that given in Table 11 lamp 2 efficacies for the appropriate space. 3 (c) Allowable wattage.--To establish allowable wattage, the 4 following shall be used: 5 (1) Using data from subsection (b), the illumination 6 levels and areas determined in subsection (a), and the 7 criteria of Table 11 on Reflectance, calculate the allowable 8 wattages using the lumen method. 9 (2) Calculate the total space wattage by adding the 10 task, general and noncritical lighting loads. 11 (3) Add the wattage of luminaires allowed in section 12 235(b). 13 Table 11 14 (a) Lamp efficacies.--The following are initial lumen output 15 per watt input, including ballast losses: 16 Application Lumens 17 per Watt 18 Where moderate color rendition is appropriate 55 19 Where good color rendition is appropriate 40 20 Where high color rendition is appropriate, 21 spaces are less than 50 square feet or where 22 use of low wattage High Intensity Discharge 23 (HID) lamps under 250 W or fluorescent 24 lamps under 40 W is appropriate 25 25 (b) Luminary coefficients of utilization (CU).--Coefficients 26 of utilization (CUs) are to be for luminaires for use in the 27 types of spaces listed below, and those luminaires shall have a 28 CU of no less than that listed below (for each type space) for a 29 Room Cavity Ratio (RCR) of 1 and reflectances as in (c). 30 Space Use Minimum CU 19770H0552B3369 - 41 -
1 (at RCR = 1) 2 For spaces with tasks subjected to veiling 3 reflections where design levels of 4 illumination are listed in terms of 5 equivalent sphere illumination (ESI) and 6 where visual comfort is important. 0.55 7 For spaces without tasks, or with tasks 8 not subjected to veiling reflections, but 9 where visual comfort is important. 0.63 10 For spaces without tasks and where visual 11 comfort is not a criterion 0.70 12 (c) Other criteria; reflectances.--For interior spaces, the 13 following initial cavity and surface reflectances shall be 14 assumed: 15 Ceiling cavity reflectance 80% 16 Wall reflectance 50% 17 Floor cavity reflectance 20% 18 Light Loss Factor. A light loss factor (LLF) of 0.70 shall be 19 used. 20 SUBCHAPTER I 21 ALTERNATIVE SYSTEMS 22 Section 237. Performance alternative. 23 Alternative building systems and equipment design may be 24 approved by the department when they can be shown to have energy 25 consumption not greater than that of a similar building with 26 similar forms of energy requirements, designed in accordance 27 with the provisions of this act or when they can be shown to 28 have energy consumption not greater than that which shall be 29 established by the department with the approval of the Building 30 Energy Conservation Committee, for the purposes of this section: 19770H0552B3369 - 42 -
1 Provided, however, That for all buildings classified as Use 2 Group R-3 alternate building systems and equipment design which 3 satisfy the criteria of this section shall not require the 4 approval of the department but the use of such an alternate 5 building system or equipment design shall be indicated in the 6 warranty provided in section 306. 7 Section 238. Nondepletable sources. 8 When such alternative systems utilize solar, geothermal, wind 9 or other nondepletable energy sources for all or part of their 10 energy sources, such nondepletable energy supplied to the 11 building shall be excluded from the total energy chargeable to 12 the proposed alternative design. 13 Section 239. Documentation. 14 Proposed alternative designs, submitted to the department as 15 requests for exception to the standard design criteria, must be 16 accompanied by an energy analysis prepared in accordance with 17 the ASHRAE Standard 90-75. 18 SUBCHAPTER J <-- 19 USE GROUP R-3 PRESCRIPTIVE STANDARDS 20 SECTION 240. MINIMUM INSULATION REQUIREMENTS FOR USE GROUP R-3. 21 USE GROUP R-3 BUILDINGS SHALL BE CONSTRUCTED UTILIZING THE 22 FOLLOWING MINIMUM INSULATION STANDARDS: 23 CEILINGS R - 19 24 EXTERIOR WALLS R - 13 25 FLOORS OVER UNHEATED BASEMENTS 26 AND CRAWL SPACES * R - 11 27 * BASEMENTS CONTAINING A FURNACE 28 AND/OR HOT WATER HEATER MAY BE 29 CONSIDERED HEATED 30 EDGE INSULATION FOR: 19770H0552B3369 - 43 -
1 HEATED SLABS R - 6.3 2 UNHEATED SLABS R - 4.2 3 WINDOWS DOUBLE GLAZED** 4 ** WINDOWS MAY BE SINGLE GLAZED 5 WHEN STORM WINDOWS ARE USED 6 ENTRANCE DOORS R - 2.5 7 SLIDING GLASS DOORS (IF APPLICABLE) DOUBLE GLAZED 8 DUCTS IN UNHEATED AREAS R - 3 9 CHAPTER 3 10 APPLICATION OF STANDARDS: ESTABLISHMENT 11 OF COMMITTEE AND PENALTIES 12 Section 301. Modification of standards; criteria. 13 The department, with the approval of the Building Energy 14 Conservation Committee established pursuant to section 304, 15 after one or more public hearings, may recommend to the General 16 Assembly modifications to the energy conservation standards 17 contained in Chapter 2 hereof. Any recommended modification to 18 the energy conservation standards shall meet the following 19 criteria: 20 (1) It shall be consistent with the latest and most 21 effective technology. 22 (2) It shall not be in conflict with existing safeguards 23 for public health and safety. 24 (3) It shall be economically feasible as determined by 25 life-cycle-cost procedures. 26 (4) It shall be sufficiently stringent to effect a 27 significant savings of energy resources. 28 (5) It shall be a performance standard for the design of 29 buildings and systems within buildings to assure maximum 30 practical conservation of energy. 19770H0552B3369 - 44 -
1 (6) Consideration shall be given to building and energy 2 standards promulgated by national and other state 3 governmental agencies, private organizations and any other 4 available energy data, as well as the total energy allocation 5 approach. 6 Section 302. Application of energy conservation standards. 7 The energy conservation standards contained herein or as 8 promulgated by the department with the approval of the Building 9 Energy Conservation Committee shall apply to new buildings or to 10 renovations on which actual construction and/or design has not 11 commenced prior to their effective dates. NO DEPARTMENT, BOARD, <-- 12 AGENCY OR COMMISSION OTHER THAN AS PROVIDED HEREIN, SHALL 13 PROMULGATE OR ADOPT ANY RULES OR REGULATIONS WHICH DEAL WITH ANY 14 SUBJECT MATTER CONTAINED IN THIS ACT. 15 Section 303. Energy conservation manual for buildings. 16 (a) Production of manual.--Concurrent with the adoption of 17 the energy conservation codes required by this act, the 18 department shall produce an energy conservation manual for use 19 by designers, builders, and contractors of residential and 20 nonresidential buildings, and municipalities of the 21 Commonwealth. This manual shall contain the established 22 standards and accepted practices. The manual shall further 23 contain prescriptive standards which, if complied with, will 24 result in conformance with the performance standards contained 25 herein or as promulgated by the department and shall be written 26 in such manner as to be easily understood by persons possessing 27 a minimal technical background. The manual shall be furnished 28 upon request to members of the public at a price sufficient to 29 cover the cost of printing. 30 (b) Review of manual.--The manual shall be reviewed by the 19770H0552B3369 - 45 -
1 department and the Building Energy Conservation Committee at 2 least annually and shall be updated as significant new energy 3 conservation information becomes available. 4 (c) Educational programs.--The department shall provide 5 seminars and other educational programs throughout the 6 Commonwealth to provide information and counseling to builders, 7 architects, other licensed design professionals, local building 8 officials and other persons affected by this act on the 9 standards contained herein or as promulgated by the department. 10 Section 304. Building Energy Conservation Committee. 11 (a) Composition of committee.--In order to further the 12 coordinated and effective administration of this act, there is 13 hereby established a Building Energy Conservation Committee. It 14 shall consist of at least 30 members and no more than 40 15 members, the membership of which shall be appointed by the 16 Governor and shall include a representative of each of the 17 following entities or their successors: 18 (1) Department of Education. 19 (2) Governor's Energy Council. 20 (3) Department of General Services. 21 (4) Department of Labor and Industry. 22 (5) Department of Community Affairs. 23 (6) Pennsylvania Builders Association. 24 (7) Pennsylvania Associated Builders and Contractors, 25 Inc. 26 (8) Pennsylvania Building Officials Conference. 27 (9) Mechanical Contractors Association of America. 28 (10) Pennsylvania Chamber of Commerce. 29 (11) General Contractors Association of Pennsylvania. 30 (12) Pennsylvania Society of Architects. 19770H0552B3369 - 46 -
1 (13) Pennsylvania Society of Professional Engineers. 2 (14) American Society of Heating, Refrigerating and Air 3 Conditioning Engineers, Inc.. 4 (15) Pennsylvania Gas Association. 5 (16) Pennsylvania Electric Association. 6 (17) Industrialized Housing Manufacturers Association. 7 (18) Thermal Insulation Manufacturers Association. 8 (19) Pennsylvania Building Trades Council. 9 (20) Consulting Engineers Council of Pennsylvania. 10 (21) Pennsylvania League of Cities. 11 (22) Pennsylvania State Association of Boroughs. 12 (23) Pennsylvania State Association of Township 13 Commissioners. 14 (24) Pennsylvania State Association of Township 15 Supervisors. 16 25 Representatives of such other agencies and 17 organizations or individuals as the Governor may find are 18 necessary and proper to carry out the purposes of the 19 committee including, but not limited to, labor organizations, 20 financial and lending institutions, and consumer groups. 21 (b) Powers and duties.--In addition to the powers and duties 22 enumerated in this act, the Building Energy Conservation 23 Committee shall: 24 (1) Be responsible for the regular exchange of 25 information and plans regarding building energy conservation, 26 for the development, review and approval of proposed and 27 existing standards, guidelines, regulations, and manuals. 28 (2) Elect from its members a Board on Variances. 29 (c) Expenses.--The members of the committee shall not 30 receive any compensation for their services but shall be 19770H0552B3369 - 47 -
1 reimbursed for their actual and necessary expenses incurred in 2 the performance of their duties. Provided, however, when acting 3 on matters concerning variances members of the Board on 4 Variances shall receive $50 per day plus their actual and 5 necessary expenses. 6 Section 305. Certification. 7 (a) Applicability.--The provisions of this section shall 8 apply to all buildings subject to this act except those 9 classified as Use Group R-3. 10 (b) Compliance with act.--It shall be the duty of the 11 licensed design professional retained in connection with the 12 design or construction of a building to certify the drawings, 13 specifications and other data showing compliance with the 14 provisions of this act, except as provided in subsection (e). If 15 the building is subject to the provisions of the act of April 16 27, 1927 (P.L.465, No.299), referred to as the Fire and Panic 17 Act, the certification required hereunder shall be submitted on 18 a form with the application for plan approval under the said 19 Fire and Panic Act. 20 (c) Inspection.--Each licensed design professional retained 21 by the owner or his designee, where any of such are retained 22 during the construction of a building, shall make periodic 23 inspections of the building progression to insure compliance 24 with this act, except as provided in subsection (e). 25 (d) Final certification.--Each licensed design professional 26 retained by the owner shall make a final certification of every 27 completed building showing compliance with the provisions of 28 this act, except as provided in subsection (e). 29 (e) Certification by builder.--If a licensed design 30 professional is not retained in connection with the design and 19770H0552B3369 - 48 -
1 construction of a building, it shall be the responsibility of 2 the builder or owner, if he is the builder, to perform the 3 inspections and certification required by this section. 4 Section 306. Use Group R-3; notice; warranty. 5 (a) Notice.--Prior to construction of any building 6 classified as Use Group R-3, the builder shall notify the 7 department by certified mail of his intent to begin 8 construction. Such notice shall contain the name of the owner of 9 the building and its location. 10 (b) Warranty.--At the time a contract for the construction 11 of any building classified as Use Group R-3 is entered into, the 12 builder shall warrant to the owner in writing that the building 13 shall be constructed in accordance with the provisions of this 14 act. Such warranty shall be a document separate from the 15 contract and shall be in the following form: 16 I, (Builder) , hereby warrant to (Owner) that the 17 premises known as (Description) 18 shall be constructed in accordance with the provisions of the 19 Act of __________, 19__, No.____, known as the "Building Energy 20 Conservation Act." This law provides building and equipment 21 standards to make your home energy efficient and also provides 22 you with legal remedies if your home is not built according to 23 the State standards. If you would like the State to do an 24 energy audit of your home to determine if it conforms to State 25 standards, you may call the Pennsylvania Department of 26 Community Affairs at (Telephone) , and they will perform an 27 inspection of your home for a fee of $25.00. 28 Indicate if alternate building system or equipment design is 29 being employed. 30 (c) If the builder is also the owner of the building at the 19770H0552B3369 - 49 -
1 time of construction, he shall provide the warranty required by 2 subsection (b) at the time of its initial sale to a new owner. 3 Such warranty shall be in substantially the same form as 4 provided in subsection (b). 5 (d) Failure to provide notice.--The Department of Community 6 Affairs, after hearing, may assess a civil penalty payable to 7 the Commonwealth of Pennsylvania not to exceed $100 upon any 8 builder who fails to give the notice required by subsection (a). 9 In determining the amount of the civil penalty, the Department 10 of Community Affairs shall consider the wilfulness of the 11 violation and the cost incurred by the department in discovering 12 the violation. 13 (e) Failure to provide warranty.--Whenever a builder fails 14 to provide the warranty required by subsections (b) or (c) such 15 required warranty shall constitute an implied warranty and the 16 owner's right to proceed under section 315(a) shall not be 17 affected. If it is established by a preponderance of the 18 evidence that the builder's failure to provide the warranty was 19 wilful, then damages in twice the amount provided in section 315 20 may be awarded. 21 Section 307. Variances. 22 (a) Requests.--Any request for a variance from the energy 23 conservation standards contained herein shall be made to the 24 Board on Variances of the Building Energy Conservation Committee 25 and a decision on such request shall be made within 30 days of 26 its filing. 27 (b) Criteria.--A variance shall be granted only if it is 28 found that: 29 (1) compliance with the provisions of this act would 30 result in extreme hardship to the owner; and 19770H0552B3369 - 50 -
1 (2) the granting of such variance would not result in a 2 significant increase in the energy usage of the building. 3 Section 308. Building permits. 4 Any building permit issued by the Commonwealth or any of its 5 political subdivisions shall have printed upon its face notice 6 that the provisions of this act must be complied with. 7 Section 309. Permits for use or occupancy. 8 Before any building or structure hereafter constructed, other 9 than a building classified as Use Group R-3, shall be used or 10 opened for occupancy, the owner thereof shall notify the 11 department of the completion of the building for the purposes of 12 this act and submit the necessary certification therewith: 13 Provided, however, That if a municipality elects to administer 14 the provisions of this act under Chapter 5 such notice and 15 certification shall be submitted to the municipality which shall 16 forward a copy of the notice to the department. No permit for 17 use or occupancy shall be granted until such submission has been 18 made. No building official of the Commonwealth or any of its 19 political subdivisions shall issue a permit until he has 20 received proof of such compliance. Where the certificate has 21 been submitted to the department, presentation to the building 22 official of the mailing receipt together with a copy of the 23 certification required by section 305 shall establish proof of 24 compliance for the purposes of this section. Upon such 25 presentation any building official of the Commonwealth or any of 26 its political subdivisions shall issue a permit for use or 27 occupancy, provided all other criteria for such a permit have 28 been satisfied and said building official shall notify the 29 department that he has issued the same. 30 Section 310. Failure to submit certification. 19770H0552B3369 - 51 -
1 Whenever the owner of any building, other than a building 2 classified as Use Group R-3, shall fail to give the notice and 3 submit the necessary certification in accordance with section 4 309 and shall nevertheless proceed with the use or occupancy of 5 the building, the department or the municipality shall serve 6 notice on the said owner that he is in violation of this act and 7 order him to comply therewith. 8 Section 311. Inspections. 9 The department may perform a nondestructive inspection within 10 two years of the date of completion of construction of any 11 building constructed after the effective date of this act to 12 determine compliance with the provisions of this act, provided 13 at least 30 days notice has been given to the owner. The 14 department may also perform such inspections at the request of 15 the owner of any building subject to this act for a fee of 16 $25.00. 17 Section 312. Appeals. 18 Review of any decisions rendered under the provisions of this 19 act shall be brought in the court of common pleas of the county 20 wherein the building is situated. Such review shall be limited 21 to determining whether any such decision was arbitrary and 22 capricious. 23 Section 313. Penalties. 24 (a) Applicability.--The provisions of this section shall 25 apply to all buildings subject to this act except those 26 classified as Use Group R-3. 27 (b) Violations of act.--Any person who shall willfully or 28 negligently violate any of the provisions of this act, or the 29 rules and regulations or the orders for the enforcement of the 30 said provisions or rules and regulations issued by duly 19770H0552B3369 - 52 -
1 authorized officers of the department or who shall hinder, delay 2 or interfere with any officer charged with the enforcement of 3 this act in the performance of his duty, shall, upon conviction 4 thereof, be punished by a fine of not more than $300 and costs. 5 In the event of violation of more than one provision of this 6 act, the violation of each provision shall be deemed a separate 7 and distinct offense for the purposes of this section. 8 (c) Institution of proceedings.--Prosecutions for violations 9 of this act or the rules and regulations of the department may 10 be instituted by the Secretary of Labor and Industry or under 11 his directions by an authorized representative of the 12 department. Upon conviction after a hearing in a court of 13 competent jurisdiction, the sentences provided in this act shall 14 be imposed and shall be final unless an appeal be taken in the 15 manner prescribed by law. 16 (d) Disposition of fines.--All fines collected under this 17 act shall be forwarded to the department who shall pay the same 18 into the State Treasury for the use of the Commonwealth. 19 (e) False certification.--Any architect or other licensed 20 design professional who willfully provides a false certification 21 for any building subject to the provisions of this act shall be 22 subject to the suspension or revocation of his license by the 23 State Board of Examiners of Architects or other applicable State 24 licensing board. 25 Section 314. Enforcement. 26 (a) Applicability.--The provisions of this act shall apply 27 to every building enumerated in this act, including buildings 28 owned in whole or in part by the Commonwealth or any political 29 subdivision thereof, and for all buildings, other than those 30 classified as Use Group R-3 shall be enforced by the Secretary 19770H0552B3369 - 53 -
1 of Labor and Industry, by and through his authorized 2 representatives. 3 (b) Powers of officers.--For the purpose of enforcing the 4 provisions of this act, all the officers charged with its 5 enforcement shall have the power to enter any of the buildings 6 enumerated in this act, and no person shall hinder or delay, or 7 interfere with any of the said officers in the performance of 8 his duty, nor refuse any pertinent information necessary to 9 determine whether the provisions of this act and the rules and 10 regulations herein provided for, are or will be complied with. 11 Section 315. Civil action. 12 (a) Use Group R-3.--The owner of any building subject to the 13 requirements of section 306 who is aggrieved as the result of 14 such building not being properly designed or constructed in 15 conformance with this act shall have a right of action for 16 breach of warranty. Remedies may include specific performance or 17 an award of damages in an amount not less than $300. Attorney's 18 fees shall be recoverable in any action in which the owner 19 prevails. Any such award shall further provide for payment of 20 the actual costs in excess of $25 incurred by the department if 21 it inspected the building for the owner and the owner shall 22 remit such amount to the department. 23 (b) Other buildings.--The owner of any building, other than 24 a building classified as Use Group R-3, at the time of its 25 design or construction under the provisions of this act who is 26 aggrieved as the result of such building not being properly 27 designed or constructed in conformance with this act shall have 28 a right of action against any person who is required to submit 29 the certificate required by section 305. 30 (c) Limitation of action.--No action brought under this 19770H0552B3369 - 54 -
1 section shall be maintained unless brought within three years 2 from the date of completion of the building. 3 CHAPTER 4 4 ADOPTION OF FUTURE STANDARDS 5 Section 401. Adoption and promulgation of standards. 6 The department, with the approval of the Building Energy 7 Conservation Committee, shall, after one or more public 8 hearings, adopt and publish energy conservation standards for 9 all buildings covered by this act in accordance with the 10 provisions of the act of July 31, 1968 (P.L.769, No.240), known 11 as the "Commonwealth Documents Law." The purpose of such 12 standards is to reduce wasteful or uneconomic consumption of 13 energy by balancing the cost of energy procurement against the 14 cost of energy-conserving building practices. The energy 15 conservation standards shall meet the following criteria: 16 (1) They shall be consistent with the latest and most 17 effective technology. 18 (2) They shall not be in conflict with existing 19 safeguards for public health and safety. 20 (3) They shall be economically feasible as determined by 21 life-cycle-cost procedures. 22 (4) They shall be sufficiently stringent to effect a 23 significant savings of energy resources. 24 (5) They shall be a performance standard for the design 25 of buildings and systems within buildings to assure maximum 26 practical conservation of energy. 27 (6) Consideration shall be given to building and energy 28 standards promulgated by national and other State 29 governmental agencies, private organizations and any other 30 available energy data, as well as the total energy allocation 19770H0552B3369 - 55 -
1 approach. 2 CHAPTER 5 3 LOCAL ELECTION 4 Section 501. Election; Use Group R-3. 5 Any municipality of this Commonwealth may elect to administer 6 the provisions of this act relating to Use Group R-3 buildings, 7 as defined in section 103, except for units subject to the act 8 of May 11, 1972 (P.L.286, No.70), known as the "Industrialized 9 Housing Act" and the act of May 11, 1972 (P.L.281, No.69), known 10 as the "Uniform Standards Code for Mobile Homes." Such election 11 shall be made by resolution of the governing body of such 12 municipality which shall be in substantially the following form: 13 The (city, borough, town, or township) of____________________ 14 hereby elects to administer the provisions of the act 15 of____________, 1978, No._______ known as the "Building Energy 16 Conservation Act" for Use Group R-3 buildings as defined 17 therein. 18 Section 502. Election; cities of the first, second and second 19 class A. 20 Any city of the first class, second class and second class A 21 may elect to administer the provisions of this act for all 22 buildings subject hereto, except for units subject to the act of 23 May 11, 1972 (P.L.286, No.70), known as the "Industrialized 24 Housing Act" and the act of May 11, 1972 (P.L.281, No.69), known 25 as the "Uniform Standards Code for Mobile Homes." Such election 26 shall be made by resolution of the governing body of such city 27 which shall be in substantially the following form: 28 The city of________________hereby elects to administer the 29 provisions of the act of _________, 1978, No._______ known as 30 the "Building Energy Conservation Act." 19770H0552B3369 - 56 -
1 Section 503. Powers of municipalities. 2 Any municipality electing to administer the provisions of 3 this act under section 501 or 502 shall exercise the same powers 4 conferred upon the department by this act, including the power 5 to institute proceedings for violations of the act, with the 6 exception of those powers specified in sections 301, 303 and in 7 Chapter 4. In addition, any such municipality may exercise such 8 other administrative and enforcement procedures as it shall deem 9 necessary to effect the purposes of this act including, but not 10 limited to, prior plan approval, building permit requirements, 11 use or occupancy permit requirements and inspections during the 12 course of construction. 13 Section 504. Variances. 14 Any municipality electing to administer the provisions of 15 this act under section 501 or 502 shall establish a Board on 16 Variances to make determinations on request for variance from 17 the energy conservation standards contained herein or as 18 promulgated by the department with the approval of the Building 19 Energy Conservation Committee, and is authorized exclusive 20 jurisdiction to grant such variances, section 307(a) 21 notwithstanding. A variance shall only be granted if the 22 criteria of section 307(b) have been satisfied. 23 Section 505. Disposition of fines. 24 Any fines collected under this act by any municipality 25 electing to administer the provisions of this act under section 26 501 or 502 shall be retained by the municipality, section 313(c) 27 notwithstanding. 28 CHAPTER 6 29 REPORT TO GENERAL ASSEMBLY 30 Section 601. Report to General Assembly. 19770H0552B3369 - 57 -
1 Thirty months after the effective date of this act, the 2 department shall report to the General Assembly the results of 3 the inspections it has performed under this act together with a 4 report on public compliance with this act. 5 Section 602. Effective date. 6 This act shall take effect as follows: 7 (1) Chapter 2 shall take effect in six months and shall 8 remain in full force and effect for a period of one year 9 after which time the provisions of Chapter 2 shall have no 10 legal effect. 11 (2) Section 301 shall take effect immediately and its 12 provisions shall remain in full force and effect for a period 13 of 18 months after which time said provisions shall have no 14 legal effect. 15 (3) Chapter 4 shall take effect in 18 months. 16 (4) All other provisions of this act shall take effect 17 immediately. B10L42JLW/19770H0552B3369 - 58 -