PRIOR PRINTER'S NOS. 600, 1775, 2328,         PRINTER'S NO. 2905
        2464, 2503

THE GENERAL ASSEMBLY OF PENNSYLVANIA


HOUSE BILL

No. 552 Session of 1977


        INTRODUCED BY MESSRS. ITKIN, B. F. O'BRIEN, TRELLO, GAMBLE,
           McCALL, LEHR, SWEET AND J. L. WRIGHT, MARCH 7, 1977

        AS RE-REPORTED FROM COMMITTEE ON MINES AND ENERGY MANAGEMENT,
           HOUSE OF REPRESENTATIVES, AS AMENDED, APRIL 4, 1978

                                     AN ACT

     1  Providing for the regulation for energy conservation purposes of
     2     the construction of buildings, the establishment of a
     3     Building Energy Conservation Committee and a Board on
     4     Variances, appeals and for penalties.

     5                         TABLE OF CONTENTS
     6  Chapter 1.  General Provisions
     7     Section 101.  Short title.
     8     Section 102.  Legislative findings and declaration of
     9                   purpose.
    10     Section 103.  Definitions.
    11  Chapter 2.  Energy Conservation Standards
    12     SUBCHAPTER A.  GENERAL PROVISIONS                              <--
    13     Section 201.  Provisions.
    14     Subchapter A B.  Plans and Specifications                      <--
    15     Section 202.  Submission.
    16     Section 203.  Contents.
    17     Subchapter B C.  Definitions Relating to Energy Conservation   <--
    18                    Standards

     1     Section 204.  Definitions relating to standards.
     2     Subchapter C D.  Building Envelope                             <--
     3     Section 205.  General provisions.
     4     Section 206.  Criteria for residential buildings.
     5     Section 207.  Other buildings.
     6     Section 208.  Air leakage.
     7     Subchapter D E.  Warm Air Heating, Ventilating and Air         <--
     8                    Conditioning Systems and Equipment
     9     Section 209.  General provisions.
    10     Section 210.  Design requirements.
    11     Section 211.  Cooling with outdoor air.
    12     Section 212.  Mechanical ventilation.
    13     Section 213.  Simultaneous heating and cooling.
    14     Section 214.  Recovered energy.
    15     Section 215.  New energy.
    16     Section 216.  Reheat systems.
    17     Section 217.  Dual duct and multizone systems.
    18     Section 218.  Recooling systems.
    19     Section 219.  Multiple zones.
    20     Section 220.  Concurrent operation.
    21     Section 221.  Equipment performance requirements.
    22     Section 222.  Duct insulation.
    23     Section 223.  System controls.
    24     Section 224.  Steam and hot water heating piping.
    25     Subchapter E F.  Plumbing Systems                              <--
    26     Section 225.  Purpose.
    27     Section 226.  Fixtures.
    28     Section 227.  Insulation.
    29     Section 228.  Equipment.
    30     Section 229.  Controls.
    19770H0552B2905                  - 2 -

     1     Subchapter F G.  Electrical Systems                            <--
     2     Section 230.  System requirements.
     3     Subchapter G H.  Lighting                                      <--
     4     Section 231.  Light power budget.
     5     Section 232.  Calculation methods.
     6     Section 233.  Building interiors.
     7     Section 234.  Building exteriors.
     8     Section 235.  Exceptions to criteria.
     9     Section 236.  Calculation procedure.
    10     Subchapter H I.  Alternative Systems                           <--
    11     Section 237.  Performance alternative.
    12     Section 238.  Nondepletable sources.
    13     Section 239.  Documentation.
    14  Chapter 3.  Application of Standards:  Establishment of
    15              Committee and Penalties
    16     Section 301.  Modification of standards; criteria.
    17     Section 302.  Application of energy conservation standards.
    18     Section 303.  Energy conservation manual for buildings.
    19     Section 304.  Building Energy Conservation Committee.
    20     Section 305.  Certification.
    21     SECTION 306.  USE GROUP R-3; NOTICE; WARRANTY.                 <--
    22     Section 306 307.  Variances.                                   <--
    23     Section 307 308.  Building permits.                            <--
    24     Section 308 309.  Permits for use or occupancy.                <--
    25     Section 309 310.  Failure to submit certification.             <--
    26     Section 310 311.  Inspections.                                 <--
    27     Section 311 312.  Appeals.                                     <--
    28     Section 312 313.  Penalties.                                   <--
    29     Section 313 314.  Enforcement.                                 <--
    30     SECTION 315.  CIVIL ACTION.                                    <--
    19770H0552B2905                  - 3 -

     1  Chapter 4.  Adoption of Future Standards
     2     Section 401.  Adoption and promulgation of standards.
     3  CHAPTER 5.  LOCAL ELECTION                                        <--
     4     SECTION 501.  ELECTION; USE GROUP R-3.
     5     SECTION 502.  ELECTION; CITIES OF THE FIRST, SECOND AND
     6                   SECOND CLASS A.
     7     SECTION 503.  POWERS OF MUNICIPALITIES.
     8     SECTION 504.  VARIANCES.
     9     SECTION 505.  DISPOSITION OF FINES.
    10  CHAPTER 6.  REPORT TO GENERAL ASSEMBLY
    11     SECTION 601.  REPORT TO GENERAL ASSEMBLY
    12     Section 402 602.  Effective date.                              <--
    13     The General Assembly of the Commonwealth of Pennsylvania
    14  hereby enacts as follows:
    15                             CHAPTER 1
    16                         GENERAL PROVISIONS
    17  Section 101.  Short title.
    18     This act shall be known and may be cited as the "Building
    19  Energy Conservation Act."
    20  Section 102.  Legislative findings and declaration of purpose.
    21     (a)  Findings.--The Legislature hereby determines that:
    22         (1)  Energy shortages in the domestic supply present far-
    23     reaching problems that promise to persist. These energy
    24     shortages affect the continued efficient operation of the
    25     Commonwealth's economy and social structure.
    26         (2)  It is the Commonwealth's responsibility to provide
    27     for energy conservation through regulation of design and
    28     construction standards.
    29         (3)  The Legislature intends, by this act, to respond to
    30     these shortages by devising a specific responsible energy
    19770H0552B2905                  - 4 -

     1     conservation policy for building systems.
     2     (b)  Purpose.--The purpose of this act is to grant to the
     3  Commonwealth of Pennsylvania and direct it to exercise specific
     4  authority in building construction to assure that such
     5  construction is performed using materials and techniques that
     6  will provide for energy conservation in the future operation and
     7  maintenance of said structure BUILDINGS.                          <--
     8  Section 103.  Definitions.
     9     The following words and phrases when used in this act shall
    10  have, unless the context clearly indicates otherwise, the
    11  meanings given to them in this section:
    12     "Building."  Any structure that provides facilities or
    13  shelter for public assembly or for educational, business,
    14  mercantile, institutional, warehouse or residential occupancy,
    15  or industrial use including, but not limited to, those portions
    16  of factory and industrial occupancy such as office space except
    17  for:
    18         (1)  Buildings and structures or portions thereof whose
    19     peak design rate of energy usage is less than one watt per
    20     square foot or 3.4 BTU/hr per square foot of floor area for
    21     all purposes.
    22         (2)  Structures or those portions of structures used for
    23     manufacturing or processing and whose manufacturing or
    24     processing procedures require the use of substantial heat
    25     producing energy or cooling to create their product.
    26         (3)  Buildings which are neither heated nor cooled.
    27         (4)  Historic buildings.
    28         (5)  BUILDINGS OWNED BY THE FEDERAL GOVERNMENT.            <--
    29     "Construction."  The erection, fabrication or renovation of a
    30  building.
    19770H0552B2905                  - 5 -

     1     "Department."  The Pennsylvania Department of Labor and
     2  Industry except that for all units subject to the act of May 11,
     3  1972 (P.L.286, No.70), known as the "Industrialized Housing
     4  Act," ALL UNITS SUBJECT TO THE ACT OF MAY 11, 1972 (P.L.281,      <--
     5  NO.69), KNOWN AS THE "UNIFORM STANDARDS CODE FOR MOBILE HOMES,"
     6  and all buildings classified as Use Group R-3, herein,
     7  department means the Pennsylvania Department of Community
     8  Affairs.
     9     "Design."  Calculations and resultant drawings and
    10  specifications which are used for the construction of a
    11  building.
    12     "Historic building."  Any building determined by the State
    13  Historic Preservation Officer to meet the criteria for listing
    14  on the National Register of Historic Places but only to the
    15  extent that compliance with this act would prevent preservation
    16  of the historic or architectural integrity of the building.
    17     "Licensed design professional."  A person licensed as an
    18  architect or professional engineer pursuant to the appropriate
    19  licensure act.
    20     "Life-cycle cost."  The cost of a building including its
    21  initial cost, the cost of the energy consumed over its economic
    22  life and the cost of its operation and maintenance.
    23     "MUNICIPALITY."  A CITY, BOROUGH, INCORPORATED TOWN OR         <--
    24  TOWNSHIP.
    25     "Performance standards."  Parameters within which designers
    26  of buildings shall work. The specific practices that a designer
    27  employs shall not be prescribed as long as the result is within
    28  the parameters established by the standards.
    29     "Renovation."  (a)  The rehabilitation of an existing
    30  building which requires more than 25% of the gross floor area or
    19770H0552B2905                  - 6 -

     1  volume of the entire building to be rebuilt; or
     2     (b)  any addition to an existing building: Provided, however,
     3  That the provisions of this act shall only apply to such
     4  addition PORTION OF THE BUILDING BEING RENOVATED and not to the   <--
     5  entire building.
     6                             CHAPTER 2
     7                   ENERGY CONSERVATION STANDARDS
     8                            SUBCHAPTER A                            <--
     9                         GENERAL PROVISIONS
    10  Section 201.  Provisions.
    11     The following provisions regulate the design and construction
    12  of the exterior envelopes and selection of HVAC, service water
    13  heating, electrical distribution, and illumination systems and
    14  equipment required for the purpose of effective use of energy
    15  and shall govern the construction of all buildings, or portions
    16  thereof, as provided herein.
    17                           SUBCHAPTER A B                           <--
    18                      PLANS AND SPECIFICATIONS
    19  Section 202.  Submission.
    20     Plans, specifications, necessary computations and any changes  <--
    21  (A)  PLANS.--PLANS, SPECIFICATIONS, COMPUTATIONS WHERE            <--
    22  NECESSARY, AND ANY CHANGES thereto together with the necessary
    23  certification required by section 305 shall be submitted FOR ALL  <--
    24  BUILDINGS EXCEPT THOSE CLASSIFIED AS USE GROUP R-3 to indicate
    25  conformance with this chapter and other applicable chapters of
    26  this act, EXCEPT AS PROVIDED IN SUBSECTIONS (B) AND (C).          <--
    27     (B)  STANDARD DESIGN.--WHENEVER A PERSON IS CONSTRUCTING A
    28  BUILDING IN ACCORDANCE WITH PLANS, SPECIFICATIONS AND
    29  COMPUTATIONS WHICH HE HAS SUBMITTED WITHIN THE PREVIOUS TWO
    30  YEARS, SUCH PLANS NEED NOT BE RESUBMITTED BUT SUCH PERSON SHALL
    19770H0552B2905                  - 7 -

     1  INDICATE UPON THE CERTIFICATE REQUIRED BY SECTION 305 THAT THEY
     2  MEET THE STANDARDS CURRENTLY IN EFFECT AND IDENTIFY THE
     3  PREVIOUSLY SUBMITTED PLANS, SPECIFICATIONS AND COMPUTATIONS.
     4     (C)  PRESCRIPTIVE STANDARDS.--WHEN THE PRESCRIPTIVE STANDARDS
     5  PROVIDED IN THE ENERGY CONSERVATION MANUAL ESTABLISHED BY
     6  SECTION 303 ARE EMPLOYED IN THE CONSTRUCTION OF A BUILDING ONLY
     7  SUCH INFORMATION AS SHALL BE REQUIRED BY THE DEPARTMENT SHALL BE
     8  SUBMITTED.
     9  Section 203.  Contents.
    10     The plans and specifications, WHERE REQUIRED BY SECTION 202,   <--
    11  shall show in sufficient detail all pertinent data and features
    12  of the building and the equipment and systems as herein
    13  governed, including but not limited to: exterior envelope
    14  component materials, U values of elements, R values of
    15  insulating materials, size and type of apparatus and equipment,
    16  equipment and system controls and other pertinent data to
    17  indicate conformance with the requirements herein.
    18                           SUBCHAPTER B C                           <--
    19                      DEFINITIONS RELATING TO
    20                   ENERGY CONSERVATION STANDARDS
    21  Section 204.  Definitions relating to standards.
    22     The following words and phrases when used in this chapter
    23  shall have, unless the context clearly indicates otherwise, the
    24  meanings given to them in this section:
    25     "Coefficient of beam utilization" (CBU).  The ratio of the
    26  luminous flux (lumens) reaching a specified area directly from a
    27  floodlight or projector to the total beam luminous flux.
    28     "Coefficient of performance" (COP) - cooling. The ratio of
    29  the rate of net heat removal to the rate of total energy input,
    30  expressed in consistent units and under designated rating
    19770H0552B2905                  - 8 -

     1  conditions.
     2     "Coefficient of performance" (COP) - heat pump, heating. The
     3  ratio of the rate of net heat output to the rate of total energy
     4  input, expressed in consistent units and under designated rating
     5  conditions.
     6     The rate of net heat output shall be defined as the change in
     7  the total heat contents of the air entering and leaving the
     8  equipment not including supplementary heat.
     9     Total energy input shall be determined by combining the
    10  energy inputs to all elements, except supplementary heaters, of
    11  the heat pump, including, but not limited to, compressors,
    12  pumps, supply air fans, return air fans, outdoor air fans,
    13  cooling tower fans and the heating, ventilating and air
    14  conditioning system equipment control circuit.
    15     "Coefficient of utilization" (CU).  The ratio of the luminous
    16  flux (lumens) from a luminaire received on the work plane to the
    17  lumens emitted by the luminaire's lamps alone.
    18     "Color rendition."  General expression for the effect of a
    19  light source on the color. Appearance of objects in conscious or
    20  subconscious comparison with their color appearance under a
    21  reference light source.
    22     "Degree day, heating."  A unit, based upon temperature
    23  difference and time, used in estimating fuel consumption and
    24  specifying nominal heating load of a building in winter. For any
    25  one day, when the mean temperature is less than 65 F., there
    26  exist as many degree days as there are Fahrenheit degrees
    27  difference in temperature between the mean temperature for the
    28  day and 65 F.
    29     "Energy efficiency ratio" (EER).  The ratio of net cooling
    30  capacity in Btuh to total rate of electric input in watts under
    19770H0552B2905                  - 9 -

     1  designated operating conditions.
     2     "Equivalent sphere illumination" (ESI).  The level of sphere
     3  illumination which would produce task visibility equivalent to
     4  that produced by a specific lighting environment.
     5     "Exterior envelope."  The elements of a building which
     6  enclose conditioned spaces through which thermal energy may be
     7  transferred to or from the exterior.
     8     "Floodlighting."  A lighting system designated to light an
     9  area using projector type luminaires usually capable of being
    10  pointed in any direction.
    11     "Floor area, gross."  Gross floor area shall be the floor
    12  area within the perimeter of the outside walls of the building
    13  under consideration, without deduction for hallways, stairs,
    14  closets, thickness of walls, columns or other features.
    15     "Illumination."  The density of the luminous flux incident on
    16  a surface. It is the quotient of the luminous flux by the area
    17  of the surface when the latter is uniformly illuminated.
    18     "Light loss factor" (LLF).  A factor used in calculating the
    19  level of illumination after a given period of time and under
    20  given conditions. It takes into account temperature and voltage
    21  variations, dirt accumulation on luminaire and room surfaces,
    22  lamp depreciation, maintenance procedures and atmosphere
    23  conditions.
    24     "Luminaire."  A complete lighting unit consisting of a lamp
    25  or lamps together with the parts designed to distribute the
    26  light, to position and protect the lamps and to connect the
    27  lamps to the power supply.
    28     "Packaged terminal air conditioner."  A factory selected
    29  combination of heating and cooling components, assemblies or
    30  sections, intended to serve a room or zone.
    19770H0552B2905                 - 10 -

     1     "Power."  In connection with machines, power is the time rate
     2  of doing work. In connection with the transmission of energy of
     3  all types, power refers to the rate at which energy is
     4  transmitted; in customary units, it is measured in watts (W) or
     5  British thermal units per hour (Btuh) and in SI units is
     6  measured in watts (W).
     7     "Reflectance."  The ratio of the light reflected by a surface
     8  to the light falling upon it.
     9     "Reheat."  The application of sensible heat to supply air
    10  that has been previously cooled below the temperature of the
    11  conditioned space by either mechanical refrigeration or the
    12  introduction of outdoor air to provide cooling.
    13     "Residential buildings."  All buildings and structures or
    14  parts thereof shall be classified in the residential (R) use
    15  group in which families or households live, or in which sleeping
    16  accommodations are provided for individuals with or without
    17  dining facilities, excluding those that are classified as
    18  institutional buildings. Residential buildings shall be
    19  classified as follows:
    20     (1)  Use group R-1 structures.  This use group shall include
    21  all hotel and motel buildings, lodging houses, boarding houses
    22  and dormitory buildings arranged for the shelter and sleeping
    23  accommodation of more than 20 individuals.
    24     (2)  Use group R-2 structures.  This use group shall include
    25  all multiple-family dwellings having more than two dwelling
    26  units; and shall also include all dormitories, boarding and
    27  lodging houses arranged for shelter and sleeping accommodation
    28  by more than five and not more than 20 individuals.
    29     (3) Use group R-3 structures.  This use group shall include
    30  all buildings arranged for the use of one or two family dwelling
    19770H0552B2905                 - 11 -

     1  units including not more than five lodgers or boarders per
     2  family.
     3     "Resistance, thermal" (R).  A measure of the ability to
     4  retard the flow of heat. The R value is the reciprocal of a heat
     5  transfer coefficient, as expressed by U.  (R = 1/U).
     6     "Thermal transmittance" (U).  Overall coefficient of heat
     7  transmission or thermal transmittance (air to air) expressed in
     8  units of BTU per hour per square foot per degree F.  It is the
     9  time rate of heat flow. The U value applies to combinations of
    10  different materials used in series along the heat flow path and
    11  also to single materials that comprise a building section and
    12  include cavity air spaces and surface air films on both sides.
    13     "Thermal transmittance" (Uo).  Overall (average) heat
    14  transmission or thermal transmittance of a gross area of the
    15  exterior building envelope, expressed in units of BTU per hour
    16  per square foot per degree F.
    17     The Uo value applies to the combined effect of the time rate
    18  of heat flows through the various parallel paths, such as
    19  windows, doors and opaque construction areas, comprising the
    20  gross area of one or more exterior building components, such as
    21  walls, floor or roof/ceiling.
    22     "Thermostat."  An instrument which measures changes in
    23  temperature and controls devices for maintaining a desired
    24  temperature.
    25     "Veiling reflections."  Regular reflections superimposed upon
    26  diffuse reflections from an object that partially or totally
    27  obscure the details to be seen by reducing the contrast. This
    28  sometimes is called "reflected glare."
    29     "Work plane."  The plane at which work usually is done and at
    30  which the illumination is specified and measured. Unless
    19770H0552B2905                 - 12 -

     1  otherwise indicated, this is assumed to be a horizontal plane 30
     2  in. (0.76 m) above the floor.
     3     "Zone."  A space or group of spaces within a building with
     4  heating or cooling requirements sufficiently similar so that
     5  comfort conditions can be maintained throughout by a single
     6  controlling device.
     7                           SUBCHAPTER C D                           <--
     8                         BUILDING ENVELOPE
     9  Section 205.  General provisions.
    10     (a)  Purpose of subchapter.--The intent of this subchapter is
    11  to provide minimum requirements for exterior envelope
    12  construction in the interest of energy conservation.
    13     In addition to the criteria set forth in this subchapter the
    14  proposed design may take into consideration the thermal mass of
    15  the building in considering energy conservation.
    16     (b)  Thermal performance.--All buildings and structures that
    17  are heated or mechanically cooled shall be constructed so as to
    18  provide the required thermal performance of the various
    19  components.
    20     The required thermal transmittance value (Uo) of any one
    21  component, such as roof/ceiling, wall or floor may be increased
    22  and the Uo value for other components decreased provided that
    23  the overall heat gain or loss for the entire building envelope
    24  does not exceed the total resulting from conformance to the
    25  required Uo values.
    26     (c)  Different requirements.--A building that is designed to
    27  be both heated and cooled shall meet the more stringent of the
    28  heating or cooling requirements of the exterior envelope as
    29  provided in this subchapter when requirements differ.
    30     (d)  Exterior walls.--For the purpose of this subchapter the
    19770H0552B2905                 - 13 -

     1  gross area of exterior walls consists of all opaque wall areas,
     2  including foundation walls above grade, peripheral edges of
     3  floors, window areas including sash, and door areas, where such
     4  surfaces are exposed to outdoor air and enclose a heated or
     5  mechanically cooled space.
     6     (e)  Roof assembly.--For the purpose of this subchapter a
     7  roof assembly shall be considered as all components of the
     8  roof/ceiling envelope through which heat flows, thereby creating
     9  a building transmission heat loss or gain, where such assembly
    10  is exposed to outdoor air and encloses a heated or mechanically
    11  cooled space.
    12     The gross area of a roof assembly consists of the total
    13  interior surface of such assembly, including skylights, exposed
    14  to the heated or mechanically cooled space.
    15     Where air ceiling plenums are employed, the roof or ceiling
    16  assembly shall:
    17         (1)  For thermal transmittance purposes not include the
    18     ceiling proper nor the plenum space as part of the assembly.
    19         (2)  For gross area purposes be based upon the interior
    20     face of the upper plenum surface.
    21  Section 206.  Criteria for residential buildings.
    22     (a)  Applicability.--The requirements herein shall apply to
    23  all buildings and structures or portions thereof of use groups
    24  R-1, R-2 and R-3 that are heated or mechanically cooled when not
    25  more than 3 stories or 40 feet in height.
    26     (b)  Walls.--The gross area of exterior walls above grade,
    27  including foundation walls, shall have a combined thermal
    28  transmittance value (Uo) not exceeding those specified in Table
    29  1.
    30                              Table 1
    19770H0552B2905                 - 14 -

     1                 Maximum Allowable "Uo" Values for
     2                   Gross Exterior Wall Assemblies
     3                                       Detached         All other
     4     Annual heating degree days*   one & two family    residential
     5                 4000                    0.25             0.31
     6                 5000                    0.23             0.29
     7                 6000                    0.22             0.27
     8                 7000                    0.20             0.26
     9     *As specified in Chapter 43 ASHRAE Handbook-Systems.
    10     (c)  Roof/ceiling.--The roof/ceiling assemblies shall have a
    11  combined thermal transmittance value (Uo) not to exceed 0.05
    12  except that roof/ceiling assemblies in which the finished
    13  interior surface is essentially the underside of the roof deck,
    14  such as a wooden cathedral ceiling, may have a "Uo" value not to
    15  exceed 0.08. These values presume no significant thermal
    16  transmission through framing members, skylights or other
    17  interruptions in the roof envelope. If such interruptions occur,
    18  calculations must be made showing conformance to the required
    19  "Uo" values.
    20     (d)  Floors over unheated spaces.--The floor of a heated or
    21  mechanically cooled space located over an unheated space shall
    22  have a combined thermal transmittance value (Uo) not to exceed
    23  0.08.
    24     (e)  Slab-on grade floors.--
    25         (1)  For slab-on grade floors, the perimeter of the floor
    26     shall be insulated with a material having a thermal
    27     resistance value (R) not less than those specified in Table
    28     2.
    29                              Table 2
    30             Minimum Allowable "R" Values of Perimeter
    19770H0552B2905                 - 15 -

     1                Insulation for Slab-On Grade Floors
     2     Annual heating degree days      Heated slab     Unheated slab
     3                 4000*                   5.5             3.5
     4                 5000                    6.3             4.2
     5                 6000                    7.0             4.9
     6                 7000                    7.8             5.5
     7     *Table values may be interpolated.
     8         (2)  The insulation shall extend downward from the top of
     9     the slab for a minimum distance of 24 inches or downward to
    10     the bottom of the slab then horizontally beneath the slab for
    11     a minimum total distance of 24 inches.
    12  Section 207.  Other buildings.
    13     (a)  Coverage.--The heating and cooling requirements herein
    14  shall govern all buildings and structures or portions thereof
    15  other than defined by section 206.
    16     (b)  Heating criteria for walls.--All buildings and
    17  structures that are heated shall have a combined thermal
    18  transmittance value (Uo) for the gross area of exterior walls
    19  not exceeding those specified in Table 3.
    20                              Table 3
    21                   Maximum Allowable "Uo" Values
    22                 for Gross Exterior Wall Assemblies
    23                                     3 stories or    More than
    24     Annual heating degree days     40 ft. or less  3 stories or
    25                                                       40 ft.
    26                 4000                    0.31            0.38
    27                 5000                    0.29            0.36
    28                 6000                    0.27            0.33
    29                 7000                    0.26            0.31
    30     (c)  Heating criteria for roof/ceiling.--All buildings and
    19770H0552B2905                 - 16 -

     1  structures that are heated shall have combined thermal
     2  transmittance value (Uo) for roof/ceiling assemblies not
     3  exceeding those specified in Table 4.
     4                              Table 4
     5                   Maximum Allowable "Uo" Values
     6                    for Roof/Ceiling Assemblies
     7     Annual heating degree days              Maximum Uo
     8             4000*                              0.092
     9             5000                               0.084
    10             6000                               0.076
    11             7000                               0.068
    12     *Table values may be interpolated.
    13     (d)  Heating criteria for floors over unheated spaces.--The
    14  floor of a heated space located over an unheated space shall
    15  have a thermal transmittance value (Uo) not exceeding 0.08.
    16     (e)  Heating criteria for slab-on grade floors.--For slab-on
    17  grade floors, the perimeter of the floor shall be insulated with
    18  a material having a thermal resistance value (R) not less than
    19  those specified in Table 5.
    20     The insulation shall extend downward from the top of the slab
    21  for a minimum distance of 24 inches or downward to the bottom of
    22  the slab then horizontally beneath the slab for a minimum total
    23  distance of 24 inches.
    24                              Table 5
    25             Minimum Allowable "R" Values of Perimeter
    26                Insulation for Slab-On Grade Floors
    27     Annual heating degree days      Heated slab    Unheated slab
    28                 4000*                   5.5             3.5
    29                 5000                    6.3             4.2
    30                 6000                    7.0             4.9
    19770H0552B2905                 - 17 -

     1                 7000                    7.8             5.5
     2     *Table values may be interpolated.
     3     (f)  Cooling criteria for walls.--All buildings and
     4  structures that are mechanically cooled shall have an overall
     5  thermal transfer value for the gross area of exterior walls not
     6  exceeding 33.5 BTU's per hour per square foot based on the
     7  following equation:
     8  OTTV = (Uw x Aw X TDEQ) + (Af x Sf x Sc) + (Uf x Af x Delta T)
     9                                     Ao
    10  OTTV = Overall thermal transfer value where:
    11    Uw = The thermal transmittance of all elements of the opaque
    12          wall area Btu/h. ft2.F (W/m2K)
    13    Aw = Opaque wall area, ft2 (m2)
    14    Uf = The thermal transmittance of the fenestration area
    15          Btu/h. ft2.F (W/m2K)
    16    Af = Fenestration area, ft2 (m2)
    17  TDEQ = Value given in the following table,F, (c):
    18                  TABLE FOR TEMPERATURE DIFFERENCE
    19     Wall Construction-mass per unit area        TDEQ
    20             LB/FT2          Kg/m2           F     C
    21             0-25            0-125           44  24.5
    22            26-40          126-195           37  21.0
    23            41-70          196-345           30  17.0
    24            71 and above   346 and above     23  13.0
    25     Weight of wall construction shall be determined from the
    26     1972 ASHRAE Handbook of Fundamentals, Chapter 22.
    27    Sc = Shading coefficient of the fenestration
    28  Delta T = Temperature difference between exterior and interior
    29         design conditions, F, for which the following
    30         temperatures shall apply:
    19770H0552B2905                 - 18 -

     1                             Indoor          Outdoor
     2                               F  C
     3             Winter           72  22.0       97 1/2%*
     4             Summer           78  25.5        2 1/2%*
     5     * Values from 1972 ASHRAE Handbook of
     6  Fundamentals, Chapter 33.
     7    SF = Solar factor value given Btu/h.ft2 (W/m2).
     8         (use 127 Btu/h.ft2)
     9    AO = Gross area of exterior walls, ft2 (m2).  The gross
    10         area of exterior walls consists of all opaque wall
    11         areas (including foundation walls, between floor span-
    12         drels, peripheral edges of floors, etc.), window
    13         areas (including sash), and door areas, where such
    14         surfaces are exposed to outdoor air and enclose a
    15         heated and/or mechanically cooled space (including
    16         intersticial areas between two such spaces).
    17  Note:  Where more than one type of wall and/or fenestration
    18         is used, the respective term or terms shall be expanded
    19         into sub-elements, as:
    20         (Uw x Aw x TDEQ) + (Uw2 x Aw2 x TDEQ2), etc.
    21     (g)  Cooling criteria for roof/ceilings.--All buildings and
    22  structures that are mechanically cooled shall have a combined
    23  thermal transmittance value (Uo) for roof/ceiling assemblies the
    24  same as specified in Table 4 for heating.
    25  Section 208.  Air leakage.
    26     (a)  Application.--The requirements of this section shall
    27  apply to all buildings and structures and apply only to those
    28  locations separating outdoor ambient conditions from interior
    29  spaces that are heated or mechanically cooled and are not
    30  applicable to separation of interior spaces from each other.
    19770H0552B2905                 - 19 -

     1     (b)  Standard.--Compliance with the criteria for air leakage
     2  shall be determined by ASTM E-283, Standard Method of Test for
     3  Rate of Air Leakage through Exterior Windows, Curtain Walls and
     4  Doors, at a pressure differential of 1.567 lb/ft2 which is
     5  equivalent to the effect of a 25 m.p.h. wind.
     6     (c)  Acceptance criteria.--The following criteria shall
     7  represent the maximum allowable air leakage:
     8         (1)  The air infiltration rate for windows shall not
     9     exceed 0.5 cfm per foot of sash crack.
    10         (2)  The air infiltration rate for sliding glass doors in
    11     residential buildings shall not exceed 0.5 cfm per square
    12     foot of door area.
    13         (3)  The air infiltration rate for swinging doors in
    14     residential buildings shall not exceed 1.25 cfm per square
    15     foot of door area.
    16         (4)  The air infiltration rate for swinging, revolving or
    17     sliding doors in other than residential buildings shall not
    18     exceed 11 cfm per lineal foot of door crack.
    19     (d)  Caulking and sealants.--Exterior joints around windows
    20  and door frames, between wall cavities and window or door
    21  frames, between wall and foundation, between wall and roof,
    22  between wall panels, at penetrations or utility services through
    23  walls, floors and roofs, and all other openings in the exterior
    24  envelope shall be caulked, gasketed, weatherstripped, or
    25  otherwise sealed.
    26                           SUBCHAPTER D E                           <--
    27         WARM AIR HEATING, VENTILATING AND AIR CONDITIONING
    28                       SYSTEMS AND EQUIPMENT
    29  Section 209.  General provisions.
    30     This subchapter applies to air duct systems employing
    19770H0552B2905                 - 20 -

     1  mechanical means for the movement of air used for warm air
     2  heating, ventilating, air conditioning systems, exhaust systems
     3  and combination heating and air conditioning systems, except
     4  that this subchapter shall not apply to systems for the removal
     5  of flammable vapors or residues or to systems for conveying
     6  dust, stock or refuse by means of air currents. Heating,
     7  ventilating and air conditioning systems of all buildings and
     8  structures or portions thereof shall be designed and installed
     9  for efficient use of energy as herein provided. For special
    10  applications such as hospitals, laboratories, thermally
    11  sensitive equipment, computer rooms, and manufacturing
    12  processes, the design concepts and parameters shall conform to
    13  the requirements of the application at minimum energy levels.
    14  Section 210.  Design requirements.
    15     In determining design conditions for calculations under this
    16  section the following design temperatures shall apply:
    17         (1)  Outdoor design temperature shall be selected for
    18     listed locations in Chapter 33 of the ASHRAE Handbook of
    19     Fundamentals, from columns of 97 1/2% values for heating and
    20     2 1/2% values for cooling.
    21         (2)  Indoor design temperature shall be 70 degrees F. for
    22     heating and 78 degrees F. for cooling.
    23         (3)  Indoor design relative humidity for heating shall
    24     not exceed 30%. For cooling, the actual design relative
    25     humidity within the comfort envelope as defined in ASHRAE
    26     Standard 55-74 "Thermal Environmental Conditions for Human
    27     Occupancy" shall be selected for the minimum total heating,
    28     ventilating, and air conditioning system energy use.
    29  Section 211.  Cooling with outdoor air.
    30     (a)  Fan system design.--Each fan system shall be designed to
    19770H0552B2905                 - 21 -

     1  use up to and including 100% of the fan system capacity for
     2  cooling with outdoor air automatically whenever its use will
     3  result in lower usage of energy than would be required under its
     4  normal operation.
     5     (b)  Exceptions.--Cooling with outdoor air is not required
     6  under any one or more of the following conditions:
     7         (1)  Fan system capacity less than 5,000 Cfm or 134,000
     8     Btu/Hr total cooling capacity.
     9         (2)  The quality of the outdoor air is so poor as to
    10     require extensive treatment of the air.
    11         (3)  The need for humidification or dehumidification
    12     requires the use of more energy than is conserved by outdoor
    13     air cooling.
    14         (4)  The use of outdoor air cooling may affect the
    15     operation of other systems (such as return or exhaust air
    16     fans or supermarket refrigeration) so as to increase the
    17     overall energy consumption of the building.
    18         (5)  Internal/external zone heat recovery or other energy
    19     recovery is used.
    20         (6)  When all space cooling is accomplished by a
    21     circulating liquid which transfers space heat directly or
    22     indirectly to a heat rejection device such as a cooling tower
    23     without the use of a refrigeration system.
    24  Section 212.  Mechanical ventilation.
    25     Each mechanical ventilation system shall be equipped with a
    26  readily accessible means for either shut-off or volume reduction
    27  and shut-off when ventilation is not required.
    28  Section 213.  Simultaneous heating and cooling.
    29     Systems that employ both heating and cooling simultaneously
    30  in order to achieve comfort conditions within a space shall be
    19770H0552B2905                 - 22 -

     1  limited to those situations where more efficient methods of
     2  heating and air conditioning cannot be effectively utilized to
     3  meet system objectives. Simultaneous heating and cooling by
     4  reheating or recooling supply air or by concurrent operation or
     5  independent heating and cooling systems serving a common zone
     6  shall be restricted as specified herein.
     7  Section 214.  Recovered energy.
     8     Recovered energy, provided the new energy expended in the
     9  recovery process is less than the amount recovered, may be used
    10  for control of temperature and humidity. New energy is defined
    11  as energy, other than recovered, utilized for the purpose of
    12  heating or cooling.
    13  Section 215.  New energy.
    14     (a)  Prevention of excess humidity.--New energy may be used,
    15  when necessary, to prevent relative humidity from rising above
    16  60% for comfort control or to prevent condensation on terminal
    17  units or outlets.
    18     (b)  Control of temperature.--New energy may be used for
    19  control of temperature if minimized as specified in sections 216
    20  through 220.
    21  Section 216.  Reheat systems.
    22     Systems employing reheat and serving multiple zones, other
    23  than those employing variable air volume for temperature
    24  control, shall be provided with control that will automatically
    25  reset the system cold air supply to the highest temperature
    26  level that will satisfy the zone requiring the coolest air.
    27  Single zone reheat systems shall be controlled to sequence
    28  reheat and cooling.
    29  Section 217.  Dual duct and multizone systems.
    30     These systems shall be provided with control that will
    19770H0552B2905                 - 23 -

     1  automatically reset the cold deck air supply to the highest
     2  temperature that will satisfy the zone requiring the coolest air
     3  and the hot deck air supply to the lowest temperature that will
     4  satisfy the zone requiring the warmest air.
     5  Section 218.  Recooling systems.
     6     Systems in which heated air is recooled directly or
     7  indirectly, to maintain space temperature, shall be provided
     8  with control that will automatically reset the temperature to
     9  which the supply air is heated to the lowest level that will
    10  satisfy the zone requiring the warmest air.
    11  Section 219.  Multiple zones.
    12     For systems with multiple zones, one or more zones may be
    13  chosen to represent a number of zones with similar heating or
    14  cooling characteristics. A multiple zone heating, ventilating
    15  and air conditioning system that employs reheating or recooling
    16  for control of not more than 5,000 Cfm or 20% of the total
    17  supply air of the system, whichever is less, shall be exempt
    18  from the supply air temperature reset requirements of sections
    19  216 through 218.
    20  Section 220.  Concurrent operation.
    21     Concurrent operation of independent heating and cooling
    22  systems serving common spaces, and requiring the use of new
    23  energy for heating or cooling shall be minimized by one or both
    24  of the following:
    25         (1)  By providing sequential temperature control of both
    26     heating and cooling capacity in each zone.
    27         (2)  By limiting the heating energy input, through
    28     automatic reset control of the heating medium temperature (or
    29     energy input rate), to only that necessary to offset heat
    30     loss due to transmission and infiltration and, where
    19770H0552B2905                 - 24 -

     1     applicable, to heat the ventilation air supply to the space.
     2  Section 221.  Equipment performance requirements.
     3     (a)  Application.--The requirements of this section apply to
     4  equipment and component performance for heating, ventilating and
     5  air conditioning systems. Where equipment efficiency levels are
     6  specified, data furnished by the equipment supplier or certified
     7  under a nationally recognized certification program or rating
     8  procedure shall be used to satisfy these requirements.
     9     (b)  Systems equipment - electrical.--Heating ventilating and
    10  air conditioning systems equipment whose energy input in the
    11  cooling mode is entirely electric shall show a coefficient of
    12  performance (COP) and energy efficiency ratio (EER) not less
    13  than the values specified in Table 6. These requirements apply
    14  to, but are not limited to, unitary cooling equipment (air and
    15  water source); packaged air conditioners; and room air
    16  conditioners. These requirements do not apply to equipment used
    17  in areas having open refrigerated food display cases. For
    18  determining coefficient of performance (COP), the rate of net
    19  heat removal shall be defined as the change in the total heat
    20  contents of the air entering and leaving the equipment (without
    21  reheat). Total energy input shall be determined by combining the
    22  energy inputs to all elements of the equipment, including but
    23  not limited to, compressors, pumps, supply-air fans, cooling
    24  tower fans and the system equipment control circuit.
    25                              Table 6
    26       Minimum EER and COP for Electric Heating, Ventilating
    27               and Air Conditioning System Equipment
    28  Standard rating capacity                       EER     COP
    29  Under 65,000 Btu/hr (19,050 watts)             6.1     1.8
    30  65,000 Btu/hr (19,050 watts) and over          6.8     2.0
    19770H0552B2905                 - 25 -

     1     (c)  Other system equipment.--Heat operated cooling equipment
     2  shall show a coefficient of performance (COP) in the cooling
     3  mode not less than the values specified in Table 7. These
     4  requirements apply to, but are not limited to, absorption,
     5  engine-driven and turbine-driven equipment. The coefficient of
     6  performance (COP) is determined excluding the electrical
     7  auxiliary inputs.
     8                              Table 7
     9     Minimum COP for Heating, Ventilating and Air Conditioning
    10               System Heat Operated Cooling Equipment
    11         Heat source                             Minimum COP
    12  Direct fired (gas, oil)                            0.40
    13  Indirect fired (steam, hot water)                  0.65
    14     (d)  System components.--Heating, ventilating and air
    15  conditioning system components whose energy input in the cooling
    16  mode is entirely electric shall show a coefficient of
    17  performance (COP) and energy efficiency ratio (EER) not less
    18  than the values specified in Table 8. For determining
    19  coefficient of performance (COP), the rate of heat removal is
    20  defined as the difference in total heat contents of the water or
    21  refrigerant entering or leaving the component. Total energy
    22  input shall be determined by combining the energy inputs to all
    23  elements and accessories of the component, including but not
    24  limited to, compressors, internal circulating pumps, condenser-
    25  air fans, evaporative-condenser cooling heater pumps, purge, and
    26  the component control circuit.
    27                              Table 8
    28      Minimum COP for Electrically Driven Heating, Ventilating
    29               and Air Conditioning System Components
    30     Component    Condensing means   Air     Water     Evaporation
    19770H0552B2905                 - 26 -

     1                                   ERR COP  EER COP     EER COP
     2  Self-contained    Centrifugal    7.5 2.2  12.9 3.8
     3  water chillers
     4                     Positive
     5                   displacement    7.2 2.1  10.9 3.2
     6  Condenserless      Positive
     7  water chillers   displacement    8.9 2.6  10.9 3.2
     8  Compressor and
     9  condenser units    Positive
    10  65,000 Btu/hr.   displacement    7.8 2.3  11.3 3.3   11.3 3.3
    11  (19,050 watts)
    12  and over
    13     (e)  Heat pumps.--Heat pumps whose energy input is entirely
    14  electric shall show a coefficient of performance (COP), heating,
    15  not less than the values specified in Table 9.
    16                              Table 9
    17              Minimum COP for Heat Pumps, Heating Mode
    18  Source and outdoor temperature (degree F.)         Minimum COP
    19  Air source--47 DB/43 WB                               2.2
    20  Air source--17 DB/15 WB                               1.2
    21  Water source--60 entering                             2.2
    22     (f)  Supplementary heater.--The heat pump shall be installed
    23  with a control to prevent supplementary heater operation when
    24  the heating load can be met by the heat pump alone.
    25  Supplementary heater operation is permitted during transient
    26  periods, such as start-ups, following room thermostat setpoint
    27  advance, and during defrost. A two-stage room thermostat, which
    28  controls the supplementary heat on its second stage, shall be
    29  accepted as meeting this requirement. The cut-on temperature for
    30  the compression heating shall be higher than the cut-on
    19770H0552B2905                 - 27 -

     1  temperature for the supplementary heat, and the cut-off
     2  temperature for the compression heating shall be higher than the
     3  cut-off temperature for the supplementary heat. Supplementary
     4  heat may be derived from any source of electric resistance
     5  heating or combustion heating.
     6     (g)  Combustion heating equipment.--All gas and oilfired
     7  comfort heating equipment shall show a minimum combustion
     8  efficiency of 75% at maximum rated output. Combustion efficiency
     9  shall be determined in accordance with the ASHRAE Standard 90.
    10  Section 222.  Duct insulation.
    11     (a)  Insulation.--All duct systems, or portions thereof,
    12  exposed to nonconditioned spaces shall be insulated to provide a
    13  thermal resistance, excluding film resistance, of
    14             ti - to
    15         R = --------(hr) (sq.ft) (F)/BTU
    16               15
    17  where ti-to is the design temperature differential (absolute
    18  value) between the air in the duct and the surrounding air with
    19  the following exceptions. Duct insulation, except when needed to
    20  prevent condensation, is not required in any of the following
    21  cases:
    22         (1)  Where ti-to is 25 degrees F. or less.
    23         (2)  When the heat gain or loss of the ducts, without
    24     insulation, will not increase the energy requirements of the
    25     building.
    26         (3)  Exhaust air ducts.
    27         (4)  Supply or return air ducts installed in crawl spaces
    28     with insulated walls, basements or cellars in one and two-
    29     family dwellings.
    30     (b)  Vapor barriers.--Where required to prevent condensation,
    19770H0552B2905                 - 28 -

     1  insulation with vapor barriers shall be installed in addition to
     2  insulation required above.
     3  Section 223.  System controls.
     4     (a)  Application.--All heating, ventilating and air
     5  conditioning systems shall be provided controls as specified
     6  herein.
     7     (b)  Temperature.--Each heating, ventilating and air
     8  conditioning system shall be provided with at least one
     9  thermostat for the regulation of temperature. Each thermostat
    10  shall be capable of being set from 55 degrees F. to 75 degrees
    11  F. where used to control heating only and from 70 degrees F. to
    12  85 degrees F. where used to control cooling only. Where used to
    13  control both heating and cooling it shall be capable of being
    14  set from 55 degrees F. to 85 degrees F. and shall be capable of
    15  operating the system heating and cooling in sequence. It shall
    16  be adjustable to provide a temperature range of up to 10 degrees
    17  F. between full heating and full cooling, except as allowed in
    18  section 220.
    19     (c)  Humidity.--If a heating, ventilating and air
    20  conditioning system is equipped with a means for adding moisture
    21  to maintain specific selected relative humidities in spaces or
    22  zones, a humidistat shall be provided. This device shall be
    23  capable of being set to prevent new energy from being used to
    24  produce space relative humidity above 30% R.H.  Where a
    25  humidistat is used in a heating, ventilating and air
    26  conditioning system for controlling moisture removal to maintain
    27  specific selected relative humidities in spaces or zones, it
    28  shall be capable of being set to prevent new energy from being
    29  used to produce a space relative humidity below 60%.
    30     (d)  Temperature zoning.--
    19770H0552B2905                 - 29 -

     1         (1)  In all buildings and structures of use group R-3, at
     2     least one thermostat for regulation of space temperature
     3     shall be provided for each separate heating, ventilating and
     4     air conditioning system. In addition, a readily accessible
     5     manual or automatic means shall be provided to partially
     6     restrict or shut-off the heating or cooling input to each
     7     zone or floor, excluding unheated or uncooled basements and
     8     garages.
     9         (2)  In all buildings and structures of use group R-2,
    10     each individual dwelling unit shall be considered separately
    11     and shall meet the requirements for one and two-family
    12     dwellings above.
    13         (3)  In all buildings and structures other than use group
    14     R-3 and in spaces other than dwelling units in use group R-2,
    15     at least one thermostat for regulation of space temperature
    16     shall be provided for each separate heating, ventilating and
    17     air conditioning system and for each floor of the building.
    18     (e)  Set-back and shut-off.--
    19         (1)  In all buildings and structures, or portions thereof
    20     of use group R-3, the thermostat, or an alternate means such
    21     as a switch or a clock, shall provide a readily accessible,
    22     manual or automatic means for reducing the energy required
    23     for heating and cooling during periods of nonuse or reduced
    24     need.
    25         (2)  In all other buildings and structures, or portions
    26     thereof each heating, ventilating and air conditioning system
    27     shall be equipped with a readily accessible means of reducing
    28     the energy used for heating, ventilating and air conditioning
    29     during periods of nonuse or alternate uses of the building
    30     spaces or zones served by the system, such as with manually
    19770H0552B2905                 - 30 -

     1     adjustable automatic timing devices, manual devices for use
     2     by operating personnel, or automatic control systems.
     3         (3)  Lowering thermostat set points to reduce energy
     4     consumption of heating systems shall not cause energy to be
     5     expended to reach the reduced setting.
     6  Section 224.  Steam and hot water heating piping.
     7     (a)  Piping insulation.--All piping serving as part of a
     8  heating or cooling system installed to serve buildings and
     9  within buildings shall be thermally insulated as shown in Table
    10  10.
    11                              Table 10
    12                      Minimum Pipe Insulation
    13                                 Insulation thickness in inches
    14             Fluid                       for pipe sizes
    15  Piping  temperature
    16  system     range,   Runouts  1" and  1 1/4-  2 1/2-  5&   8" and
    17  types        F.     up to 2"  less     2       4     6    larger
    18  Heating systems
    19     Steam &
    20     hot water
    21  High pressure/
    22  temp       306-450   1 1/2     1 1/2    2    2 1/2  3 1/2  3 1/2
    23  Med. pressure/
    24  temp       251-305   1 1/2     1 1/2    2    2 1/2  3      3
    25  Low pressure/
    26  temp       201-250   1         1       1 1/2 1 1/2  2      2
    27  Low tem-
    28  perature   120-200    1/2       3/4     1    1      1      1 1/2
    29  Steam con-
    30  densate      Any     1         1        1    1 1/2  1 1/2  2
    19770H0552B2905                 - 31 -

     1  (for feed
     2  water)
     3  Cooling systems
     4  Chilled
     5  water,      40-55     1/2       1/2      3/4 1      1      1
     6  Refrigerant,
     7  or brine  Below 40   1         1       1 1/2  1 1/2 1 1/2  1 1/2
     8  Insulation thicknesses are based on insulation having thermal
     9  resistances in the range of 4.0 to 4.6 per inch of thickness on
    10  a flat surface at a mean temperature of 75 degrees F. Minimum
    11  insulation thickness shall be increased for materials having R
    12  values less than 4.0 or may be reduced for materials having R
    13  values greater than 4.6 per inch of thickness as follows:
    14     (b)  High thermal resistance.--For materials with thermal
    15  resistance greater than R=4.6, the minimum insulation thickness
    16  may be reduced as follows:
    17         4.6 x Table 10 Thickness    =   New Minimum Thickness
    18               Actual R
    19     (c)  Low thermal resistance.--For materials with thermal
    20  resistance less than R=4.0 the minimum insulation thickness
    21  shall be increased as follows:
    22         4.0 x Table 10 Thickness    =   New Minimum Thickness
    23               Actual R
    24  Piping insulation, except when needed to prevent condensation,
    25  is not required in any of the following cases:
    26         (1)  Piping installed within heating, ventilating and air
    27     conditioning equipment.
    28         (2)  Piping at temperatures between 55 degrees F. and 120
    29     degrees F.
    30         (3)  When the heat loss or heat gain of the piping,
    19770H0552B2905                 - 32 -

     1     without insulation, does not increase the energy requirements
     2     of the building.
     3         (4)  Piping installed in basements or cellars in one and
     4     two-family dwellings.
     5     (d)  Vapor barriers.--Where required to prevent condensation,
     6  insulation with vapor barriers shall be installed in addition to
     7  insulation required above.
     8                           SUBCHAPTER E F                           <--
     9                          PLUMBING SYSTEMS
    10  Section 225.  Purpose.
    11     This subchapter sets forth provisions for design and
    12  equipment selection for energy conservation in service water
    13  heating systems.
    14  Section 226.  Fixtures.
    15     (a)  Lavatories.--Lavatories in restrooms of public
    16  facilities shall be equipped with self-closing outlet devices
    17  which limit the flow of hot water to a maximum of 0.5 Gpm,
    18  devices which limit the outlet temperature to a maximum of 110
    19  degrees F. and selfclosing valves which limit the quantity of
    20  hot water to a maximum of 0.25 gallons.
    21     (b)  Showers.--Showers used for other than safety reasons
    22  shall be equipped with flow control devices to limit total flow
    23  to a maximum of 3 Gpm per shower head.
    24  Section 227.  Insulation.
    25     (a)  Piping insulation.--Piping in required return
    26  circulation systems shall be insulated so that heat loss is
    27  limited to a maximum of 25 Btuh per square foot of external pipe
    28  surface for above ground piping and a maximum of 35 Btuh per
    29  square foot of external pipe surface for underground piping.
    30  Maximum heat loss shall be determined at a temperature
    19770H0552B2905                 - 33 -

     1  differential equal to the maximum water temperature minus a
     2  design ambient temperature no higher than 65 degrees F. except
     3  that conformance with table 10 for "low temperature piping
     4  system" shall be deemed as complying with this section.
     5     (b)  Tanks.--Unfired hot water storage tanks shall be
     6  insulated so that heat loss is limited to a maximum of 15 Btuh
     7  per square foot of external tank surface area. For purposes of
     8  determining this heat loss, the design ambient temperature shall
     9  be no higher than 65 degrees F.
    10  Section 228.  Equipment.
    11     (a)  Pump operation.--Circulating hot water systems shall be
    12  arranged so that the circulating pump can be conveniently turned
    13  off either automatically or manually when the hot water system
    14  is not in operation.
    15     (b)  Electric water heaters.--All automatic electric storage
    16  water heaters shall have a stand-by loss not exceeding 4 watts
    17  per square foot of tank surface area. The method of test of
    18  stand-by loss shall be as described in section 4.3.1 of ANSI
    19  C72.1 Household Automatic Electrical Storage-Type Water Heaters.
    20     (c)  Gas and oil-fired water heaters.--All gas and oil-fired
    21  automatic storage heaters shall have a recovery efficiency, ER,
    22  not less than 75% and a stand-by loss percentage S, not
    23  exceeding S=2.3+67/V where V=rated volume in gallons. The method
    24  of test of ER and S shall be as described in section 2.7 of ANSI
    25  Z21.10.3 Circulating Tank, Instantaneous and Large Automatic
    26  Storage Type Water Heaters, Approval Requirements for Gas Water
    27  Heaters.
    28  Section 229.  Controls.
    29     (a)  Temperature controls.--All hot water supply systems
    30  shall be equipped with automatic temperature controls capable of
    19770H0552B2905                 - 34 -

     1  adjustments from the lowest to the highest acceptable
     2  temperature settings for the intended use.
     3     (b)  Shut down.--A separate switch shall be provided to
     4  terminate the energy supplied to electric hot water supply
     5  systems. A separate valve shall be provided to turn off the
     6  energy supplied to the main burner of all other types of hot
     7  water supply systems.
     8                           SUBCHAPTER F G                           <--
     9                         ELECTRICAL SYSTEMS
    10  Section 230.  System requirements.
    11     (a)  Power factor.--The power factor of the overall
    12  electrical distribution system in a building shall be not less
    13  than 90% under rated design installed load of the building,
    14  either by utilization equipment design or by the use of power
    15  factor corrective devices. The power factor corrective devices
    16  may be installed on individual equipment, rated greater than
    17  1,000 watts and switched therewith, regionally grouped, located
    18  at the service equipment or power factor correction achieved by
    19  other equivalent means. The choice among these corrective
    20  methods should be made based upon an engineering evaluation of
    21  each distribution system.
    22     (b)  Service voltage.--Where a choice of service voltage is
    23  available, the voltage resulting in the least energy loss shall
    24  be used.
    25     (c)  Voltage drop.--In any building, the maximum total
    26  voltage drop shall not exceed 3% in branch circuits or feeders,
    27  for a total of 5% to the farthest outlet based on steady state
    28  design load conditions.
    29     (d)  Lighting switching.--Switching shall be provided for
    30  each lighting circuit, or for portions of each circuit, so that
    19770H0552B2905                 - 35 -

     1  the partial lighting required for custodial or for effective
     2  complementary use with natural lighting may be operated
     3  selectively.
     4     (e)  Separate metering.--In all multi-family dwellings
     5  provisions shall be made to determine the electrical energy
     6  consumed by each tenant.
     7                           SUBCHAPTER G H                           <--
     8                              LIGHTING
     9  Section 231.  Light power budget.
    10     A lighting power budget is the upper limit of the power to be
    11  available to provide the lighting needs in accordance with a
    12  given set of criteria and given calculation procedure.
    13  Section 232.  Calculation methods.
    14     The criteria specified below shall be utilized for
    15  computation of the lighting power budget. All calculations shall
    16  be in accordance with accepted engineering practice. When
    17  insufficient information is known about the specific use of the
    18  building space (e.g., number of occupants, space function,
    19  location of partitions), the budget shall be based on the
    20  apparent intended use of the building space.
    21  Section 233.  Building interiors.
    22     (a)  Procedure.--The allowable electric power for lighting
    23  shall be established by using the criteria and the calculation
    24  procedures specified in section 236. The value shall be based on
    25  the use for which the space within the building is intended and
    26  on efficient energy utilization.
    27     (b)  Illumination level criteria.--For the purpose of
    28  establishing a budget, levels of illumination shall be those
    29  listed in fig. 9-80 of the IES Lighting Handbook, and those
    30  levels shall be used as follows:
    19770H0552B2905                 - 36 -

     1         (1)  For task lighting, the levels of illumination listed
     2     are for specific tasks. These levels are for the task areas
     3     defined in the IES Lighting Handbook or, where not defined,
     4     at all usable portions of task surfaces. In some cases, the
     5     levels of illumination are listed for locations (e.g.,
     6     auditoriums). These levels are to be considered as average
     7     levels.
     8         (2)  For general lighting, in areas surrounding task
     9     locations, the average level of general lighting, for budget
    10     purposes only, shall be one-third the level for the tasks
    11     performed in the area but in no case less than 20-foot
    12     candles. Where more than one task level occurs in a space,
    13     the general level shall be one-third the weighted average of
    14     the specific task levels.
    15         (3)  For noncritical lighting, in circulation and seating
    16     areas, where no specific visual tasks occur, the average
    17     level of illumination shall be one-third of the average
    18     general lighting in the adjacent task spaces but in no case
    19     less than ten-foot candles.
    20         (4)  For the purpose of establishing a power budget, only
    21     lamp efficacies and coefficients of utilization (CU)
    22     specified in Table 11, shall be assumed.
    23  Section 234.  Building exteriors.
    24     (a)  Basis on use.--In exterior spaces, the lighting power
    25  budget shall be based on the use of which the space is intended
    26  (for task performance, safety, or security) and on efficient
    27  energy utilization.
    28     (b)  Criteria.--The same criteria as those for interior
    29  spaces apply for illumination levels and lighting systems with
    30  the addition of luminaires for flood lighting. For power budget
    19770H0552B2905                 - 37 -

     1  purposes floodlighting shall be selected with luminaires having
     2  a greater percentage of their beam lumens restricted to the area
     3  to be lighted. Such luminaires are defined as those with at
     4  least the minimum efficiencies listed in the IES Lighting
     5  Handbook.
     6     (c)  Facade lighting.--Facade lighting for budget purposes
     7  shall be no greater than 2% of the total interior load of the
     8  building.
     9     (d)  Calculation procedure.--In establishing a lighting power
    10  budget the following procedures shall be used:
    11         (1)  For overhead lighting the procedure specified in
    12     section 236 shall be followed, but using reflectances as
    13     found.
    14         (2)  For flood lighting the beam lumen method, as shows    <--
    15     SHOWN in the IES Lighting Handbook and a coefficient of beam   <--
    16     utilization (CBU) of 0.75 shall be used for floodlighting
    17     calculations.
    18  Section 235.  Exceptions to criteria.
    19     (a)  Interiors.--The criteria of section 233 shall not apply
    20  to the following areas when calculating the load:
    21         (1)  Portions of residential occupancies except for
    22     kitchens, bathrooms, and laundry areas and public spaces
    23     including lobbies, halls, stairways, basement areas, and
    24     utility rooms.
    25         (2)  Residential type spaces similar to those stated in
    26     paragraph (1) in institutions, such as hospitals, hotels,
    27     funeral homes, churches, museums, etc.
    28         (3)  Theater auditoriums, entertainment and audiovisual
    29     presentations where the lighting is an essential technical
    30     element for the function performed.
    19770H0552B2905                 - 38 -

     1     (b)  Exteriors.--The criteria of section 234 shall not apply
     2  to the following lamps and luminaries; however, their use shall
     3  be accounted for in the calculation of task lighting loads for
     4  specific tasks. The allowable load shall be based on the
     5  luminary wattage to achieve the levels of illumination as
     6  covered in section 233 using a point calculation method given in
     7  the IES Lighting Handbook. The excepted lamps and luminaires are
     8  as follows:
     9         (1)  Luminaires for medical and dental purposes.
    10         (2)  Luminaires for highlighting applications, such as
    11     sculpture exhibits, art exhibits, and individual items of
    12     display merchandise.
    13         (3)  Luminaires for specialized lighting applications
    14     (color matching, where electrical interference cannot be
    15     tolerated, etc.).
    16     (c)  Control of reflectances.--The criteria of Table 11 shall
    17  not apply in spaces where it is impractical to control
    18  reflectances and where a dirty atmosphere cannot be avoided.
    19  Where this condition exists, the values for reflectances and
    20  light loss factors shall be those expected to be found and shall
    21  be approved by the department. The calculation shall make a note
    22  of this deviation.
    23  Section 236.  Calculation procedure.
    24     (a)  Illumination levels and areas.--To establish
    25  illumination levels and areas, the following procedure shall be
    26  used:
    27         (1)  Determine the visual tasks that are expected to be
    28     performed in each space and the number of planned work
    29     locations where tasks will be performed. If assumptions are
    30     made, their bases shall be indicated.
    19770H0552B2905                 - 39 -

     1         (2)  Select the illumination level, in foot-candles for
     2     those expected tasks in accordance with section 233(b)(1).
     3         (3)  Calculate total task areas to be illuminated to the
     4     same level by multiplying the number of work locations by 50
     5     square feet per work location. (Total task areas shall not
     6     exceed actual total space area). If actual task area is
     7     greater than 50 square feet the actual area shall be used. If
     8     special task lighting or localized lighting is to be
     9     employed, use the actual task areas and point calculation
    10     procedures.
    11         (4)  Calculate the level of general lighting by
    12     multiplying the task lighting level by one-third, where there
    13     is only one task level, or by taking one-third of the sum of
    14     the products of the task levels as provided for in paragraph
    15     (2) and their areas as provided for in paragraph (3) divided
    16     by the total task areas.
    17         (5)  Calculate the level of noncritical lighting.
    18     (b)  Lighting system data.--To establish lighting system
    19  data, the following shall be used:
    20         (1)  Light source and luminaire types to use.
    21         (2)  Lamp lumens per watt and luminaire coefficients of
    22     utilization for room and luminaire mounting height
    23     dimensions. Luminaire CUs shall be selected from the IES
    24     Lighting Handbook. In all cases, no luminaire shall have a CU
    25     for RCR = 1 of less than that given in Table 11 lamp
    26     efficacies for the appropriate space.
    27     (c)  Allowable wattage.--To establish allowable wattage, the
    28  following shall be used:
    29         (1)  Using data from subsection (b), the illumination
    30     levels and areas determined in subsection (a), and the
    19770H0552B2905                 - 40 -

     1     criteria of Table 11 on Reflectance, calculate the allowable
     2     wattages using the lumen method.
     3         (2)  Calculate the total space wattage by adding the
     4     task, general and noncritical lighting loads.
     5         (3)  Add the wattage of luminaires allowed in section
     6     235(b).
     7                              Table 11
     8     (a)  Lamp efficacies.--The following are initial lumen output
     9  per watt input, including ballast losses:
    10                 Application                             Lumens
    11                                                        per Watt
    12     Where moderate color rendition is appropriate         55
    13     Where good color rendition is appropriate             40
    14     Where high color rendition is appropriate,
    15     spaces are less than 50 square feet or where
    16     use of low wattage High Intensity Discharge
    17     (HID) lamps under 250 W or fluorescent
    18     lamps under 40 W is appropriate                       25
    19     (b)  Luminary coefficients of utilization (CU).--Coefficients
    20  of utilization (CUs) are to be for luminaires for use in the
    21  types of spaces listed below, and those luminaires shall have a
    22  CU of no less than that listed below (for each type space) for a
    23  Room Cavity Ratio (RCR) of 1 and reflectances as in (c).
    24                 Space Use                           Minimum CU
    25                                                    (at RCR = 1)
    26     For spaces with tasks subjected to veiling
    27     reflections where design levels of
    28     illumination are listed in terms of
    29     equivalent sphere illumination (ESI) and
    30     where visual comfort is important.                  0.55
    19770H0552B2905                 - 41 -

     1     For spaces without tasks, or with tasks
     2     not subjected to veiling reflections, but
     3     where visual comfort is important.                  0.63
     4     For spaces without tasks and where visual
     5     comfort is not a criterion                          0.70
     6     (c)  Other criteria; reflectances.--For interior spaces, the
     7  following initial cavity and surface reflectances shall be
     8  assumed:
     9     Ceiling cavity reflectance              80%
    10     Wall reflectance                        50%
    11     Floor cavity reflectance                20%
    12  Light Loss Factor.  A light loss factor (LLF) of 0.70 shall be
    13  used.
    14                           SUBCHAPTER H I                           <--
    15                        ALTERNATIVE SYSTEMS
    16  Section 237.  Performance alternative.
    17     Alternative building systems and equipment design may be
    18  approved by the department when they can be shown to have energy
    19  consumption not greater than that of a similar building with
    20  similar forms of energy requirements, designed in accordance
    21  with the provisions of this act or when they can be shown to
    22  have energy consumption not greater than that which shall be
    23  established by the department with the approval of the Building
    24  Energy Conservation Committee, for the purposes of this section:  <--
    25  PROVIDED, HOWEVER, THAT FOR ALL BUILDINGS CLASSIFIED AS USE
    26  GROUP R-3 ALTERNATE BUILDING SYSTEMS AND EQUIPMENT DESIGN WHICH
    27  SATISFY THE CRITERIA OF THIS SECTION SHALL NOT REQUIRE THE
    28  APPROVAL OF THE DEPARTMENT BUT THE USE OF SUCH AN ALTERNATE
    29  BUILDING SYSTEM OR EQUIPMENT DESIGN SHALL BE INDICATED IN THE
    30  WARRANTY PROVIDED IN SECTION 306.
    19770H0552B2905                 - 42 -

     1  Section 238.  Nondepletable sources.
     2     When such alternative systems utilize solar, geothermal, wind
     3  or other nondepletable energy sources for all or part of their
     4  energy sources, such nondepletable energy supplied to the
     5  building shall be excluded from the total energy chargeable to
     6  the proposed alternative design.
     7  Section 239.  Documentation.
     8     Proposed alternative designs, submitted TO THE DEPARTMENT as   <--
     9  requests for exception to the standard design criteria, must be
    10  accompanied by an energy analysis prepared in accordance with
    11  the ASHRAE Standard 90-75.
    12                             CHAPTER 3
    13              APPLICATION OF STANDARDS: ESTABLISHMENT
    14                     OF COMMITTEE AND PENALTIES
    15  Section 301.  Modification of standards; criteria.
    16     The department, with the approval of the Building Energy
    17  Conservation Committee established pursuant to section 304,
    18  after one or more public hearings, may recommend to the General
    19  Assembly modifications to the energy conservation standards
    20  contained in Chapter 2 hereof. Any recommended modification to
    21  the energy conservation standards shall meet the following
    22  criteria:
    23         (1)  It shall be consistent with the latest and most
    24     effective technology.
    25         (2)  It shall not be in conflict with existing safeguards
    26     for public health and safety.
    27         (3)  It shall be economically feasible as determined by
    28     life-cycle-cost procedures.
    29         (4)  It shall be sufficiently stringent to effect a
    30     significant savings of energy resources.
    19770H0552B2905                 - 43 -

     1         (5)  It shall be a performance standard for the design of
     2     buildings and systems within buildings to assure maximum
     3     practical conservation of energy.
     4         (6)  Consideration shall be given to building and energy
     5     standards promulgated by national and other state
     6     governmental agencies, private organizations and any other
     7     available energy data, as well as the total energy allocation
     8     approach.
     9  Section 302.  Application of energy conservation standards.
    10     The energy conservation standards contained herein or as
    11  promulgated by the department with the approval of the Building
    12  Energy Conservation Committee shall apply to new buildings or to
    13  renovations on which actual construction and/or design has not
    14  commenced prior to their effective dates.
    15  Section 303.  Energy conservation manual for buildings.
    16     (a)  Production of manual.--Concurrent with the adoption of
    17  the energy conservation codes required by this act, the
    18  department shall produce an energy conservation manual for use
    19  by designers, builders, and contractors of residential and
    20  nonresidential buildings, AND MUNICIPALITIES OF THE               <--
    21  COMMONWEALTH. This manual shall contain the established
    22  standards and accepted practices. THE MANUAL SHALL FURTHER        <--
    23  CONTAIN PRESCRIPTIVE STANDARDS WHICH, IF COMPLIED WITH, WILL
    24  RESULT IN CONFORMANCE WITH THE PERFORMANCE STANDARDS CONTAINED
    25  HEREIN OR AS PROMULGATED BY THE DEPARTMENT AND SHALL BE WRITTEN
    26  IN SUCH MANNER AS TO BE EASILY UNDERSTOOD BY PERSONS POSSESSING
    27  A MINIMAL TECHNICAL BACKGROUND. The manual shall be furnished
    28  upon request to members of the public at a price sufficient to
    29  cover the cost of printing.
    30     (b)  Review of manual.--The manual shall be reviewed by the
    19770H0552B2905                 - 44 -

     1  department and the Building Energy Conservation Committee at
     2  least annually and shall be updated as significant new energy
     3  conservation information becomes available.
     4     (C)  EDUCATIONAL PROGRAMS.--THE DEPARTMENT SHALL PROVIDE       <--
     5  SEMINARS AND OTHER EDUCATIONAL PROGRAMS THROUGHOUT THE
     6  COMMONWEALTH TO PROVIDE INFORMATION AND COUNSELING TO BUILDERS,
     7  ARCHITECTS, OTHER LICENSED DESIGN PROFESSIONALS, LOCAL BUILDING
     8  OFFICIALS AND OTHER PERSONS AFFECTED BY THIS ACT ON THE
     9  STANDARDS CONTAINED HEREIN OR AS PROMULGATED BY THE DEPARTMENT.
    10  Section 304.  Building Energy Conservation Committee.
    11     (a)  Composition of committee.--In order to further the
    12  coordinated and effective administration of this act, there is
    13  hereby established a Building Energy Conservation Committee. It
    14  shall consist of at least 25 30 members and no more than 35 40    <--
    15  members, the membership of which shall be appointed by the
    16  Governor and shall include a representative of each of the
    17  following entities or their successors:
    18         (1)  Department of Education.
    19         (2)  Governor's Energy Council.
    20         (3)  Department of General Services.
    21         (4)  Department of Labor and Industry.
    22         (5)  Department of Community Affairs.
    23         (6)  Pennsylvania Builders Association.
    24         (7)  Pennsylvania Associated Builders and Contractors,
    25     Inc.
    26         (8)  Pennsylvania Building Officials Conference.
    27         (9)  Mechanical Contractors Association of America.
    28         (10)  Pennsylvania Chamber of Commerce.
    29         (11)  General Contractors Association of Pennsylvania.
    30         (12)  Pennsylvania Society of Architects.
    19770H0552B2905                 - 45 -

     1         (13)  Pennsylvania Society of Professional Engineers.
     2         (14)  American Society of Heating, Refrigerating and Air
     3     Conditioning Engineers, Inc..
     4         (15)  Pennsylvania Gas Association.
     5         (16)  Pennsylvania Electric Association.
     6         (17)  Industrialized Housing Manufacturers Association.
     7         (18)  Thermal Insulation Manufacturers Association.
     8         (19)  Pennsylvania Building Trades Council.
     9         (20)  CONSULTING ENGINEERS COUNCIL OF PENNSYLVANIA.        <--
    10         (21)  PENNSYLVANIA LEAGUE OF CITIES.
    11         (22)  PENNSYLVANIA STATE ASSOCIATION OF BOROUGHS.
    12         (23)  PENNSYLVANIA STATE ASSOCIATION OF TOWNSHIP
    13     COMMISSIONERS.
    14         (24)  PENNSYLVANIA STATE ASSOCIATION OF TOWNSHIP
    15     SUPERVISORS.
    16         (20) 25  Representatives of such other agencies and        <--
    17     organizations or individuals as the Governor may find are
    18     necessary and proper to carry out the purposes of the
    19     committee including, but not limited to, labor organizations,
    20     financial and lending institutions, and consumer groups.
    21     (b)  Powers and duties.--In addition to the powers and duties
    22  enumerated in this act, the Building Energy Conservation
    23  Committee shall:
    24         (1)  Be responsible for the regular exchange of
    25     information and plans regarding building energy conservation,
    26     for the development, review and approval of proposed and
    27     existing standards, guidelines, regulations, and manuals.
    28         (2)  Elect from its members a Board on Variances.
    29     (c)  Expenses.--The members of the committee shall not
    30  receive any compensation for their services but shall be
    19770H0552B2905                 - 46 -

     1  reimbursed for their actual and necessary expenses incurred in
     2  the performance of their duties. Provided, however, when acting
     3  on matters concerning variances members of the Board on
     4  Variances shall receive $50 per day plus their actual and
     5  necessary expenses.
     6  Section 305.  Certification.
     7     (A)  APPLICABILITY.--THE PROVISIONS OF THIS SECTION SHALL      <--
     8  APPLY TO ALL BUILDINGS SUBJECT TO THIS ACT EXCEPT THOSE
     9  CLASSIFIED AS USE GROUP R-3.
    10     (a) (B)  Compliance with act.--It shall be the duty of the     <--
    11  architect LICENSED DESIGN PROFESSIONAL retained in connection     <--
    12  with the design OR construction or renovation of a building to    <--
    13  certify the drawings, specifications and other data showing
    14  compliance with the provisions of this act, except as provided
    15  in subsection (d) (E). If the building is subject to the          <--
    16  provisions of the act of April 27, 1927 (P.L.465, No.299),
    17  referred to as the Fire and Panic Act, the certification
    18  required hereunder shall be submitted on a form with the
    19  application for plan approval under the said Fire and Panic Act.
    20     (b) (C)  Inspection.--Each architect, other licensed design    <--
    21  professional retained by the owner in lieu of an architect, or    <--
    22  the architect's OR HIS designee, WHERE ANY OF SUCH ARE RETAINED   <--
    23  DURING THE CONSTRUCTION OF A BUILDING, shall make periodic
    24  inspections of the building progression to insure compliance
    25  with this act, except as provided in subsection (d) (E).          <--
    26     (c) (D)  Final certification.--Each architect or other         <--
    27  licensed design professional retained by the owner in lieu of an  <--
    28  architect shall make a final certification of every completed
    29  building showing compliance with the provisions of this act,
    30  except as provided in subsection (d) (E).                         <--
    19770H0552B2905                 - 47 -

     1     (d) (E)  Certification by builder.--If an architect or other   <--
     2  A licensed design professional is not retained in connection      <--
     3  with the design AND construction or renovation of a building, it  <--
     4  shall be the responsibility of the builder or owner, if he is
     5  the builder, to perform the inspections and certification
     6  required by this section.
     7  SECTION 306.  USE GROUP R-3; NOTICE; WARRANTY.                    <--
     8     (A)  NOTICE.--PRIOR TO CONSTRUCTION OF ANY BUILDING
     9  CLASSIFIED AS USE GROUP R-3, THE BUILDER SHALL NOTIFY THE
    10  DEPARTMENT BY CERTIFIED MAIL OF HIS INTENT TO BEGIN
    11  CONSTRUCTION. SUCH NOTICE SHALL CONTAIN THE NAME OF THE OWNER OF
    12  THE BUILDING AND ITS LOCATION.
    13     (B)  WARRANTY.--AT THE TIME A CONTRACT FOR THE CONSTRUCTION
    14  OF ANY BUILDING CLASSIFIED AS USE GROUP R-3 IS ENTERED INTO, THE
    15  BUILDER SHALL WARRANT TO THE OWNER IN WRITING THAT THE BUILDING
    16  SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS OF THIS
    17  ACT. SUCH WARRANTY SHALL BE A DOCUMENT SEPARATE FROM THE
    18  CONTRACT AND SHALL BE IN THE FOLLOWING FORM:
    19     I,  (BUILDER)  , HEREBY WARRANT TO  (OWNER)  THAT THE
    20  PREMISES KNOWN AS  (DESCRIPTION)
    21  SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS OF THE
    22  ACT OF __________, 19__, NO.____, KNOWN AS THE "BUILDING ENERGY
    23  CONSERVATION ACT."  THIS LAW PROVIDES BUILDING AND EQUIPMENT
    24  STANDARDS TO MAKE YOUR HOME ENERGY EFFICIENT AND ALSO PROVIDES
    25  YOU WITH LEGAL REMEDIES IF YOUR HOME IS NOT BUILT ACCORDING TO
    26  THE STATE STANDARDS.  IF YOU WOULD LIKE THE STATE TO DO AN
    27  ENERGY AUDIT OF YOUR HOME TO DETERMINE IF IT CONFORMS TO STATE
    28  STANDARDS, YOU MAY CALL THE PENNSYLVANIA DEPARTMENT OF
    29  COMMUNITY AFFAIRS AT  (TELEPHONE)  , AND THEY WILL PERFORM AN
    30  INSPECTION OF YOUR HOME FOR A FEE OF $25.00.
    19770H0552B2905                 - 48 -

     1     INDICATE IF ALTERNATE BUILDING SYSTEM OR EQUIPMENT DESIGN IS
     2  BEING EMPLOYED.
     3     (C)  IF THE BUILDER IS ALSO THE OWNER OF THE BUILDING AT THE
     4  TIME OF CONSTRUCTION, HE SHALL PROVIDE THE WARRANTY REQUIRED BY
     5  SUBSECTION (B) AT THE TIME OF ITS INITIAL SALE TO A NEW OWNER.
     6  SUCH WARRANTY SHALL BE IN SUBSTANTIALLY THE SAME FORM AS
     7  PROVIDED IN SUBSECTION (B).
     8     (D)  FAILURE TO PROVIDE NOTICE.--THE DEPARTMENT OF COMMUNITY
     9  AFFAIRS, AFTER HEARING, MAY ASSESS A CIVIL PENALTY PAYABLE TO
    10  THE COMMONWEALTH OF PENNSYLVANIA NOT TO EXCEED $100 UPON ANY
    11  BUILDER WHO FAILS TO GIVE THE NOTICE REQUIRED BY SUBSECTION (A).
    12  IN DETERMINING THE AMOUNT OF THE CIVIL PENALTY, THE DEPARTMENT
    13  OF COMMUNITY AFFAIRS SHALL CONSIDER THE WILFULNESS OF THE
    14  VIOLATION AND THE COST INCURRED BY THE DEPARTMENT IN DISCOVERING
    15  THE VIOLATION.
    16     (E)  FAILURE TO PROVIDE WARRANTY.--WHENEVER A BUILDER FAILS
    17  TO PROVIDE THE WARRANTY REQUIRED BY SUBSECTIONS (B) OR (C) SUCH
    18  REQUIRED WARRANTY SHALL CONSTITUTE AN IMPLIED WARRANTY AND THE
    19  OWNER'S RIGHT TO PROCEED UNDER SECTION 315(A) SHALL NOT BE
    20  AFFECTED. IF IT IS ESTABLISHED BY A PREPONDERANCE OF THE
    21  EVIDENCE THAT THE BUILDER'S FAILURE TO PROVIDE THE WARRANTY WAS
    22  WILFUL, THEN DAMAGES IN TWICE THE AMOUNT PROVIDED IN SECTION 315
    23  MAY BE AWARDED.
    24  Section 306 307.  Variances.                                      <--
    25     (a)  Requests.--Any request for a variance from the energy
    26  conservation standards contained herein shall be made to the
    27  Board on Variances of the Building Energy Conservation Committee
    28  AND A DECISION ON SUCH REQUEST SHALL BE MADE WITHIN 30 DAYS OF    <--
    29  ITS FILING.
    30     (b)  Criteria.--A variance shall be granted only if it is
    19770H0552B2905                 - 49 -

     1  found that:
     2         (1)  compliance with the provisions of this act would
     3     result in extreme hardship to the owner; and
     4         (2)  the granting of such variance would not result in a
     5     significant increase in the energy usage of the building.
     6  Section 307 308.  Building permits.                               <--
     7     Any building permit issued by the Commonwealth or any of its
     8  political subdivisions shall have printed upon its face notice
     9  that the provisions of this act must be complied with.
    10  Section 308 309.  Permits for use or occupancy.                   <--
    11     Before any building or structure hereafter constructed or      <--
    12  renovated , OTHER THAN A BUILDING CLASSIFIED AS USE GROUP R-3,    <--
    13  shall be used or opened for occupancy, the owner thereof shall
    14  notify the department of the completion of the building FOR THE   <--
    15  PURPOSES OF THIS ACT and submit the necessary certification
    16  therewith: PROVIDED, HOWEVER, THAT IF A MUNICIPALITY ELECTS TO    <--
    17  ADMINISTER THE PROVISIONS OF THIS ACT UNDER CHAPTER 5 SUCH
    18  NOTICE AND CERTIFICATION SHALL BE SUBMITTED TO THE MUNICIPALITY
    19  WHICH SHALL FORWARD A COPY OF THE NOTICE TO THE DEPARTMENT.
    20  Within 10 days of receipt of the certification the department     <--
    21  shall forward notice of receipt of such certification to the
    22  owner. No permit for use or occupancy shall be granted until
    23  such submission has been made. No building official of the
    24  Commonwealth or any of its political subdivisions shall issue a
    25  permit until he has received proof of SUCH compliance. Provided,  <--
    26  however, that if the certification is forwarded to the
    27  department by certified mail with a return receipt requested and
    28  the owner does not receive the notice of receipt of
    29  certification provided for by this section within the time
    30  provided herein, in such case, any building official of the
    19770H0552B2905                 - 50 -

     1  Commonwealth or any of its political subdivisions shall issue a
     2  permit for use or occupancy upon presentation of the return
     3  receipt by the owner WHERE THE CERTIFICATE HAS BEEN SUBMITTED TO  <--
     4  THE DEPARTMENT, PRESENTATION TO THE BUILDING OFFICIAL OF THE
     5  MAILING RECEIPT TOGETHER WITH A COPY OF THE CERTIFICATION
     6  REQUIRED BY SECTION 305 SHALL ESTABLISH PROOF OF COMPLIANCE FOR
     7  THE PURPOSES OF THIS SECTION. UPON SUCH PRESENTATION ANY
     8  BUILDING OFFICIAL OF THE COMMONWEALTH OR ANY OF ITS POLITICAL
     9  SUBDIVISIONS SHALL ISSUE A PERMIT FOR USE OR OCCUPANCY, PROVIDED
    10  ALL OTHER CRITERIA FOR SUCH A PERMIT HAVE BEEN SATISFIED and
    11  said building official shall notify the department that he has
    12  issued the same.
    13  Section 309 310.  Failure to submit certification.                <--
    14     Whenever the owner of any building, or structure OTHER THAN A  <--
    15  BUILDING CLASSIFIED AS USE GROUP R-3, shall fail to notify the    <--
    16  department of the completion of the building and to GIVE THE      <--
    17  NOTICE AND submit the necessary certification IN ACCORDANCE WITH  <--
    18  SECTION 309 and shall nevertheless proceed with the use or
    19  occupancy of the building, the department or the political        <--
    20  subdivision MUNICIPALITY shall serve notice on the said owner     <--
    21  that he is in violation of this act and order him to comply
    22  therewith.
    23  Section 310 311.  Inspections.                                    <--
    24     The department may inspect PERFORM A NONDESTRUCTIVE            <--
    25  INSPECTION within two years of the date of completion of
    26  construction or renovation OF any building constructed or         <--
    27  renovated after the effective date of this act to determine
    28  compliance with the provisions of this act, provided at least 30
    29  days notice has been given to the owner. THE DEPARTMENT MAY ALSO  <--
    30  PERFORM SUCH INSPECTIONS AT THE REQUEST OF THE OWNER OF ANY
    19770H0552B2905                 - 51 -

     1  BUILDING SUBJECT TO THIS ACT FOR A FEE OF $25.00.
     2  Section 311 312.  Appeals.                                        <--
     3     Review of any decisions rendered under the provisions of this
     4  act shall be brought in the court of common pleas of the county
     5  wherein the building is situated. Such review shall be limited
     6  to determining whether any such decision was arbitrary and
     7  capricious.
     8  Section 312 313.  Penalties.                                      <--
     9     (A)  APPLICABILITY.--THE PROVISIONS OF THIS SECTION SHALL      <--
    10  APPLY TO ALL BUILDINGS SUBJECT TO THIS ACT EXCEPT THOSE
    11  CLASSIFIED AS USE GROUP R-3.
    12     (a) (B)  Violations of act.--Any person who shall willfully    <--
    13  or negligently violate any of the provisions of this act, or the
    14  rules and regulations or the orders for the enforcement of the
    15  said provisions or rules and regulations issued by duly
    16  authorized officers of the department or who shall hinder, delay
    17  or interfere with any officer charged with the enforcement of
    18  this act in the performance of his duty, shall, upon conviction
    19  thereof, be punished by a fine of not more than $300 and costs.
    20  In the event of violation of more than one provision of this
    21  act, the violation of each provision shall be deemed a separate
    22  and distinct offense for the purposes of this section.
    23     (b) (C)  Institution of proceedings.--Prosecutions for         <--
    24  violations of this act or the rules and regulations of the
    25  department may be instituted by the Secretary of Labor and
    26  Industry or the Secretary of Community Affairs, or under his      <--
    27  directions by an authorized representative of the department.
    28  Upon conviction after a hearing IN A COURT OF COMPETENT           <--
    29  JURISDICTION, the sentences provided in this act shall be
    30  imposed and shall be final unless an appeal be taken in the
    19770H0552B2905                 - 52 -

     1  manner prescribed by law.
     2     (c) (D)  Disposition of fines.--All fines collected under      <--
     3  this act shall be forwarded to the department who shall pay the
     4  same into the State Treasury for the use of the Commonwealth.
     5     (d) (E)  False certification.--Any architect or other          <--
     6  licensed design professional who willfully provides a false
     7  certification for any building subject to the provisions of this
     8  act shall be subject to the suspension or revocation of his
     9  license by the State Board of Examiners of Architects or other
    10  applicable State licensing board.
    11  Section 313 314.  Enforcement.                                    <--
    12     (a)  Applicability.--The provisions of this act shall apply
    13  to every building enumerated in this act, except buildings owned  <--
    14  by the Federal Government, including buildings owned in whole or
    15  in part by the Commonwealth or any political subdivision
    16  thereof, and FOR ALL BUILDINGS, OTHER THAN THOSE CLASSIFIED AS    <--
    17  USE GROUP R-3 shall be enforced by the Secretary of Labor and
    18  Industry, or by the Secretary of Community Affairs, by and        <--
    19  through his authorized representatives.
    20     (b)  Powers of officers.--For the purpose of enforcing the
    21  provisions of this act, all the officers charged with its
    22  enforcement shall have the power to enter any of the buildings
    23  enumerated in this act, and no person shall hinder or delay, or
    24  interfere with any of the said officers in the performance of
    25  his duty, nor refuse any pertinent information necessary to
    26  determine whether the provisions of this act and the rules and
    27  regulations herein provided for, are or will be complied with.
    28  SECTION 315.  CIVIL ACTION.                                       <--
    29     (A)  USE GROUP R-3.--THE OWNER OF ANY BUILDING SUBJECT TO THE
    30  REQUIREMENTS OF SECTION 306 WHO IS AGGRIEVED AS THE RESULT OF
    19770H0552B2905                 - 53 -

     1  SUCH BUILDING NOT BEING PROPERLY DESIGNED OR CONSTRUCTED IN
     2  CONFORMANCE WITH THIS ACT SHALL HAVE A RIGHT OF ACTION FOR
     3  BREACH OF WARRANTY. REMEDIES MAY INCLUDE SPECIFIC PERFORMANCE OR
     4  AN AWARD OF DAMAGES IN AN AMOUNT NOT LESS THAN $300. ATTORNEY'S
     5  FEES SHALL BE RECOVERABLE IN ANY ACTION IN WHICH THE OWNER
     6  PREVAILS. ANY SUCH AWARD SHALL FURTHER PROVIDE FOR PAYMENT OF
     7  THE ACTUAL COSTS IN EXCESS OF $25 INCURRED BY THE DEPARTMENT IF
     8  IT INSPECTED THE BUILDING FOR THE OWNER AND THE OWNER SHALL
     9  REMIT SUCH AMOUNT TO THE DEPARTMENT.
    10     (B)  OTHER BUILDINGS.--THE OWNER OF ANY BUILDING, OTHER THAN
    11  A BUILDING CLASSIFIED AS USE GROUP R-3, AT THE TIME OF ITS
    12  DESIGN OR CONSTRUCTION UNDER THE PROVISIONS OF THIS ACT WHO IS
    13  AGGRIEVED AS THE RESULT OF SUCH BUILDING NOT BEING PROPERLY
    14  DESIGNED OR CONSTRUCTED IN CONFORMANCE WITH THIS ACT SHALL HAVE
    15  A RIGHT OF ACTION AGAINST ANY PERSON WHO IS REQUIRED TO SUBMIT
    16  THE CERTIFICATE REQUIRED BY SECTION 305.
    17     (C)  LIMITATION OF ACTION.--NO ACTION BROUGHT UNDER THIS
    18  SECTION SHALL BE MAINTAINED UNLESS BROUGHT WITHIN THREE YEARS
    19  FROM THE DATE OF COMPLETION OF THE BUILDING.
    20                             CHAPTER 4
    21                    ADOPTION OF FUTURE STANDARDS
    22  Section 401.  Adoption and promulgation of standards.
    23     The department, with the approval of the Building Energy
    24  Conservation Committee, shall, after one or more public
    25  hearings, adopt and publish energy conservation standards for
    26  all buildings covered by this act in accordance with the
    27  provisions of the act of July 31, 1968 (P.L.769, No.240), known
    28  as the "Commonwealth Documents Law." The purpose of such
    29  standards is to reduce wasteful or uneconomic consumption of
    30  energy by balancing the cost of energy procurement against the
    19770H0552B2905                 - 54 -

     1  cost of energy-conserving building practices. The energy
     2  conservation standards shall meet the following criteria:
     3         (1)  They shall be consistent with the latest and most
     4     effective technology.
     5         (2)  They shall not be in conflict with existing
     6     safeguards for public health and safety.
     7         (3)  They shall be economically feasible as determined by
     8     life-cycle-cost procedures.
     9         (4)  They shall be sufficiently stringent to effect a
    10     significant savings of energy resources.
    11         (5)  They shall be a performance standard for the design
    12     of buildings and systems within buildings to assure maximum
    13     practical conservation of energy.
    14         (6)  Consideration shall be given to building and energy
    15     standards promulgated by national and other State
    16     governmental agencies, private organizations and any other
    17     available energy data, as well as the total energy allocation
    18     approach.
    19                             CHAPTER 5                              <--
    20                           LOCAL ELECTION
    21  SECTION 501.  ELECTION; USE GROUP R-3.
    22     ANY MUNICIPALITY OF THIS COMMONWEALTH MAY ELECT TO ADMINISTER
    23  THE PROVISIONS OF THIS ACT RELATING TO USE GROUP R-3 BUILDINGS,
    24  AS DEFINED IN SECTION 103, EXCEPT FOR UNITS SUBJECT TO THE ACT
    25  OF MAY 11, 1972 (P.L.286, NO.70), KNOWN AS THE "INDUSTRIALIZED
    26  HOUSING ACT" AND THE ACT OF MAY 11, 1972 (P.L.281, NO.69), KNOWN
    27  AS THE "UNIFORM STANDARDS CODE FOR MOBILE HOMES." SUCH ELECTION
    28  SHALL BE MADE BY RESOLUTION OF THE GOVERNING BODY OF SUCH
    29  MUNICIPALITY WHICH SHALL BE IN SUBSTANTIALLY THE FOLLOWING FORM:
    30     THE (CITY, BOROUGH, TOWN, OR TOWNSHIP) OF____________________
    19770H0552B2905                 - 55 -

     1  HEREBY ELECTS TO ADMINISTER THE PROVISIONS OF THE ACT
     2  OF____________, 1978, NO._______ KNOWN AS THE "BUILDING ENERGY
     3  CONSERVATION ACT" FOR USE GROUP R-3 BUILDINGS AS DEFINED
     4  THEREIN.
     5  SECTION 502.  ELECTION; CITIES OF THE FIRST, SECOND AND SECOND
     6                CLASS A.
     7     ANY CITY OF THE FIRST CLASS, SECOND CLASS AND SECOND CLASS A
     8  MAY ELECT TO ADMINISTER THE PROVISIONS OF THIS ACT FOR ALL
     9  BUILDINGS SUBJECT HERETO, EXCEPT FOR UNITS SUBJECT TO THE ACT OF
    10  MAY 11, 1972 (P.L.286, NO.70), KNOWN AS THE "INDUSTRIALIZED
    11  HOUSING ACT" AND THE ACT OF MAY 11, 1972 (P.L.281, NO.69), KNOWN
    12  AS THE "UNIFORM STANDARDS CODE FOR MOBILE HOMES." SUCH ELECTION
    13  SHALL BE MADE BY RESOLUTION OF THE GOVERNING BODY OF SUCH CITY
    14  WHICH SHALL BE IN SUBSTANTIALLY THE FOLLOWING FORM:
    15     THE CITY OF________________HEREBY ELECTS TO ADMINISTER THE
    16  PROVISIONS OF THE ACT OF _________, 1978, NO._______ KNOWN AS
    17  THE "BUILDING ENERGY CONSERVATION ACT."
    18  SECTION 503.  POWERS OF MUNICIPALITIES.
    19     ANY MUNICIPALITY ELECTING TO ADMINISTER THE PROVISIONS OF
    20  THIS ACT UNDER SECTION 501 OR 502 SHALL EXERCISE THE SAME POWERS
    21  CONFERRED UPON THE DEPARTMENT BY THIS ACT, INCLUDING THE POWER
    22  TO INSTITUTE PROCEEDINGS FOR VIOLATIONS OF THE ACT, WITH THE
    23  EXCEPTION OF THOSE POWERS SPECIFIED IN SECTIONS 301, 303 AND IN
    24  CHAPTER 4. IN ADDITION, ANY SUCH MUNICIPALITY MAY EXERCISE SUCH
    25  OTHER ADMINISTRATIVE AND ENFORCEMENT PROCEDURES AS IT SHALL DEEM
    26  NECESSARY TO EFFECT THE PURPOSES OF THIS ACT INCLUDING, BUT NOT
    27  LIMITED TO, PRIOR PLAN APPROVAL, BUILDING PERMIT REQUIREMENTS,
    28  USE OR OCCUPANCY PERMIT REQUIREMENTS AND INSPECTIONS DURING THE
    29  COURSE OF CONSTRUCTION.
    30  SECTION 504.  VARIANCES.
    19770H0552B2905                 - 56 -

     1     ANY MUNICIPALITY ELECTING TO ADMINISTER THE PROVISIONS OF
     2  THIS ACT UNDER SECTION 501 OR 502 SHALL ESTABLISH A BOARD ON
     3  VARIANCES TO MAKE DETERMINATIONS ON REQUEST FOR VARIANCE FROM
     4  THE ENERGY CONSERVATION STANDARDS CONTAINED HEREIN OR AS
     5  PROMULGATED BY THE DEPARTMENT WITH THE APPROVAL OF THE BUILDING
     6  ENERGY CONSERVATION COMMITTEE, AND IS AUTHORIZED EXCLUSIVE
     7  JURISDICTION TO GRANT SUCH VARIANCES, SECTION 307(A)
     8  NOTWITHSTANDING. A VARIANCE SHALL ONLY BE GRANTED IF THE
     9  CRITERIA OF SECTION 307(B) HAVE BEEN SATISFIED.
    10  SECTION 505.  DISPOSITION OF FINES.
    11     ANY FINES COLLECTED UNDER THIS ACT BY ANY MUNICIPALITY
    12  ELECTING TO ADMINISTER THE PROVISIONS OF THIS ACT UNDER SECTION
    13  501 OR 502 SHALL BE RETAINED BY THE MUNICIPALITY, SECTION 313(C)
    14  NOTWITHSTANDING.
    15                             CHAPTER 6
    16                     REPORT TO GENERAL ASSEMBLY
    17  SECTION 601.  REPORT TO GENERAL ASSEMBLY.
    18     THIRTY MONTHS AFTER THE EFFECTIVE DATE OF THIS ACT, THE
    19  DEPARTMENT SHALL REPORT TO THE GENERAL ASSEMBLY THE RESULTS OF
    20  THE INSPECTIONS IT HAS PERFORMED UNDER THIS ACT TOGETHER WITH A
    21  REPORT ON PUBLIC COMPLIANCE WITH THIS ACT.
    22  Section 402 602.  Effective date.                                 <--
    23     This act shall take effect as follows:
    24         (1)  Chapter 2 shall take effect in six months and shall
    25     remain in full force and effect for a period of one year
    26     after which time the provisions of Chapter 2 shall have no
    27     legal effect.
    28         (2)  Section 301 shall take effect immediately and its
    29     provisions shall remain in full force and effect for a period
    30     of 18 months after which time said provisions shall have no
    19770H0552B2905                 - 57 -

     1     legal effect.
     2         (3)  Chapter 4 shall take effect in 18 months.
     3         (4)  All other provisions of this act shall take effect
     4     immediately.


















    B10L42JLW/19770H0552B2905       - 58 -