PRIOR PRINTER'S NOS. 600, 1775                PRINTER'S NO. 2328

THE GENERAL ASSEMBLY OF PENNSYLVANIA


HOUSE BILL

No. 552 Session of 1977


        INTRODUCED BY MESSRS. ITKIN, B. F. O'BRIEN, MISCEVICH, ABRAHAM,
           TRELLO, GAMBLE, McCALL, LEHR, SWEET AND J. L. WRIGHT,
           MARCH 7, 1977

        AS RE-REPORTED FROM COMMITTEE ON MINES AND ENERGY MANAGEMENT,
           HOUSE OF REPRESENTATIVES, AS AMENDED, NOVEMBER 21, 1977

                                     AN ACT

     1  Providing for the regulation for energy conservation purposes of
     2     the construction of buildings, the establishment of a
     3     Building Energy Conservation Committee, appeals and for
     4     penalties.

     5                         TABLE OF CONTENTS
     6  Chapter 1.  General Provisions
     7     Section 101.  Short title.
     8     Section 102.  Legislative findings and declaration of
     9                   purpose.
    10     Section 103.  Definitions.
    11  Chapter 2.  Energy Conservation Standards
    12     Section 201.  Provisions.
    13     Subchapter A.  Plans and Specifications
    14     Section 202.  Submission.
    15     Section 203.  Contents.
    16     Subchapter B.  Definitions Relating to Energy Conservation
    17                    Standards
    18     Section 204.  Definitions relating to standards.

     1     Subchapter C.  Building Envelope
     2     Section 205.  General provisions.
     3     Section 206.  Criteria for residential buildings.
     4     Section 207.  Other buildings.
     5     Section 208.  Air leakage.
     6     Subchapter D.  Warm Air Heating, Ventilating and Air
     7                    Conditioning Systems and Equipment
     8     Section 209.  General provisions.
     9     Section 210.  Design requirements.
    10     Section 211.  Cooling with outdoor air.
    11     Section 212.  Mechanical ventilation.
    12     Section 213.  Simultaneous heating and cooling.
    13     Section 214.  Reheat systems.
    14     Section 215.  Dual duct and multizone systems.
    15     Section 216.  Recooling systems.
    16     Section 217.  Multiple zones.
    17     Section 218.  Concurrent operation.
    18     Section 219.  Equipment performance requirements.
    19     Section 220.  Duct insulation.
    20     Section 221.  System controls.
    21     Section 222.  Steam and hot water heating piping.
    22     Subchapter E.  Plumbing Systems
    23     Section 223.  Purpose.
    24     Section 224.  Fixtures.
    25     Section 225.  Insulation.
    26     Section 226.  Equipment.
    27     Section 227.  Controls.
    28     Subchapter F.  Electrical Systems
    29     Section 228.  System requirements.
    30     Subchapter G.  Lighting
    19770H0552B2328                  - 2 -

     1     Section 229.  Light power budget.
     2     Section 230.  Calculation methods.
     3     Section 231.  Building interiors.
     4     Section 232.  Building exteriors.
     5     Section 233.  Exceptions to criteria.
     6     Section 234.  Calculation procedure.
     7     Subchapter H.  Alternative Systems
     8     Section 235.  Performance alternative.
     9     Section 236.  Nondepletable sources.
    10     Section 237.  Documentation.
    11  Chapter 3.  Application of Standards:  Establishment of
    12              Committee and Penalties
    13     Section 301.  Modification of standards; criteria.
    14     Section 302.  Application of energy conservation standards.
    15     Section 303.  Energy conservation manual for buildings.
    16     Section 304.  Building Energy Conservation Committee.
    17     Section 305.  Certification.
    18     Section 306.  Variances.
    19     Section 307.  Building permits.
    20     Section 308.  Permits for use or occupancy.
    21     Section 309.  Failure to submit certification.
    22     Section 310.  Inspections.
    23     Section 311.  Failure to comply with provisions of this act.   <--
    24     Section 312 311.  Appeals.                                     <--
    25     Section 313 312.  Penalties.                                   <--
    26     Section 314 313.  Enforcement.                                 <--
    27  CHAPTER 4.  DEPARTMENT'S STANDARD                                 <--
    28     SECTION 401.  ADOPTION AND PROMULGATION OF STANDARDS
    29     Section 315 402.  Effective date.                              <--
    30     The General Assembly of the Commonwealth of Pennsylvania
    19770H0552B2328                  - 3 -

     1  hereby enacts as follows:
     2                             CHAPTER 1
     3                         GENERAL PROVISIONS
     4  Section 101.  Short title.
     5     This act shall be known and may be cited as the "Building
     6  Energy Conservation Act."
     7  Section 102.  Legislative findings and declaration of purpose.
     8     (a)  Findings.--The Legislature hereby determines that:
     9         (1)  Energy shortages in the domestic supply present far-
    10     reaching problems that promise to persist. These energy
    11     shortages effect the continued efficient operation of the
    12     Commonwealth's economy and social structure.
    13         (2)  It is the Commonwealth's responsibility to provide
    14     for energy conservation through regulation of design and
    15     construction standards.
    16         (3)  The Legislature intends, by this act, to respond to
    17     these shortages by devising a specific responsible energy
    18     conservation policy for building systems.
    19     (b)  Purpose.--The purpose of this act is to grant to the
    20  Commonwealth of Pennsylvania and direct it to exercise specific
    21  authority in building construction to assure that such
    22  construction is performed using materials and techniques that
    23  will provide for energy conservation in the future operation and
    24  maintenance of said structure.
    25  Section 103.  Definitions.
    26     The following words and phrases when used in this act shall
    27  have, unless the context clearly indicates otherwise, the
    28  meanings given to them in this section:
    29     "Building."  Any structure that provides facilities or
    30  shelter for public assembly or for educational, business,
    19770H0552B2328                  - 4 -

     1  mercantile, institutional, warehouse or residential occupancy,
     2  or industrial use including, but not limited to, those portions
     3  of factory and industrial occupancy such as office space except
     4  for:
     5         (1)  Buildings and structures or portions thereof whose
     6     peak design rate of energy usage is less than one watt per
     7     square foot or 3.4 BTU/hr per square foot of floor area for
     8     all purposes.
     9         (2)  Structures or those portions of structures used for
    10     manufacturing or processing and whose manufacturing or
    11     processing procedures require the use of substantial heat
    12     producing energy to create their product.
    13         (3)  Buildings which are neither heated nor cooled.
    14         (4)  Historic buildings.
    15     "Construction."  The erection, fabrication or renovation of a
    16  building.
    17     "Department."  The Pennsylvania Department of Labor and
    18  Industry EXCEPT THAT FOR ALL UNITS SUBJECT TO THE ACT OF MAY 11,  <--
    19  1972 (P.L.286, NO.70), KNOWN AS THE "INDUSTRIALIZED HOUSING
    20  ACT," AND ALL BUILDINGS CLASSIFIED AS USE GROUP R-3, HEREIN,
    21  DEPARTMENT MEANS THE PENNSYLVANIA DEPARTMENT OF COMMUNITY
    22  AFFAIRS.
    23     "Design."  Calculations and resultant drawings and
    24  specifications which are used for the construction of a
    25  building.
    26     "Historic building."  Any building which is deliberately
    27  preserved beyond its normal term of use because of historic
    28  associations, architectural interest, or public policy; or which
    29  qualifies for special historic building code provisions.
    30     "LICENSED DESIGN PROFESSIONAL."  A PERSON LICENSED AS AN       <--
    19770H0552B2328                  - 5 -

     1  ARCHITECT OR PROFESSIONAL ENGINEER PURSUANT TO THE APPROPRIATE
     2  LICENSURE ACT.
     3     "Life-cycle cost."  The cost of a building including its
     4  initial cost, the cost of the energy consumed over its economic
     5  life and the cost of its operation and maintenance.
     6     "Performance standards."  Parameters within which designers
     7  of buildings shall work. The specific practices that a designer
     8  employs shall not be prescribed as long as the result is within
     9  the parameters established by the standards.
    10     "Renovation."  The rehabilitation of an existing building to   <--
    11  reasonably place it in its original structural condition and
    12  which requires more than 25% of the gross floor area or volume
    13  of the entire building to be rebuilt.
    14                             CHAPTER 2
    15                   ENERGY CONSERVATION STANDARDS
    16  Section 201.  Provisions.
    17     The following provisions regulate the design and construction
    18  of the exterior envelopes and selection of HVAC, service water
    19  heating, electrical distribution, and illumination systems and
    20  equipment required for the purpose of effective use of energy
    21  and shall govern the construction of all buildings, or portions
    22  thereof, as provided herein.
    23                            SUBCHAPTER A
    24                      PLANS AND SPECIFICATIONS
    25  Section 202.  Submission.
    26     Plans, specifications and necessary computations together
    27  with the necessary certification required by section 305 shall
    28  be submitted to indicate conformance with this chapter and other
    29  applicable chapters of this act.
    30  Section 203.  Contents.
    19770H0552B2328                  - 6 -

     1     The plans and specifications shall show in sufficient detail
     2  all pertinent data and features of the building and the
     3  equipment and systems as herein governed, including but not
     4  limited to: exterior envelope component materials, U values of
     5  elements, R values of insulating materials, size and type of
     6  apparatus and equipment, equipment and system controls and other
     7  pertinent data to indicate conformance with the requirements
     8  herein.
     9                            SUBCHAPTER B
    10                      DEFINITIONS RELATING TO
    11                   ENERGY CONSERVATION STANDARDS
    12  Section 204.  Definitions relating to standards.
    13     The following words and phrases when used in this chapter
    14  shall have, unless the context clearly indicates otherwise, the
    15  meanings given to them in this section:
    16     "Coefficient of beam utilization" (CBU).  The ratio of the
    17  luminous flux (lumens) reaching a specified area directly from a
    18  floodlight or projector to the total beam luminous flux.
    19     "Coefficient of performance" (COP) - cooling:  The ratio of
    20  the rate of net heat removal to the rate of total energy input,
    21  expressed in consistent units and under designated rating
    22  conditions.
    23     "Coefficient of performance" (COP) - heat pump, heating:  The
    24  ratio of the rate of net heat output to the rate of total energy
    25  input, expressed in consistent units and under designated rating
    26  conditions.
    27     The rate of net heat output shall be defined as the change in
    28  the total heat contents of the air entering and leaving the
    29  equipment not including supplementary heat.
    30     Total energy input shall be determined by combining the
    19770H0552B2328                  - 7 -

     1  energy inputs to all elements, except supplementary heaters, of
     2  the heat pump, including, but not limited to, compressors,
     3  pumps, supply air fans, return air fans, outdoor air fans,
     4  cooling tower fans and the heating, ventilating and air
     5  conditioning system equipment control circuit.
     6     "Coefficient of utilization" (CU).  The ratio of the luminous
     7  flux (lumens) from a luminaire received on the work plane to the
     8  lumens emitted by the luminaire's lamps alone.
     9     "Color rendition."  General expression for the effect of a
    10  light source on the color. Appearance of objects in conscious or
    11  subconscious comparison with their color appearance under a
    12  reference light source.
    13     "Degree day, heating."  A unit, based upon temperature
    14  difference and time, used in estimating fuel consumption and
    15  specifying nominal heating load of a building in winter. For any
    16  one day, when the mean temperature is less than 65 F., there
    17  exists as many degree days as there are Fahrenheit degrees
    18  difference in temperature between the mean temperature for the
    19  day and 65 F.
    20     "Energy efficiency ratio" (EER).  The ratio of net cooling
    21  capacity in Btuh to total rate of electric input in watts under
    22  designated operating conditions.
    23     "Equivalent sphere illumination" (ESI).  The level of sphere
    24  illumination which would produce task visibility equivalent to
    25  that produced by a specific lighting environment.
    26     "Exterior envelope."  The elements of a building which
    27  enclose conditioned spaces through which thermal energy may be
    28  transferred to or from the exterior.
    29     "Floodlighting."  A lighting system designated to light an
    30  area using projector type luminaires usually capable of being
    19770H0552B2328                  - 8 -

     1  pointed in any direction.
     2     "Flood "FLOOR area, gross."  Gross floor area shall be the     <--
     3  floor area within the perimeter of the outside walls of the
     4  building under consideration, without deduction for hallways,
     5  stairs, closets, thickness of walls, columns or other features.
     6     "Illumination."  The density of the luminous flux incident on
     7  a surface. it IT is the quotient of the luminous flux by the      <--
     8  area of the surface when the latter is uniformly illuminated.
     9     "Light loss factor" (LLF).  A factor used in calculating the
    10  level of illumination after a given period of time and under
    11  given conditions. It takes into account temperature and voltage
    12  variations, dirt accumulation on luminaire and room surfaces,
    13  lamp depreciation, maintenance procedures and atmosphere
    14  conditions.
    15     "Luminaire."  A complete lighting unit consisting of a lamp
    16  or lamps together with the parts designed to distribute the
    17  light, to position and protect the lamps and to connect the
    18  lamps to the power supply.
    19     "Packaged terminal air conditioner."  A factory selected
    20  combination of heating and cooling components, assemblies or
    21  sections, intended to serve a room or zone.
    22     "Power."  In connection with machines, power is the time rate
    23  of doing work. In connection with the transmission of energy of
    24  all types, power refers to the rate at which energy is
    25  transmitted; in customary units, it is measured in watts (W) or
    26  British thermal units per hour (Btuh) and in SI units is
    27  measured in watts (W).
    28     "Reflectance."  The ratio of the light reflected by a surface
    29  to the light falling upon it.
    30     "Reheat."  The application of sensible heat to supply air
    19770H0552B2328                  - 9 -

     1  that has been previously cooled below the temperature of the
     2  conditioned space by either mechanical refrigeration or the
     3  introduction of outdoor air to provide cooling.
     4     "Residential buildings."  All buildings and structures or
     5  parts thereof shall be classified in the residential (R) use
     6  group in which families or households live, or in which sleeping
     7  accommodations are provided for individuals with or without
     8  dining facilities, excluding those that are classified as
     9  institutional buildings.
    10     Use group R-1 structures.  This use group shall include all
    11  hotel and motel buildings, lodging houses, boarding houses and
    12  dormitory buildings arranged for the shelter and sleeping
    13  accommodation of more than 20 individuals.
    14     Use group R-2 structures.  This use group shall include all
    15  multiple-family dwellings having more than two dwelling units;
    16  and shall also include all dormitories, boarding and lodging
    17  houses arranged for shelter and sleeping accommodation by more
    18  than five and not more than 20 individuals.
    19     Use group R-3 structures.  This use group shall include all
    20  buildings arranged for the use of one or two family dwelling
    21  units including not more than five lodgers or boarders per
    22  family.
    23     "Resistance, thermal" (R).  A measure of the ability to
    24  retard the flow of heat. The R value is the reciprocal of a heat
    25  transfer coefficient, as expressed by U.  R = 1/U.
    26     "Thermal transmittance" (U).  Overall coefficient of heat
    27  transmission or thermal transmittance (air to air) expressed in
    28  units of BTU per hour per square foot per degree F.  It is the
    29  time rate of heat flow. The U value applies to combinations of
    30  different materials used in series along the heat flow path and
    19770H0552B2328                 - 10 -

     1  also to single materials that comprise a building section and
     2  include cavity air spaces and surface air films on both sides.
     3     "Thermal transmittance" (Uo).  Overall (average) heat
     4  transmission or thermal transmittance of a gross area of the
     5  exterior building envelope, expressed in units of BTU per hour
     6  per square foot per degree F.
     7     The Uo value applies to the combined effect of the time rate
     8  of heat flows through the various parallel paths, such as
     9  windows, doors and opaque construction areas, comprising the
    10  gross area of one or more exterior building components, such as
    11  walls, floor or roof/ceiling.
    12     "Thermostat."  An instrument which measures changes in
    13  temperature and controls devices for maintaining a desired
    14  temperature.
    15     "Veiling reflections."  Regular reflections superimposed upon
    16  diffuse reflections from an object that partially or totally
    17  obscure the details to be seen by reducing the contrast. This
    18  sometimes is called "reflected glare."
    19     "Work plane."  The plane at which work usually is done and at
    20  which the illumination is specified and measured. Unless
    21  otherwise indicated, this is assumed to be a horizontal plane 30
    22  in. (0.76 m) above the floor.
    23     "Zone."  A space or group of spaces within a building with
    24  heating or cooling requirements sufficiently similar so that
    25  comfort conditions can be maintained throughout by a single
    26  controlling device.
    27                            SUBCHAPTER C
    28                         BUILDING ENVELOPE
    29  Section 205.  General provisions.
    30     (a)  Purpose of subchapter.--The intent of this subchapter is
    19770H0552B2328                 - 11 -

     1  to provide minimum requirements for exterior envelope
     2  construction in the interest of energy conservation.
     3     In addition to the criteria set forth in this subchapter the
     4  proposed design may take into consideration the thermal mass of
     5  the building in considering energy conservation.
     6     (b)  Thermal performance.--All buildings and structures that
     7  are heated or mechanically cooled shall be constructed so as to
     8  provide the required thermal performance of the various
     9  components.
    10     The required thermal transmittance value (Uo) of any one
    11  component, such as roof/ceiling, wall or floor may be increased
    12  and the Uo value for other components decreased provided that
    13  the overall heat gain or loss for the entire building envelope
    14  does not exceed the total resulting from conformance to the
    15  required Uo values.
    16     (c)  Different requirements.--A building that is designed to
    17  be both heated and cooled shall meet the more stringent of the
    18  heating or cooling requirements of the exterior envelope as
    19  provided in this subchapter when requirements differ.
    20     (d)  Exterior walls.--For the purpose of this subchapter the
    21  gross area of exterior walls consists of all opaque wall areas,
    22  including foundation walls above grade, peripheral edges of
    23  floors, window areas including sash, and door areas, where such
    24  surfaces are exposed to outdoor air and enclose a heated or
    25  mechanically cooled space.
    26     (e)  Roof assembly.--For the purpose of this subchapter a
    27  roof assembly shall be considered as all components of the
    28  roof/ceiling envelope through which heat flows, thereby creating
    29  a building transmission heat loss or gain, where such assembly
    30  is exposed to outdoor air and encloses a heated or mechanically
    19770H0552B2328                 - 12 -

     1  cooled space.
     2     The gross area of a roof assembly consists of the total
     3  interior surface of such assembly, including skylights, exposed
     4  to the heated or mechanically cooled space.
     5     Where air ceiling plenums are employed, the roof or ceiling
     6  assembly shall:
     7         (1)  For thermal transmittance purposes not include the
     8     ceiling proper nor the plenum space as part of the assembly.
     9         (2)  For gross area purposes be based upon the interior
    10     face of the upper plenum surface.
    11  Section 206.  Criteria for residential buildings.
    12     (a)  Applicability.--The requirements herein shall apply to
    13  all buildings and structures or portions thereof of use groups
    14  R-1, R-2 and R-3 that are heated or mechanically cooled when not
    15  more than 3 stories or 40 feet in height.
    16     (b)  Walls.--The gross area of exterior walls above grade,
    17  including foundation walls, shall have a combined thermal
    18  transmittance value (Uo) not exceeding those specified in Table
    19  1. with the following exceptions:                                 <--
    20         (1)  In locations with less than 500 heating degree days
    21     there shall not be a maximum Uo requirement if only heating
    22     is provided and the Uo shall be 0.30 maximum if the building
    23     is mechanically cooled.
    24         (2)  The opaque exterior wall areas may be constructed
    25     having thermal transmittance (U) values in conjunction with
    26     glazed opening areas in accordance with Table 2.
    27                              Table 1
    28                 Maximum Allowable "Uo" Values for
    29                   Gross Exterior Wall Assemblies
    30                                       Detached         All other
    19770H0552B2328                 - 13 -

     1     Annual heating degree days*   one & two family    residential
     2                  500                    0.30             0.38      <--
     3                 1000                    0.29             0.37
     4                 2000                    0.28             0.35
     5                 3000                    0.26             0.33
     6                 4000                    0.25             0.31
     7                 5000                    0.23             0.29
     8                 6000                    0.22             0.27
     9                 7000                    0.20             0.26
    10                 8000                    0.19             0.24      <--
    11                 9000                    0.17             0.22
    12            10,000 or more               0.16             0.20
    13     *As specified in Chapter 43 ASHRAE Handbook-Systems.
    14                              Table 2                               <--
    15       Maximum Allowable "U" Values for Above-Grade Exterior
    16         Wall Sections and Corresponding Maximum Allowable
    17                        Glazed Opening Areas
    18                                     Required "U" opaque walls
    19                                Btuh per square foot per degree F.
    20                                         (3 stories or less)
    21         Yearly      Glazed                  Use group R-3
    22     degree days    openings             per cent glazed opening
    23                                         10     15     20     25
    24     2500 or Less    Single              .21    .15    .09    .03
    25                     Double              .26    .24    .21    .18
    26     2501 to 4500    Single              .17    .12    .06    .02
    27                     Double              .23    .20    .18    .14
    28     4501 to 6000    Single              .14    .08    .02    NP
    29                     Double              .19    .17    .14    .10
    30     6001 to 8000    Single              .12    .06    .01    NP
    19770H0552B2328                 - 14 -

     1                     Double              .17    .14    .11    .08
     2     8001 to 10,000  Single              .09    .02    NP     NP
     3                     Double              .14    .11    .08    .04
     4    10,000 or more   Single              .05    NP     NP     NP
     5                     Double              .11    .07    .04    NP
     6         Yearly      Glazed               All other residential
     7     degree days    openings             per cent glazed opening
     8                                         15     20     25     30
     9     2500 or Less    Single              .25    .19    .13    .07
    10                     Double              .33    .31    .29    .27
    11     2501 to 4500    Single              .20    .14    .08    .03
    12                     Double              .29    .26    .24    .21
    13     4501 to 6000    Single              .15    .09    .03    NP
    14                     Double              .24    .21    .18    .15
    15     6001 to 8000    Single              .13    .07    .01    NP
    16                     Double              .21    .19    .16    .13
    17     8001 to 10,000  Single              .08    .02    NP     NP
    18                     Double              .17    .14    .10    .06
    19    10,000 or more   Single              .04    NP     NP     NP
    20                     Double              .12    .09    .05    NP
    21     Note 1.  NP - Not Permitted.
    22     Note 2.  For glazed opening percentages other than those
    23  specified above, linear interpolation may be utilized.
    24     Note 3.  For combinations of single and double glazing, the
    25  "U" values above may be interpolated in proportion to the single
    26  and double glazed areas utilized.
    27     Note 4.  To obtain credit for triple glazing or superior
    28  quality sash, or to utilize combinations of single and double
    29  glazing not permitted by this table, use Table 1.
    30     Note 5.  Interpolation between given "U" values and between
    19770H0552B2328                 - 15 -

     1  degrees days is not permitted.
     2     (c)  Roof/ceiling.--The roof/ceiling assemblies shall have a
     3  combined thermal transmittance value (Uo) NOT TO EXCEED 0.05      <--
     4  EXCEPT THAT ROOF/CEILING ASSEMBLIES IN WHICH THE FINISHED
     5  INTERIOR SURFACE IS ESSENTIALLY THE UNDERSIDE OF THE ROOF DECK,
     6  SUCH AS A WOODEN CATHEDRAL CEILING, MAY HAVE A "UO" VALUE NOT TO
     7  EXCEED 0.08. THESE VALUES PRESUME NO SIGNIFICANT THERMAL
     8  TRANSMISSION THROUGH FRAMING MEMBERS, SKYLIGHTS OR OTHER
     9  INTERRUPTIONS IN THE ROOF ENVELOPE. IF SUCH INTERRUPTIONS OCCUR,
    10  CALCULATIONS MUST BE MADE SHOWING CONFORMANCE TO THE REQUIRED
    11  "UO" VALUES. or shall be provided with thermal insulation having  <--
    12  an "R" value as specified in Table 3 with the following
    13  exception:
    14     Roof/ceiling assemblies in which the finished interior
    15  surface is essentially the underside of the roof deck, such as a
    16  wooden cathedral ceiling, may have a "Uo" value not to exceed
    17  0.08 BTU per hour per square foot per degree F. for any heating
    18  degree day area.
    19                              Table 3
    20           Maximum Allowable "Uo" Values and Alternative
    21          Minimum Allowable "R" Values of Added Insulation
    22                    for Roof/Ceiling Assemblies
    23     Annual heating degree days      Maximum "Uo"    Minimum "R"
    24             8000 or Less                0.05            19
    25             More than 8000              0.04            22
    26     Note 1.  These values presume no significant thermal
    27  transmission through framing members, skylights or other
    28  interruptions in the roof envelope. If such interruptions occur,
    29  calculations must be made showing conformance to the required
    30  "Uo" values.
    19770H0552B2328                 - 16 -

     1     (d)  Floors over unheated spaces.--The floor of a heated or
     2  mechanically cooled space located over an unheated space shall
     3  have a combined thermal transmittance value (Uo) or shall be      <--
     4  provided with thermal insulation having an "R" value as
     5  specified in Table 4. NOT TO EXCEED 0.08.                         <--
     6                              Table 4                               <--
     7           Maximum Allowable "Uo" Values and Alternative
     8          Minimum Allowable "R" Values of Added Insulation
     9                  for Floors over Unheated Spaces
    10     Annual heating degree days      Maximum "Uo"    Minimum "R"
    11              500*                       0.36            --
    12             1000                        0.32            --
    13             2000                        0.25            4
    14             3000                        0.18            6
    15             4000                        0.11            9
    16             4500 or More                0.08           11
    17     *Table values may be interpolated.
    18     (e)  Slab-on grade floors.--
    19         (1)  For slab-on grade floors, the perimeter of the floor
    20     shall be insulated with a material having a thermal
    21     resistance value (R) not less than those specified in Table 5  <--
    22     2.
    23                             Table 5 2                              <--
    24             Minimum Allowable "R" Values of Perimeter
    25                Insulation for Slab-On Grade Floors
    26     Annual heating degree days      Heated slab     Unheated slab
    27                  500*                   2.9             --         <--
    28                 1000                    3.3             --
    29                 2000                    4.0             --
    30                 3000                    4.8             2.8
    19770H0552B2328                 - 17 -

     1                 4000                    5.5             3.5
     2                 5000                    6.3             4.2
     3                 6000                    7.0             4.9
     4                 7000                    7.8             5.5
     5                 8000                    8.5             6.2        <--
     6                 9000                    9.3             6.8
     7         10,000 or more                 10.0             7.5
     8     *Table values may be interpolated.
     9         (2)  The insulation shall extend downward from the top of
    10     the slab for a minimum distance of 24 inches or downward to
    11     the bottom of the slab then horizontally beneath the slab for
    12     a minimum total distance of 24 inches.
    13  Section 207.  Other buildings.
    14     (a)  Coverage.--The heating and cooling requirements herein
    15  shall govern all buildings and structures or portions thereof
    16  other than defined by section 206.
    17     (b)  Heating criteria for walls.--All buildings and
    18  structures that are heated shall have a combined thermal
    19  transmittance value (Uo) for the gross area of exterior walls
    20  not exceeding those specified in Table 6 3.                       <--
    21                             Table 6 3                              <--
    22                   Maximum Allowable "Uo" Values
    23                 for Gross Exterior Wall Assemblies
    24                                     3 stories or    More than
    25     Annual heating degree days     40 ft. or less  3 stories or
    26                                                       40 ft.
    27                  500                    0.38            0.47       <--
    28                 1000                    0.37            0.46
    29                 2000                    0.35            0.43
    30                 3000                    0.33            0.41
    19770H0552B2328                 - 18 -

     1                 4000                    0.31            0.38
     2                 5000                    0.29            0.36
     3                 6000                    0.27            0.33
     4                 7000                    0.26            0.31
     5                 8000                    0.24            0.28       <--
     6                 9000                    0.22            0.28
     7            10,000 or more               0.20            0.28
     8     (c)  Heating criteria for roof/ceiling.--All buildings and
     9  structures that are heated shall have combined thermal
    10  transmittance value (Uo) for roof/ceiling assemblies not
    11  exceeding those specified in Table 7 4.                           <--
    12                             Table 7 4                              <--
    13                   Maximum Allowable "Uo" Values
    14                    for Roof/Ceiling Assemblies
    15     Annual heating degree days              Maximum Uo
    16             3000 and less*                     0.10                <--
    17             4000                               0.092
    18             4000*                              0.092               <--
    19             5000                               0.084
    20             6000                               0.076
    21             7000                               0.068
    22             8000 and more                      0.06                <--
    23     *Table values may be interpolated.
    24     (d)  Heating criteria for floors over unheated spaces.--The
    25  floor of a heated space located over an unheated space shall
    26  have a thermal transmittance value (Uo) not exceeding those       <--
    27  specified in Table 8 0.08.
    28                              Table 8                               <--
    29                 Maximum Allowable "Uo" Values for
    30               Floor Assemblies over Unheated Spaces
    19770H0552B2328                 - 19 -

     1     Annual heating degree days              Maximum Uo
     2                  500*                           0.36
     3                 1000                            0.32
     4                 2000                            0.25
     5                 3000                            0.18
     6                 4000                            0.11
     7                 4500 or more                    0.08
     8     *Table values may be interpolated.
     9     (e)  Heating criteria for slab-on grade floors.--For slab-on
    10  grade floors, the perimeter of the floor shall be insulated with
    11  a material having a thermal resistance value (R) not less than
    12  those specified in Table 9 5.                                     <--
    13     The insulation shall extend downward from the top of the slab
    14  for a minimum distance of 24 inches or downward to the bottom of
    15  the slab then horizontally beneath the slab for a minimum total
    16  distance of 24 inches.
    17                             Table 9 5                              <--
    18             Minimum Allowable "R" Values of Perimeter
    19                Insulation for Slab-On Grade Floors
    20     Annual heating degree days      Heated slab    Unheated slab
    21                  500*                   2.9             --         <--
    22                 1000                    3.3             --
    23                 2000                    4.0             --
    24                 3000                    4.8             2.8
    25                 4000                    5.5             3.5
    26                 4000*                   5.5             3.5        <--
    27                 5000                    6.3             4.2
    28                 6000                    7.0             4.9
    29                 7000                    7.8             5.5
    30                 8000                    8.5             6.2        <--
    19770H0552B2328                 - 20 -

     1                 9000                    9.3             6.8
     2            10,000 or more              10.0             7.5
     3     *Table values may be interpolated.
     4     (f)  Cooling criteria for walls.--All buildings and
     5  structures that are mechanically cooled shall have an overall
     6  thermal transfer value for the gross area of exterior walls not
     7  exceeding those specified in Table 10.                            <--
     8                              Table 10
     9              Maximum Overall Thermal Transfer Values
    10                      for Gross Exterior Walls
    11                                 Maximum overall thermal transfer
    12     Degrees north latitude        value Btuh per square foot
    13             24                              29.0
    14             32                              31.3
    15             40                              33.5
    16             48                              35.7
    17             56                              38.0
    18  33.5 BTU'S PER HOUR PER SQUARE FOOT BASED ON THE FOLLOWING        <--
    19  EQUATION:
    20  OTTV = (UW X AW X TDEQ) + (AF X SF X SC) + (UF X AF X DELTA T)
    21                                     AO
    22  OTTV = OVERALL THERMAL TRANSFER VALUE WHERE:
    23    UW = THE THERMAL TRANSMITTANCE OF ALL ELEMENTS OF THE OPAQUE
    24          WALL AREA BTU/H. FT2.F (W/M2K)
    25    AW = OPAQUE WALL AREA, FT2 (M2)
    26    UF = THE THERMAL TRANSMITTANCE OF THE FENESTRATION AREA
    27          BTU/H. FT2.F (W/M2K)
    28    AF = FENESTRATION AREA, FT2 (M2)
    29  TDEQ = VALUE GIVEN IN THE FOLLOWING TABLE,F(OC):
    30                  TABLE FOR TEMPERATURE DIFFERENCE
    19770H0552B2328                 - 21 -

     1     WALL CONSTRUCTION-MASS PER UNIT AREA        TDEQ
     2             16/FT2          KG/M2           F     C
     3             0-25            0-125           44  24.5
     4            26-40          126-195           37  21.0
     5            41-70          196-345           30  17.0
     6            71 AND ABOVE   346 AND ABOVE     23  13.0
     7     WEIGHT OF WALL CONSTRUCTION SHALL BE DETERMINED FROM THE
     8     1972 ASHRAE HANDBOOK OF FUNDAMENTALS, CHAPTER 22.
     9    SC = SHADING COEFFICIENT OF THE FENESTRATION
    10  DELTA T = TEMPERATURE DIFFERENCE BETWEEN EXTERIOR AND INTERIOR
    11         DESIGN CONDITIONS, F, FOR WHICH THE FOLLOWING
    12         TEMPERATURES SHALL APPLY:
    13                             INDOOR          OUTDOOR
    14                               F  OC
    15             WINTER           72  22.0       97 1/2%
    16             SUMMER           78  25.5       2 1/2%
    17    SF = SOLAR FACTOR VALUE GIVEN BTU/H.FT2 (W/M2).
    18         (USE 127 BTU/H.FT2)
    19    AO = GROSS AREA OF EXTERIOR WALLS, FT2 (M2).  THE GROSS
    20         AREA OF EXTERIOR WALLS CONSISTS OF ALL OPAQUE WALL
    21         AREAS (INCLUDING FOUNDATION WALLS, BETWEEN FLOOR SPAN-
    22         DRELS, PERIPHERAL EDGES OF FLOORS, ETC.), WINDOW
    23         AREAS (INCLUDING SASH), AND DOOR AREAS, WHERE SUCH
    24         SURFACES ARE EXPOSED TO OUTDOOR AIR AND ENCLOSE A
    25         HEATED AND/OR MECHANICALLY COOLED SPACE (INCLUDING
    26         INTERSTICIAL AREAS BETWEEN TWO SUCH SPACES).
    27  NOTE:  WHERE MORE THAN ONE TYPE OF WALL AND/OR FENESTRATION
    28         IS USED, THE RESPECTIVE TERM OR TERMS SHALL BE EXPANDED
    29         INTO SUB-ELEMENTS, AS:
    30         (UW X AW X TDEQ) + (UW2 X AW2 X TDEQ2), ETC.
    19770H0552B2328                 - 22 -

     1     (g)  Cooling criteria for roof/ceilings.--All buildings and
     2  structures that are mechanically cooled shall have a combined
     3  thermal transmittance value (Uo) for roof/ceiling assemblies the
     4  same as specified in Table 7 4 for heating.                       <--
     5  Section 208.  Air leakage.
     6     (a)  Application.--The requirements of this section shall
     7  apply to all buildings and structures and apply only to those
     8  locations separating outdoor ambient conditions from interior
     9  spaces that are heated or mechanically cooled and are not
    10  applicable to separation of interior spaces from each other.
    11     (b)  Standard.--Compliance with the criteria for air leakage
    12  shall be determined by ASTM E-283, Standards Method Test for
    13  Rate of Air Leakage through Exterior Windows, Curtain Walls and
    14  Doors, at a pressure differential of 1.567 lb/ft2 which is
    15  equivalent to the effect of a 25 m.p.h. wind.
    16     (c)  Acceptance criteria.--The following criteria shall
    17  represent the maximum allowable air leakage:
    18         (1)  The air infiltration rate for windows shall not
    19     exceed 0.5 cfm per foot of sash crack.
    20         (2)  The air infiltration rate for sliding glass doors in
    21     residential buildings shall not exceed 0.5 cfm per square
    22     foot of door area.
    23         (3)  The air infiltration rate for swinging doors in
    24     residential buildings shall not exceed 1.25 cfm per square
    25     foot of door area.
    26         (4)  The air infiltration rate for swinging, revolving or
    27     sliding doors in other than residential buildings shall not
    28     exceed 11 cfm per lineal foot of door crack.
    29     (d)  Caulking and sealants.--Exterior joints around windows
    30  and door frames, between wall cavities and window or door
    19770H0552B2328                 - 23 -

     1  frames, between wall and foundation, between wall and roof,
     2  between wall panels, at penetrations or utility services through
     3  walls, floors and roofs, and all other openings in the exterior
     4  envelope shall be caulked, gasketed, weatherstripped, or
     5  otherwise sealed.
     6                            SUBCHAPTER D
     7         WARM AIR HEATING, VENTILATING AND AIR CONDITIONING
     8                       SYSTEMS AND EQUIPMENT
     9  Section 209.  General provisions.
    10     This subchapter applies to air duct systems employing
    11  mechanical means for the movement of air used for warm air
    12  heating, ventilating, air conditioning systems, exhaust systems
    13  and combination heating and air conditioning systems, except
    14  that this subchapter shall not apply to systems for the removal
    15  of flammable vapors or residues or to systems for conveying
    16  dust, stock or refuse by means of air currents. Heating,
    17  ventilating and air conditioning systems of all buildings and
    18  structures or portions thereof shall be designed and installed
    19  for efficient use of energy as herein provided. For special
    20  applications such as hospitals, laboratories, thermally
    21  sensitive equipment, computer rooms, and manufacturing
    22  processes, the design concepts and parameters shall conform to
    23  the requirements of the application at minimum energy levels.
    24  Section 210.  Design requirements.
    25     In determining design conditions for calculations under this
    26  section the following design temperatures shall apply:
    27         (1)  Outdoor design temperature shall be selected for
    28     listed locations in Chapter 33 of the ASHRAE handbook of
    29     Fundamentals, from columns of 97 1/2% values for heating and
    30     2 1/2% values for cooling.
    19770H0552B2328                 - 24 -

     1         (2)  Indoor design temperature shall be 70 degrees F. for
     2     heating and 78 degrees F. for cooling.
     3         (3)  Indoor design relative humidity for heating shall
     4     not exceed 30%. For cooling the actual design relative
     5     humidity within the comfort envelope as defined in ASHRAE
     6     Standard 55-74 "Thermal Environmental Conditions for Human
     7     Occupancy" shall be selected for the minimum total heating,
     8     ventilating, and air conditioning system energy use.
     9  Section 211.  Cooling with outdoor air.
    10     (a)  Fan system design.--Each fan system shall be designed to
    11  use up to and including 100% of the fan system capacity for
    12  cooling with outdoor air automatically whenever its use will
    13  result in lower usage of energy than would be required under its
    14  normal operation.
    15     (b)  Exceptions.--Cooling with outdoor air is not required
    16  under any one or more of the following conditions:
    17         (1)  Fan system capacity less than 5,000 Cfm or 134,000
    18     Btu/Hr total cooling capacity.
    19         (2)  The quality of the outdoor air is so poor as to
    20     require extensive treatment of the air.
    21         (3)  The need for humidification or dehumidification
    22     requires the use of more energy than is conserved by outdoor
    23     air cooling.
    24         (4)  The use of outdoor air cooling may affect the
    25     operation of other systems (such as return or exhaust air
    26     fans or supermarket refrigeration) so as to increase the
    27     overall energy consumption of the building.
    28         (5)  Internal/external zone heat recovery or other energy
    29     recovery is used.
    30         (6)  Annual heating degree days are less than 2,500.       <--
    19770H0552B2328                 - 25 -

     1         (7) (6)  When all space cooling is accomplished by a
     2     circulating liquid which transfers space heat directly or
     3     indirectly to a heat rejection devise such as a cooling tower
     4     without the use of a refrigeration system.
     5  Section 212.  Mechanical ventilation.
     6     Each mechanical ventilation system shall be equipped with a
     7  readily accessible means for either shut-off or volume reduction
     8  and shut-off when ventilation is not required.
     9  Section 213.  Simultaneous heating and cooling.
    10     Systems that employ both heating and cooling simultaneously
    11  in order to achieve comfort conditions within a space shall be
    12  limited to those situations where more efficient methods of
    13  heating and air conditioning cannot be effectively utilized to
    14  meet system objectives. Simultaneous heating and cooling by
    15  reheating or recooling supply air or by concurrent operation or
    16  independent heating and cooling systems serving a common zone
    17  shall be restricted as follows:
    18         (1)  Recovered energy, provided the new energy expended
    19     in the recovery process is less than the amount recovered,
    20     may be used for control of temperature and humidity. New
    21     energy is defined as energy, other than recovered, utilized
    22     for the purpose of heating or cooling.
    23         (2)  New energy may be used, when necessary, to prevent
    24     relative humidity from rising above 60% for comfort control
    25     or to prevent condensation on terminal units or outlets.
    26         (3)  New energy may be used for control of temperature if
    27     minimized as specified in sections 214 through 218.
    28  Section 214.  Reheat systems.
    29     Systems employing reheat and serving multiple zones, other
    30  than those employing variable air volume for temperature
    19770H0552B2328                 - 26 -

     1  control, shall be provided with control that will automatically
     2  reset the system cold air supply to the highest temperature
     3  level that will satisfy the zone requiring the coolest air.
     4  Single zone reheat systems shall be controlled to sequence
     5  reheat and cooling.
     6  Section 215.  Dual duct and multizone systems.
     7     These systems shall be provided with control that will
     8  automatically reset the cold deck air supply to the highest
     9  temperature that will satisfy the zone requiring the coolest air
    10  and the hot deck air supply to the lowest temperature that will
    11  satisfy the zone requiring the warmest air.
    12  Section 216.  Recooling systems.
    13     Systems in which heated air is recooled directly or
    14  indirectly, to maintain space temperature, shall be provided
    15  with control that will automatically reset the temperature to
    16  which the supply air is heated to the lowest level that will
    17  satisfy the zone requiring the warmest air.
    18  Section 217.  Multiple zones.
    19     For systems with multiple zones, one or more zones may be
    20  chosen to represent a number of zones with similar heating or
    21  cooling characteristics. A multiple zone heating, ventilating
    22  and air conditioning system that employs reheating or recooling
    23  for control of not more than 5,000 Cfm or 20% of the total
    24  supply air of the system, whichever is less, shall be exempt
    25  from the supply air temperature reset requirements of sections
    26  214 through 216.
    27  Section 218.  Concurrent operation.
    28     Concurrent operation of independent heating and cooling
    29  systems serving common spaces, and requiring the use of new
    30  energy for heating or cooling shall be minimized by one or both
    19770H0552B2328                 - 27 -

     1  of the following:
     2         (1)  By providing sequential temperature control of both
     3     heating and cooling capacity in each zone.
     4         (2)  By limiting the heating energy input, through
     5     automatic reset control of the heating medium temperature (or
     6     energy input rate), to only that necessary to offset heat
     7     loss due to transmission and infiltration and, where
     8     applicable, to heat the ventilation air supply to the space.
     9  Section 219.  Equipment performance requirements.
    10     (a)  Application.--The requirements of this section apply to
    11  equipment and component performance for heating, ventilating and
    12  air conditioning systems. Where equipment efficiency levels are
    13  specified, data furnished by the equipment supplier or certified
    14  under a nationally recognized certification program or rating
    15  procedure shall be used to satisfy these requirements.
    16     (b)  Electric system equipment.--Heating ventilating and air
    17  conditioning systems equipment whose energy input in the cooling
    18  mode is entirely electric shall slow SHOW a coefficient of        <--
    19  performance (COP) and energy efficiency ratio (EER) not less
    20  than the values specified in Table 11 6. These requirements       <--
    21  apply to, but are not limited to, unitary cooling equipment (air
    22  and water source); packaged air conditioners; and room air
    23  conditioners. These requirements do not apply to equipment used
    24  in areas having open refrigerated food display cases. For
    25  determining coefficient of performance (COP), the rate of net
    26  heat removal shall be defined as the change in the total heat
    27  contents of the air entering and leaving the equipment (without
    28  reheat). Total energy input shall be determined by combining the
    29  energy inputs to all elements of the equipment, including but
    30  not limited to, compressors, pumps, supply-air fans, cooling
    19770H0552B2328                 - 28 -

     1  tower fans and the system equipment control circuit.
     2                             Table 11 6                             <--
     3       Minimum EER and COP for Electric Heating, Ventilating
     4               and Air Conditioning System Equipment
     5  Standard rating capacity                       Eer     Cop
     6  Under 65,000 Btu/hr (19,050 watts)             6.1     1.8
     7  65,000 Btu/hr (19,050 watts) and over          6.8     2.0
     8     (c)  Other system equipment.--Heat operated cooling equipment
     9  shall show a coefficient of performance (COP) in the cooling
    10  mode not less than the values specified in Table 12 7. These      <--
    11  requirements apply to, but are not limited to, absorption,
    12  engine-driven and turbine-driven equipment. The coefficient of
    13  performance (COP) is determined excluding the electrical
    14  auxiliary inputs.
    15                             Table 12 7                             <--
    16     Minimum COP for Heating, Ventilating and Air Conditioning
    17               System Heat Operated Cooling Equipment
    18         Heat source                             Minimum cop
    19  Direct fired (gas, oil)                            0.40
    20  Indirect fired (steam, hot water)                  0.65
    21     (d)  System components.--Heating, ventilating and air
    22  conditioning system components whose energy input in the cooling
    23  mode is entirely electric shall show a coefficient of
    24  performance (COP) and energy efficiency ratio (EER) not less
    25  than the values specified in Table 13 8. For determining          <--
    26  coefficient of performance (COP), the rate of heat removal is
    27  defined as the difference in total heat contents of the water or
    28  refrigerant entering or leaving the component. Total energy
    29  input shall be determined by combining the energy inputs to all
    30  elements and accessories of the component, including but not
    19770H0552B2328                 - 29 -

     1  limited to, compressors, internal circulating pumps, condenser-
     2  air fans, evaporative-condenser cooling heater pumps, purge, and
     3  the component control circuit.
     4                             Table 13 8                             <--
     5      Minimum COP for Electrically Driven Heating, Ventilating
     6               and Air Conditioning System Components
     7     Component                       Air     Water     Evaporation
     8                 Condensing means  Eer Cop  Eer Cop     Eer Cop
     9  Self-contained    Centrifugal    7.5 2.2  12.9 3.8
    10  water chillers
    11                     Positive
    12                   displacement    7.2 2.1  10.9 3.2
    13  Condenserless      Positive
    14  water chillers   displacement    8.9 2.6  10.9 3.2
    15  Compressor and
    16  condenser units    Positive
    17  65,000 Btu/hr.   displacement    7.8 2.3  11.3 3.3   11.3 3.3
    18  (19.050 watts)                                                    <--
    19  (19,050 WATTS)                                                    <--
    20  and over
    21     (e)  Heat pumps.--Heat pumps whose energy input is entirely
    22  electric shall show a coefficient of performance (COP), heating,
    23  not less than the values specified in Table 14 9.                 <--
    24                             Table 14 9                             <--
    25              Minimum COP for Heat Pumps, Heating Mode
    26  Source and outdoor temperature (degree F.)         Minimum cop
    27  Air source--47 DB/43 WB                               2.2
    28  Air source--17 DB/15 WB                               1.2
    29  Water source--60 entering                             2.2
    30     (f)  Supplementary heater.--The heat pump shall be installed
    19770H0552B2328                 - 30 -

     1  with a control to prevent supplementary heater operation when
     2  the heating load can be met by the heat pump alone.
     3  Supplementary heater operation is permitted during transient
     4  periods, such as start-ups, following room thermostat setpoint
     5  advance, and during defrost. A two-stage room thermostat, which
     6  controls the supplementary heat on its second stage, shall be
     7  accepted as meeting this requirement. The cut-on temperature for
     8  the compression heating shall be higher than the cut-on
     9  temperature for the supplementary heat, and the cut-off
    10  temperature for the compression heating shall be higher than the
    11  cut-off temperature for the supplementary heat. Supplementary
    12  heat may be derived from any source of electric resistance
    13  heating or combustion heating.
    14     (g)  Combustion heating equipment.--All gas and oilfired
    15  comfort heating equipment shall show a minimum combustion
    16  efficiency of 75% at maximum rated output. Combustion efficiency
    17  shall be determined in accordance with the ASHRAE Standard 90.
    18  Section 220.  Duct insulation.
    19     (a)  Insulation.--All duct systems, or portions thereof,
    20  exposed to nonconditioned spaces shall be insulated to provide a
    21  thermal resistance, excluding film resistance, of
    22             ti - to
    23         R = --------(hr) (sq.ft) (F)/BTU
    24               15
    25  where ti-to is the design temperature differential (absolute
    26  value) between the air in the duct and the surrounding air with
    27  certain exceptions, duct THE FOLLOWING EXCEPTIONS. DUCT           <--
    28  insulation, except when needed to prevent condensation, is not
    29  required in any of the following cases:
    30         (1)  Where ti-to is 25 degrees F. or less.
    19770H0552B2328                 - 31 -

     1         (2)  When the heat gain or loss of the ducts, without
     2     insulation, will not increase the energy requirements of the
     3     building.
     4         (3)  Exhaust air ducts.
     5         (4)  Supply or return air ducts installed in crawl spaces
     6     with insulated walls, basements or cellars in one and two-
     7     family dwellings.
     8     (b)  Vapor barriers.--Where required to prevent condensation,
     9  insulation with vapor barriers shall be installed in addition to
    10  insulation required above.
    11  Section 221.  System controls.
    12     (a)  Application.--All heating, ventilating and air
    13  conditioning systems shall be provided controls as specified
    14  herein.
    15     (b)  Temperature.--Each heating, ventilating and air
    16  conditioning system shall be provided with at least one
    17  thermostat for the regulation of temperature. Each thermostat
    18  shall be capable of being set from 55 degrees F. to 75 degrees
    19  F. where used to control heating only and from 70 degrees F. to
    20  85 degrees F. where used to control cooling only. Where used to
    21  control both heating and cooling it shall be capable of being
    22  set from 55 degrees F. to 85 degrees F. and shall be capable of
    23  operating the system heating and cooling in sequence. It shall
    24  be adjustable to provide a temperature range of up to 10 degrees
    25  F. between full heating and full cooling, except as allowed in
    26  section 218.
    27     (c)  Humidity.--If a heating, ventilating and air
    28  conditioning system is equipped with a means for adding moisture
    29  to maintain specific selected relative humidities in spaces or
    30  zones, a humidistat shall be provided. This device shall be
    19770H0552B2328                 - 32 -

     1  capable of being set to prevent new energy from being used to
     2  produce space relative humidity above 30% R.H.  Where a
     3  humidistat is used in a heating, ventilating and air
     4  conditioning system for controlling moisture removal to maintain
     5  specific selected relative humidities in spaces or zones, it
     6  shall be capable of being set to prevent new energy from being
     7  used to produce a space relative humidity below 60%.
     8     (d)  Temperature zoning.--
     9         (1)  In all buildings and structures of use group R-3, at
    10     least one thermostat for regulation of space temperature
    11     shall be provided for each separate heating, ventilating and
    12     air conditioning system. In addition, a readily accessible
    13     manual or automatic means shall be provided to partially
    14     restrict or shut-off the heating or cooling input to each
    15     zone or floor, excluding unheated or uncooled basements and
    16     garages.
    17         (2)  In all buildings and structures of use group R-2,
    18     each individual dwelling unit shall be considered separately
    19     and shall meet the requirements for one and two-family
    20     dwellings above.
    21         (3)  In all buildings and structures other than use group
    22     R-3 and in spaces other than dwelling units in use group R-2,
    23     at least one thermostat for regulation of space temperature
    24     shall be provided for each separate heating, ventilating and
    25     air conditioning system and for each floor of the building.
    26     (e)  Set-back and shut-off.--
    27         (1)  In all buildings and structures, or portions thereof
    28     of use group R-3, the thermostat, or an alternate means such
    29     as a switch or a clock, shall provide a readily accessible,
    30     manual or automatic means for reducing the energy required
    19770H0552B2328                 - 33 -

     1     for heating and cooling during periods of nonuse or reduced
     2     need.
     3         (2)  In all other buildings and structures, or portions
     4     thereof each heating, ventilating and air conditioning system
     5     shall be equipped with a readily accessible means of reducing
     6     the energy used for heating, ventilating and air conditioning
     7     during periods of nonuse or alternate uses of the building
     8     spaces or zones served by the system, such as with manually
     9     adjustable automatic timing devices, manual devices for use
    10     by operating personnel, or automatic control systems.
    11         (3)  Lowering thermostat set points to reduce energy
    12     consumption of heating systems shall not cause energy to be
    13     expended to reach the reduced setting.
    14  Section 222.  Steam and hot water heating piping.
    15     (a)  Piping insulation.--All piping serving as part of a
    16  heating or cooling system installed to serve buildings and
    17  within buildings shall be thermally insulated as shown in Table
    18  15 10.                                                            <--
    19                            Table 15 10                             <--
    20                      Minimum Pipe Insulation
    21                                 Insulation thickness in inches
    22             Fluid                       for pipe sizes
    23  Piping  temperature
    24  system     range,   Runouts  1" and  1 1/4-  2 1/2-  5&   8" and
    25  types        F.     up to 2"  less     2       4     6    larger
    26  Heating systems
    27     Steam &
    28     hot water
    29  High pressure/
    30  temp       306-450   1 1/2     1 1/2    2    2 1/2  3 1/2  3 1/2
    19770H0552B2328                 - 34 -

     1  Med. pressure/
     2  temp       251-305   1 1/2     1 1/2    2    2 1/2  3      3
     3  Low pressure/
     4  temp       201-250   1         1       1 1/2 1 1/2  2      2
     5  Low tem-
     6  perature   120-200    1/2       3/4     1    1      1      1 1/2
     7  Steam con-
     8  densate      Any     1         1        1    1 1/2  1 1/2  2
     9  (for feed
    10  water)
    11  Cooling systems
    12  Chilled
    13  water,      40-55     1/2       1/2      3/4 1      1      1
    14  Refrigerant,
    15  or brine  Below 40   1         1       1 1/2  1 1/2 1 1/2  1 1/2
    16  Insulation thicknesses are based on insulation having thermal
    17  resistances in the range of 4.0 to 4.6 per inch of thickness on
    18  a flat surface at a mean temperature of 75 degrees F. Minimum
    19  insulation thickness shall be increased for materials having R
    20  values less than 4.0 or may be reduced for materials having R
    21  values greater than 4.6 per inch of thickness as follows:
    22     (b)  High thermal resistance.--For materials with thermal
    23  resistance greater than R=4.5, the minimum insulation thickness
    24  may be reduced as follows:
    25         4.6 x Table 15 10 Thickness    =   New Minimum Thickness   <--
    26               Actual R
    27     (c)  Low thermal resistance.--For materials with thermal
    28  resistance less than R=4.0 the minimum insulation thickness
    29  shall be increased as follows:
    30         4.0 x Table 15 10 Thickness    =   New Minimum Thickness   <--
    19770H0552B2328                 - 35 -

     1               Actual R
     2  Piping insulation, except when needed to prevent condensation,
     3  is not required in any of the following cases:
     4         (1)  Piping installed within heating, ventilating and air
     5     conditioning equipment.
     6         (2)  Piping at temperatures between 55 degrees F. and 120
     7     degrees F.
     8         (3)  When the heat loss or heat gain of the piping,
     9     without insulation, does not increase the energy requirements
    10     of the building.
    11         (4)  Piping installed in basements or cellars in one and
    12     two-family dwellings.
    13     (d)  Vapor barriers.--Where required to prevent condensation,
    14  insulation with vapor barriers shall be installed in addition to
    15  insulation required above.
    16                            SUBCHAPTER E
    17                          PLUMBING SYSTEMS
    18  Section 223.  Purpose.
    19     This subchapter sets forth provisions for design and
    20  equipment selection for energy conservation in service water
    21  heating systems.
    22  Section 224.  Fixtures.
    23     (a)  Lavatories.--Lavatories in restrooms of public
    24  facilities shall be equipped with self-closing outlet devices
    25  which limit the flow of hot water to a maximum of 0.5 Gpm,
    26  devices which limit the outlet temperature to a maximum of 110
    27  degrees F. and selfclosing valves which limit the quantity of
    28  hot water to a maximum of 0.25 gallons.
    29     (b)  Showers.--Showers used for other than safety reasons
    30  shall be equipped with flow control devices to limit total flow
    19770H0552B2328                 - 36 -

     1  to a maximum of 3 Gpm per shower head.
     2  Section 225.  Insulation.
     3     (a)  Piping insulation.--Piping in required return
     4  circulation systems shall be insulated so that heat loss is
     5  limited to a maximum of 25 Btuh per square foot of external pipe
     6  surface for above ground piping and a maximum of 35 Btuh per
     7  square foot of external pipe surface for underground piping.
     8  Maximum heat loss shall be determined at a temperature
     9  differential equal to the maximum water temperature minus a
    10  design ambient temperature no higher than 65 degrees F. except
    11  that conformance with table 15 10 for "low temperature piping     <--
    12  system" shall be deemed as complying with this section.
    13     (b)  Tanks.--Unfired hot water storage tanks shall be
    14  insulated so that heat loss is limited to a maximum of 15 Btuh
    15  per square foot of external tank surface area. For purposes of
    16  determining this heat loss, the design ambient temperature shall
    17  be no higher than 65 degrees F.
    18  Section 226.  Equipment.
    19     (a)  Pump operation.--Circulating hot water systems shall be
    20  arranged so that the circulating pump can be conveniently turned
    21  off either automatically or manually when the hot water system
    22  is not in operation.
    23     (b)  Electric water heaters.--All automatic electric storage
    24  water heaters shall have a stand-by loss not exceeding 4 watts
    25  per square foot of tank surface area. The method of test of
    26  stand-by loss shall be as described in section 4.3.1 of ANSI
    27  C72.1 Household Automatic Electrical Storage-Type Water Heaters.
    28     (c)  Gas and oil-fired water heaters.--All gas and oil-fired
    29  automatic storage heaters shall have a recovery efficiency, ER,
    30  not less than 75% and a stand-by loss percentage S, not
    19770H0552B2328                 - 37 -

     1  exceeding S=2.3+67/V where V=rated volume in gallons. The method
     2  of test of ER and S shall be as described in section 2.7 of ANSI
     3  Z21.10.3 Circulating Tank, Instantaneous and Large Automatic
     4  Storage Type Water Heaters, Approval Requirements for Gas Water
     5  Heaters.
     6  Section 227.  Controls.
     7     (a)  Temperature controls.--All hot water supply systems
     8  shall be equipped with automatic temperature controls capable of
     9  adjustments from the lowest to the highest acceptable
    10  temperature settings for the intended use.
    11     (b)  Shut down.--A separate switch shall be provided to
    12  terminate the energy supplied to electric hot water supply
    13  systems. A separate valve shall be provided to turn off the
    14  energy supplied to the main burner of all other types of hot
    15  water supply systems.
    16                            SUBCHAPTER F
    17                         ELECTRICAL SYSTEMS
    18  Section 228.  System requirements.
    19     (a)  Power factor.--The power factor of the overall
    20  electrical distribution system in a building shall be not less
    21  than 90% under rated design installed load of the building,
    22  either by utilization equipment design or by the use of power
    23  factor corrective devices. The power factor corrective devices
    24  may be installed on individual equipment, rated greater than
    25  1,000 watts and switched therewith, regionally grouped, located
    26  at the service equipment or power factor correction achieved by
    27  other equivalent means. The choice among these corrective
    28  methods should be made based upon an engineering evaluation of
    29  each distribution system.
    30     (b)  Service voltage.--Where a choice of service voltage is
    19770H0552B2328                 - 38 -

     1  available, the voltage resulting in the least energy loss shall
     2  be used.
     3     (c)  Voltage drop.--In any building, the maximum total
     4  voltage drop shall not exceed 3% in branch circuits or feeders,
     5  for a total of 5% to the farthest outlet based on steady state
     6  design load conditions.
     7     (d)  Lighting switching.--Switching shall be provided for
     8  each lighting circuit, or for portions of each circuit, so that
     9  the partial lighting required for custodial or for effective
    10  complementary use with natural lighting may be operated
    11  selectively.
    12     (e)  Separate metering.--In all multi-family dwelling          <--
    13  DWELLINGS provisions shall be made to determine the electrical    <--
    14  energy consumed by each tenant.
    15                            SUBCHAPTER G
    16                              LIGHTING
    17  Section 229.  Light power budget.
    18     A lighting power budget is the upper limit of the power to be
    19  available to provide the lighting needs in accordance with a
    20  given set of criteria and given calculation procedure.
    21  Section 230.  Calculation methods.
    22     The criteria specified below shall be utilized for
    23  computation of the lighting power budget. All calculations shall
    24  be in accordance with accepted engineering practice. When
    25  insufficient information is known about the specific use of the
    26  building space (e.g., number of occupants, space function,
    27  location of partitions), the budget shall be based on the
    28  apparent intended use of the building space.
    29  Section 231.  Building interiors.
    30     (a)  Procedure.--The allowable electric power for lighting
    19770H0552B2328                 - 39 -

     1  shall be established by using the criteria and the calculation
     2  procedures specified in section 234. The value shall be based on
     3  the use for which the space within the building is intended and
     4  on efficient energy utilization.
     5     (b)  Illumination level criteria.--For the purpose of
     6  establishing a budget, levels of illumination shall be those
     7  listed in fig. 9-80 of the IES Lighting Handbook, and those
     8  levels shall be used as follows:
     9         (1)  For task lighting, the levels of illumination listed
    10     are for specific tasks. These levels are for the task areas
    11     defined in the IES Lighting Handbook or, where not defined,
    12     at all usable portions of task surfaces. In some cases, the
    13     levels of illumination are listed for locations (e.g.,
    14     auditoriums). These levels are to be considered as average
    15     levels.
    16         (2)  For general lighting, in areas surrounding task
    17     locations, the average level of general lighting, for budget
    18     purposes only, shall be one-third the level for the tasks
    19     performed in the area but in no case less than 20-foot
    20     candles. Where more than one task level occurs in a space,
    21     the general level shall be one-third the weighted average of
    22     the specific task levels.
    23         (3)  For noncritical lighting, in circulation and seating
    24     areas, where no specific visual task TASKS occur, the average  <--
    25     level of illumination shall be one-third of the average
    26     general lighting in the adjacent task spaces but in no case
    27     less than ten-foot candles.
    28         (4)  For the purpose of establishing a power budget, only
    29     lamp efficacies and coefficients of utilization (CU)
    30     specified in Table 16 11, shall be assumed.                    <--
    19770H0552B2328                 - 40 -

     1  Section 232.  Building exteriors.
     2     (a)  Basis on use.--In exterior spaces, the lighting power
     3  budget shall be based on the use of which the space is intended
     4  (for task performance, safety, or security) and on efficient
     5  energy utilization.
     6     (b)  Criteria.--The same criteria as those for interior
     7  spaces apply for illumination levels and lighting systems with
     8  the addition of luminaires for flood lighting. For power budget
     9  purposes floodlighting shall be selected with luminaires having
    10  a greater percentage of their beam lumens restricted to the area
    11  to be lighted. Such luminaires are defined as those with at
    12  least the minimum efficiencies listed in the IES Lighting
    13  Handbook.
    14     (c)  Facade lighting.--Facade lighting for budget purposes
    15  shall be no greater than 2% of the total interior load of the
    16  building.
    17     (d)  Calculation procedure.--In establishing a lighting power
    18  budget the following procedures shall be used:
    19         (1)  For overhead lighting the procedure specified in
    20     section 234 shall be followed, but using reflectances as
    21     found.
    22         (2)  For flood lighting the beam lumen method, as shows
    23     in the IES Lighting Handbook and a coefficient of beam
    24     utilization (CBU) of 0.75 shall be used for floodlighting
    25     calculations.
    26  Section 233.  Exceptions to criteria.
    27     (a)  Interiors.--The criteria of section 231 shall not apply
    28  to the following areas when calculating the load.
    29         (1)  Portions of residential occupancies except for
    30     kitchens, bathrooms, and laundry areas and public spaces
    19770H0552B2328                 - 41 -

     1     including lobbies, halls, stairways, basement areas, and
     2     utility rooms.
     3         (2)  Residential type spaces similar to those stated in
     4     paragraph (1) in institutions, such as hospitals, hotels,
     5     funeral homes, churches, museums, etc.
     6         (3)  Theater auditoriums, entertainment and audiovisual
     7     presentations where the lighting is an essential technical
     8     element for the function performed.
     9     (b)  Exteriors.--The criteria of section 232 shall not apply
    10  to the following lamps and luminaries; however, their use shall
    11  be accounted for in the calculation of task lighting loads for
    12  specific tasks. The allowable load shall be based on the
    13  luminary wattage to achieve the levels of illumination as
    14  covered in section 231 using a point calculation method given in
    15  the IES Lighting Handbook. The excepted lamps and luminaries are
    16  as follows:
    17         (1)  Luminaries for medical and dental purposes.
    18         (2)  Luminaries for highlighting applications, such as
    19     sculpture exhibits, art exhibits, and individual items of
    20     display merchandise.
    21         (3)  Luminaries for specialized lighting applications
    22     (color matching, where electrical interference cannot be
    23     tolerated, etc.).
    24     (c)  Control of reflectances.--The criteria of Table 16 11     <--
    25  shall not apply in spaces where it is impractical to control
    26  reflectances and where a dirty atmosphere cannot be avoided.
    27  Where this condition exists, the values for reflectances and
    28  light loss factors shall be those expected to be found and shall
    29  be approved by the department. The calculation shall make a note
    30  of this deviation.
    19770H0552B2328                 - 42 -

     1  Section 234.  Calculation procedure.
     2     (a)  Illumination levels and areas.--To establish
     3  illumination levels and areas, the following procedure shall be
     4  used:
     5         (1)  Determine the visual tasks that are expected to be
     6     performed in each space and the number of planned work
     7     locations where tasks will be performed. If assumptions are
     8     made, their bases shall be indicated.
     9         (2)  Select the illumination level, in foot-candles for
    10     those expected tasks in accordance with section 231(b)(1).
    11         (3)  Calculate total task areas to be illuminated to the
    12     same level by multiplying the number of work locations by 50
    13     square feet per work location. (Total task areas shall not
    14     exceed actual total space area). If actual task area is
    15     greater than 50 square feet the actual area shall be used. If
    16     special task lighting or localized lighting is to be
    17     employed, use the actual task areas and point calculation
    18     procedures.
    19         (4)  Calculate the level of general lighting by
    20     multiplying the task lighting level by one-third, where there
    21     is only one task level, or by taking one-third of the sum of
    22     the products of the task levels as provided for in paragraph
    23     (2) and their areas as provided for in paragraph (3) divided
    24     by the total task areas.
    25         (5)  Calculate the level of noncritical lighting.
    26     (b)  Lighting system data.--To establish lighting system
    27  data, the following shall be used:
    28         (1)  Light source and luminaire types to use.
    29         (2)  Lamp lumens per watt and luminaire coefficients of
    30     utilization for room and luminaire mounting height
    19770H0552B2328                 - 43 -

     1     dimensions. Luminaire CUs shall be selected from the IES
     2     Lighting Handbook. In all cases, no luminaire shall have a CU
     3     for RCR = 1 of less than that given in Table 16 11 lamp        <--
     4     efficacies for the appropriate space.
     5     (c)  Allowable wattage.--To establish allowable wattage, the
     6  following shall be used:
     7         (1)  Using data from subsection (b), the illumination
     8     levels and areas determined in subsection (a), and the
     9     criteria of Table 16 11 on Reflectance, calculate the          <--
    10     allowable wattages using the lumen method.
    11         (2)  Calculate the total space wattage by adding the
    12     task, general and noncritical lighting loads.
    13         (3)  Add the wattage of luminaries allowed in section
    14     233(b).
    15                            Table 16 11                             <--
    16     (a)  Lamp efficacies.--The following are initial lumen output
    17  per watt input, including ballast losses:
    18                 Application                             Lumens
    19                                                        per Watt
    20     Where moderate color rendition is appropriate         55
    21     Where good color rendition is appropriate             40
    22     Where high color rendition is appropriate,
    23     spaces are less than 50 square feet or where
    24     use of low wattage High Intensity Discharge
    25     (HID) lamps under 250 W or fluorescent
    26     lamps under 40 W is appropriate                       25
    27     (b)  Luminary coefficients of utilization (CU).--Coefficients
    28  of utilization (CUs) are to be for luminaries for use in the
    29  types of spaces listed below, and those luminaries shall have a
    30  CU of no less than that listed below (for each type space) for a
    19770H0552B2328                 - 44 -

     1  Room Cavity Ratio (RCR) of 1 and reflectances as in (c).
     2                 Space Use                           Minimum CU
     3                                                    (at RCR - 1)    <--
     4                                                    (AT RCR = 1)    <--
     5     For spaces with tasks subjected to veiling
     6     reflections where design levels of
     7     illumination are listed in terms of
     8     equivalents EQUIVALENT sphere illumination (ESI) and           <--
     9     where visual comfort is important.                  0.55
    10     For spaces without tasks, or with tasks
    11     not subjected to veiling reflections, but
    12     where visual comfort is important.                  0.63
    13     For spaces without tasks and where visual
    14     comfort is not a criterion                          0.70
    15     (c)  Other criteria; reflectances.--For interior spaces, the
    16  following initial cavity and surface reflectances shall be
    17  assumed:
    18     Ceiling cavity reflectance              80%
    19     Wall reflectance                        50%
    20     Floor cavity reflectance                20%
    21  Light Loss Factor.  A light loss factor (LLF) of 0.70 shall be
    22  used.
    23                            SUBCHAPTER H
    24                        ALTERNATIVE SYSTEMS
    25  Section 235.  Performance alternative.
    26     Alternative building systems and equipment design may be
    27  approved by the department when they can be shown to have energy
    28  consumption not greater than that of a similar building with
    29  similar forms of energy requirements, designed in accordance
    30  with the provisions of this act OR WHEN THEY CAN BE SHOWN TO      <--
    19770H0552B2328                 - 45 -

     1  HAVE ENERGY CONSUMPTION NOT GREATER THAN THAT WHICH SHALL BE
     2  ESTABLISHED BY THE DEPARTMENT WITH THE APPROVAL OF THE BUILDING
     3  ENERGY CONSERVATION COMMITTEE, FOR THE PURPOSES OF THIS SECTION.
     4  Section 236.  Nondepletable sources.
     5     When such alternative systems utilize solar, geothermal, wind
     6  or other nondepletable energy sources for all or part of its
     7  energy sources, such nondepletable energy supplied to the
     8  building shall be excluded from the total energy chargeable to
     9  the proposed alternative design.
    10  Section 237.  Documentation.
    11     Proposed alternative designs, submitted as requests for
    12  exception to the standard design criteria, must be accompanied
    13  by an energy analysis prepared in accordance with the ASHRAE
    14  Standard 90 90-75.                                                <--
    15                             CHAPTER 3
    16              APPLICATION OF STANDARDS: ESTABLISHMENT
    17                     OF COMMITTEE AND PENALTIES
    18  Section 301.  Modification of standards; criteria.
    19     The department, with the approval of the Building Energy
    20  Conservation Committee, established pursuant to section 304,
    21  after one or more public hearings, may recommend to the General
    22  Assembly modifications to the energy conservation standards
    23  CONTAINED IN CHAPTER 2 HEREOF. Any recommended modification to    <--
    24  the energy conservation standards shall meet the following
    25  criteria:
    26         (1)  It shall be consistent with the latest and most
    27     effective technology.
    28         (2)  It shall not be in conflict with existing safeguards
    29     for public health and safety.
    30         (3)  It shall be economically feasible as determined by
    19770H0552B2328                 - 46 -

     1     life-cycle-cost procedures.
     2         (4)  It shall be sufficiently stringent to effect a
     3     significant savings of energy resources.
     4         (5)  It shall be a performance standard for the design of
     5     buildings and systems within buildings to assure maximum
     6     practical conservation of energy.
     7         (6)  Consideration shall be given to building and energy
     8     standards promulgated by National and other state
     9     governmental agencies, private organizations and any other
    10     available energy data, as well as the total energy allocation
    11     approach.
    12  Section 302.  Application of energy conservation standards.
    13     The energy conservation standards contained herein OR AS       <--
    14  PROMULGATED BY THE DEPARTMENT WITH THE APPROVAL OF THE BUILDING
    15  ENERGY CONSERVATION COMMITTEE shall apply to new buildings or to
    16  renovations on which actual construction and/or design has not
    17  commenced prior to their effective date DATES.                    <--
    18  Section 303.  Energy conservation manual for buildings.
    19     (a)  Production of manual.--Concurrent with the adoption of
    20  the energy conservation code CODES required by this act, the      <--
    21  department shall produce an energy conservation manual for use
    22  by designers, builders, and contractors of residential and
    23  nonresidential buildings. This manual shall contain the
    24  established standards and accepted practices. The manual shall
    25  be furnished upon request to members of the public at a price
    26  sufficient to cover the cost of printing.
    27     (b)  Review of manual.--The manual shall be reviewed by the
    28  department and the Building Energy Conservation Committee at
    29  least annually and shall be updated as significant new energy
    30  conservation information becomes available.
    19770H0552B2328                 - 47 -

     1  Section 304.  Building Energy Conservation Committee.
     2     (a)  Composition of committee.--In order to further the
     3  coordinated and effective administration of this act, there is
     4  hereby established a Building Energy Conservation Committee. It
     5  shall consist of at least 15 25 members and no more than 25 35    <--
     6  members, the membership of which shall be appointed by the
     7  Secretary of Labor and Industry GOVERNOR and shall include a      <--
     8  representative of each of the following entities or their
     9  successors:
    10         (1)  Department of Education.
    11         (2)  Governor's Energy Council.
    12         (3)  Department of General Services.
    13         (4)  Department of Labor and Industry.
    14         (5)  Department of Community Affairs.
    15         (6)  Pennsylvania Builders Association.
    16         (7)  Pennsylvania Associated Builders and Contractors,
    17     Inc.
    18         (8)  Pennsylvania Building Officials Conference.
    19         (9)  Mechanical Contractors Association of America.
    20         (10)  Pennsylvania Chamber of Commerce.
    21         (11)  General Contractors Association of Pennsylvania.
    22         (12)  Pennsylvania Society of Architects.
    23         (13)  Pennsylvania Society of Professional Engineers.
    24         (14)  AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR   <--
    25     CONDITIONING ENGINEERS, INC..
    26         (15)  PENNSYLVANIA GAS ASSOCIATION.
    27         (16)  PENNSYLVANIA ELECTRIC ASSOCIATION.
    28         (17)  INDUSTRIALIZED HOUSING MANUFACTURERS ASSOCIATION.
    29         (18)  THERMAL INSULATION MANUFACTURERS ASSOCIATION.
    30         (14) (19)  Representatives of such other agencies and      <--
    19770H0552B2328                 - 48 -

     1     organizations or individuals as the secretary GOVERNOR may     <--
     2     find are necessary and proper to carry out the purposes of
     3     the committee including, but not limited to, labor
     4     organizations, financial and lending institutions, and
     5     organizations directly involved in the supply of energy        <--
     6     throughout the Commonwealth. CONSUMER GROUPS.                  <--
     7     (b)  Powers and duties.--In addition to the powers and duties
     8  enumerated in this act, the Building Energy Conservation
     9  Committee shall perform the following duties:                     <--
    10         (1)  The committee shall be responsible for the regular
    11     exchange of information and plans regarding building energy
    12     conservation, for the development, and review REVIEW AND       <--
    13     APPROVAL of proposed and existing standards, guidelines,
    14     regulations, and manuals. and shall make recommendations to    <--
    15     the Industrial Board of the Department of Labor and  Industry
    16     consistent with the provisions of this act.
    17         (2)  Said committee shall act as an advisory committee to
    18     the Industrial Board of the Department of Labor and Industry
    19     and the Advisory Board in the Department of Labor and
    20     Industry in matters of building energy conservation and may
    21     recommend to the Industrial Board variances from standards,
    22     guidelines, regulations and manuals after consultation within
    23     the committee or with any person affected by such standards,
    24     guidelines, regulations or manuals.
    25     (c)  Expenses.--The members of the committee shall not
    26  receive any compensation for their services but shall be
    27  reimbursed for their actual and necessary expenses incurred in
    28  the performance of their duties. Provided, however, when acting
    29  as an advisory committee to the Industrial Board or the Advisory  <--
    30  Board on matters concerning variances which have been referred    <--
    19770H0552B2328                 - 49 -

     1  to the Industrial Board, they shall receive $50 per day plus
     2  their actual and necessary expenses.
     3  Section 305.  Certification.
     4     (a)  Compliance with act.--It shall be the duty of the
     5  architect retained in connection with the DESIGN, construction    <--
     6  or renovation of a building to certify the drawings,
     7  specifications and other data showing compliance with the
     8  provisions of this act.
     9     (b)  Inspection.--Each architect, or his OTHER LICENSED        <--
    10  DESIGN PROFESSIONAL RETAINED BY THE OWNER IN LIEU OF AN
    11  ARCHITECT, OR THE ARCHITECT'S designee shall make periodic
    12  inspections of the building progression to insure compliance
    13  with this act.
    14     (c)  Final certification.--Each architect OR OTHER LICENSED    <--
    15  DESIGN PROFESSIONAL RETAINED BY THE OWNER IN LIEU OF AN
    16  ARCHITECT shall make a final certification of every completed
    17  building showing compliance with the provisions of this act.
    18     (d)  Certification by builder; bonds.--If an architect OR      <--
    19  OTHER LICENSED DESIGN PROFESSIONAL is not retained in connection
    20  with the DESIGN, construction or renovation of a building, it     <--
    21  shall be the responsibility of the builder to perform the
    22  inspections and certification required by this section. and to    <--
    23  file with the department an indemnity bond in such amount as the
    24  department shall require indemnifying the owner for any costs
    25  said owner may incur in bringing the building into compliance
    26  with this act, should the department find it to be in
    27  noncompliance. Said indemnity bond shall remain in full force
    28  and effect for a period of two years from the date of completion
    29  of the construction or renovation of the building.
    30  Section 306.  Variances.
    19770H0552B2328                 - 50 -

     1     (a)  Requests.--Any request for a variance from the energy
     2  conservation standards contained herein shall be made to the
     3  Industrial Board of the Department of Labor and Industry.         <--
     4  BUILDING ENERGY CONSERVATION COMMITTEE.                           <--
     5     (b)  Criteria.--A variance shall be granted only if it is
     6  found that:
     7         (1)  compliance with the provisions of this act would
     8     result in extreme hardship to the owner; and
     9         (2)  the granting of such variance would not result in a
    10     significant increase in the energy usage of the building.
    11  Section 307.  Building permits.
    12     Any building permit issued by the Commonwealth or any of its
    13  political subdivisions shall have printed upon its face notice
    14  that the provisions of this act must be complied with.
    15  Section 308.  Permits for use or occupancy.
    16     Before any building or structure hereafter constructed or
    17  renovated shall be used or opened for occupancy, the owner
    18  thereof shall notify the department of Labor and Industry of the  <--
    19  completion of the building and submit the necessary
    20  certification therewith. WITHIN 30 DAYS OF RECEIPT OF THE         <--
    21  CERTIFICATION THE DEPARTMENT SHALL FORWARD NOTICE OF RECEIPT OF
    22  SUCH CERTIFICATION TO THE OWNER. No permit for use or occupancy
    23  shall be granted until such submission has been made. No
    24  building official of the Commonwealth or any of its political
    25  subdivisions shall issue a permit until he has received proof of
    26  compliance.
    27  Section 309.  Failure to submit certification.
    28     Whenever the owner of any building or structure shall fail to
    29  notify the department of the completion of the building and to
    30  submit the necessary certification and shall nevertheless
    19770H0552B2328                 - 51 -

     1  proceed with the use or occupancy of the building, the
     2  department or the political subdivision shall serve notice on
     3  the said owner to immediately cease using or occupying said       <--
     4  building and a notice shall be placed on the premises
     5  prohibiting such use or occupancy until such certification has
     6  been submitted. THAT HE IS IN VIOLATION OF THIS ACT AND ORDER     <--
     7  HIM TO COMPLY THEREWITH.
     8  Section 310.  Inspections.
     9     The department may inspect within two years of the date of
    10  completion of construction or renovation any building
    11  constructed or renovated after the effective date of this act to
    12  determine compliance with the provisions of this act.
    13  Section 311.  Failure to comply with provisions of this act.      <--
    14     Whenever the owner of any building, as described in this act,
    15  shall fail to comply with the provisions of this act, or the
    16  rules and regulations of the department formulated under the
    17  authority of this act, and upon whom a written order shall be
    18  served by the department to comply with the said provisions of
    19  this act and the rules and regulations of the department and who
    20  nevertheless shall have failed to comply with the said written
    21  order within the time specified in the same, the department
    22  shall be authorized to immediately order the building or
    23  structure to be vacated or placed out of service until such time
    24  as the requirements of this act and the rules and regulations of
    25  the department shall have been fully complied with.
    26  Section 312 311.  Appeals.                                        <--
    27     Review of any decisions rendered under the provisions of this
    28  act shall be brought in the court of common pleas of the county
    29  wherein the building is situated. Such review shall be limited
    30  to determining whether any such decision was arbitrary and
    19770H0552B2328                 - 52 -

     1  capricious.
     2  Section 313 312.  Penalties.                                      <--
     3     (a)  Violations of act.--Any person who shall violate any of
     4  the provisions of this act, or the rules and regulations or the
     5  orders for the enforcement of the said provisions or rules and
     6  regulations issued by duly authorized officers of the department
     7  or who shall hinder, delay or interfere with any officer charged
     8  with the enforcement of this act in the performance of his duty,
     9  shall, upon conviction thereof, be punished by a fine of NOT      <--
    10  MORE THAN $300 and costs, or not more than three months
    11  imprisonment in the county jail, or either, or both, in the
    12  discretion of the court. IN THE EVENT OF VIOLATION OF MORE THAN   <--
    13  ONE PROVISION OF THIS ACT, THE VIOLATION OF EACH PROVISION SHALL
    14  BE DEEMED A SEPARATE AND DISTINCT OFFENSE FOR THE PURPOSES OF
    15  THIS SECTION.
    16     (b)  Refusal to vacate.--Any person who shall fail or refuse   <--
    17  to vacate a building or portion of a building, or who shall fail
    18  to vacate or place out of service any building, after due notice
    19  having been served upon him by an officer of the department and
    20  proper notice having been placed upon the building or structure
    21  by such officer, shall be liable for a penalty of $100 a day for
    22  each day he shall have so failed or refused to vacate, or place
    23  out of service the building, portion of building upon which such
    24  notice has been placed, the said penalty to be collectible in
    25  the same manner as any fine payable to the Commonwealth.
    26     (c) (B)  Institution of proceedings.--Prosecutions for         <--
    27  violations of this act, or the rules and regulations of the
    28  department may be instituted by the Secretary of Labor and
    29  Industry OR THE SECRETARY OF COMMUNITY AFFAIRS, or under his      <--
    30  directions by an authorized representative of the department.
    19770H0552B2328                 - 53 -

     1  Upon conviction after a hearing the sentences provided in this
     2  act shall be imposed, and shall be final unless an appeal be
     3  taken in the manner prescribed by law.
     4     (d) (C)  Disposition of fines.--All fines collected under      <--
     5  this act shall be forwarded to the department who shall pay the
     6  same into the State Treasury for the use of the Commonwealth.
     7     (e) (D)  False certification.--Any architect OR OTHER          <--
     8  LICENSED DESIGN PROFESSIONAL who willfully provides a false
     9  certification for any building subject to the provisions of this
    10  act shall be subject to the suspension or revocation of his
    11  license by the State Board of Examiners of Architects OR OTHER    <--
    12  APPLICABLE STATE LICENSING BOARD.
    13  Section 314 313.  Enforcement.                                    <--
    14     (a)  Applicability.--The provisions of this act shall apply
    15  to every building enumerated in this act, except buildings owned
    16  by the Federal Government, including buildings owned in whole or
    17  in part by the Commonwealth or any political subdivision
    18  thereof, and shall be enforced by the Secretary of Labor and
    19  Industry OR BY THE SECRETARY OF COMMUNITY AFFAIRS, by and         <--
    20  through his authorized representatives.
    21     (b)  Powers of officers.--For the purpose of enforcing the
    22  provisions of this act, all the officers charged with its
    23  enforcement shall have the power to enter any of the buildings
    24  enumerated in this act, and no person shall hinder or delay, or
    25  interfere with any of the said officers in the performance of
    26  his duty, nor refuse any pertinent information necessary to
    27  determine whether the provisions of this act and the rules and
    28  regulations herein provided for, are or will be complied with.
    29                             CHAPTER 4                              <--
    30                       DEPARTMENT'S STANDARD
    19770H0552B2328                 - 54 -

     1  SECTION 401.  ADOPTION AND PROMULGATION OF STANDARDS.
     2     THE DEPARTMENT, WITH THE APPROVAL OF THE BUILDING ENERGY
     3  CONSERVATION COMMITTEE, SHALL, AFTER ONE OR MORE PUBLIC
     4  HEARINGS, ADOPT AND PUBLISH ENERGY CONSERVATION STANDARDS FOR
     5  ALL BUILDINGS COVERED BY THIS ACT IN ACCORDANCE WITH THE
     6  PROVISIONS OF THE ACT OF JULY 31, 1968 (P.L.769, NO.240), KNOWN
     7  AS THE "COMMONWEALTH DOCUMENTS LAW," THE PURPOSE OF SUCH
     8  STANDARDS IS TO REDUCE WASTEFUL OR UNECONOMIC CONSUMPTION OF
     9  ENERGY BY BALANCING THE COST OF ENERGY PROCUREMENT AGAINST THE
    10  COST OF ENERGY-CONSERVING BUILDING PRACTICES. THE ENERGY
    11  CONSERVATION STANDARDS SHALL MEET THE FOLLOWING CRITERIA:
    12         (1)  THEY SHALL BE CONSISTENT WITH THE LATEST AND MOST
    13     EFFECTIVE TECHNOLOGY.
    14         (2)  THEY SHALL NOT BE IN CONFLICT WITH EXISTING
    15     SAFEGUARDS FOR PUBLIC HEALTH AND SAFETY.
    16         (3)  THEY SHALL BE ECONOMICALLY FEASIBLE AS DETERMINED BY
    17     LIFE-CYCLE-COST PROCEDURES.
    18         (4)  THEY SHALL BE SUFFICIENTLY STRINGENT TO EFFECT A
    19     SIGNIFICANT SAVINGS OF ENERGY RESOURCES.
    20         (5)  THEY SHALL BE A PERFORMANCE STANDARD FOR THE DESIGN
    21     OF BUILDINGS AND SYSTEMS WITHIN BUILDINGS TO ASSURE MAXIMUM
    22     PRACTICAL CONSERVATION OF ENERGY.
    23         (6)  CONSIDERATION SHALL BE GIVEN TO BUILDING AND ENERGY
    24     STANDARDS PROMULGATED BY NATIONAL AND OTHER STATE
    25     GOVERNMENTAL AGENCIES, PRIVATE ORGANIZATIONS AND ANY OTHER
    26     AVAILABLE ENERGY DATA, AS WELL AS THE TOTAL ENERGY ALLOCATION
    27     APPROACH.
    28  Section 315 402.  Effective date.                                 <--
    29     This act shall take effect as follows:
    30         (1)  Chapter 2 shall take effect in six months.            <--
    19770H0552B2328                 - 55 -

     1         (2)  All other provisions of this act shall take effect
     2     immediately.
     3         (1)  CHAPTER 2 SHALL TAKE EFFECT IN SIX MONTHS AND SHALL   <--
     4     REMAIN IN FULL FORCE AND EFFECT FOR A PERIOD OF ONE YEAR
     5     AFTER WHICH TIME THE PROVISIONS OF CHAPTER 2 SHALL HAVE NO
     6     LEGAL EFFECT.
     7         (2)  SECTION 301 SHALL TAKE EFFECT IMMEDIATELY AND ITS
     8     PROVISIONS SHALL REMAIN IN FULL FORCE AND EFFECT FOR A PERIOD
     9     OF 18 MONTHS AFTER WHICH TIME SAID PROVISIONS SHALL HAVE NO
    10     LEGAL EFFECT.
    11         (3)  CHAPTER 4 SHALL TAKE EFFECT IN 18 MONTHS.
    12         (4)  ALL OTHER PROVISIONS OF THIS ACT SHALL TAKE EFFECT
    13     IMMEDIATELY.












    B10L42JLW/19770H0552B2328       - 56 -