PRIOR PRINTER'S NOS. 600, 1775, 2328,         PRINTER'S NO. 2503
        2464

THE GENERAL ASSEMBLY OF PENNSYLVANIA


HOUSE BILL

No. 552 Session of 1977


        INTRODUCED BY MESSRS. ITKIN, B. F. O'BRIEN, MISCEVICH, ABRAHAM,
           TRELLO, GAMBLE, McCALL, LEHR, SWEET AND J. L. WRIGHT,
           MARCH 7, 1977

        AS AMENDED ON SECOND CONSIDERATION, HOUSE OF REPRESENTATIVES,
           JANUARY 30, 1978

                                     AN ACT

     1  Providing for the regulation for energy conservation purposes of
     2     the construction of buildings, the establishment of a
     3     Building Energy Conservation COMMITTEE and a Board on          <--
     4     Variances, appeals and for penalties.

     5                         TABLE OF CONTENTS
     6  Chapter 1.  General Provisions
     7     Section 101.  Short title.
     8     Section 102.  Legislative findings and declaration of
     9                   purpose.
    10     Section 103.  Definitions.
    11  Chapter 2.  Energy Conservation Standards
    12     Section 201.  Provisions.
    13     Subchapter A.  Plans and Specifications
    14     Section 202.  Submission.
    15     Section 203.  Contents.
    16     Subchapter B.  Definitions Relating to Energy Conservation
    17                    Standards


     1     Section 204.  Definitions relating to standards.
     2     Subchapter C.  Building Envelope
     3     Section 205.  General provisions.
     4     Section 206.  Criteria for residential buildings.
     5     Section 207.  Other buildings.
     6     Section 208.  Air leakage.
     7     Subchapter D.  Warm Air Heating, Ventilating and Air
     8                    Conditioning Systems and Equipment
     9     Section 209.  General provisions.
    10     Section 210.  Design requirements.
    11     Section 211.  Cooling with outdoor air.
    12     Section 212.  Mechanical ventilation.
    13     Section 213.  Simultaneous heating and cooling.
    14     SECTION 214.  RECOVERED ENERGY.                                <--
    15     SECTION 215.  NEW ENERGY.
    16     Section 214 216.  Reheat systems.                              <--
    17     Section 215 217.  Dual duct and multizone systems.             <--
    18     Section 216 218.  Recooling systems.                           <--
    19     Section 217 219.  Multiple zones.                              <--
    20     Section 218 220.  Concurrent operation.                        <--
    21     Section 219 221.  Equipment performance requirements.          <--
    22     Section 220 222.  Duct insulation.                             <--
    23     Section 221 223.  System controls.                             <--
    24     Section 222 224.  Steam and hot water heating piping.          <--
    25     Subchapter E.  Plumbing Systems
    26     Section 223 225.  Purpose.                                     <--
    27     Section 224 226.  Fixtures.                                    <--
    28     Section 225 227.  Insulation.                                  <--
    29     Section 226 228.  Equipment.                                   <--
    30     Section 227 229.  Controls.                                    <--
    19770H0552B2503                  - 2 -

     1     Subchapter F.  Electrical Systems
     2     Section 228 230.  System requirements.                         <--
     3     Subchapter G.  Lighting
     4     Section 229 231.  Light power budget.                          <--
     5     Section 230 232.  Calculation methods.                         <--
     6     Section 231 233.  Building interiors.                          <--
     7     Section 232 234.  Building exteriors.                          <--
     8     Section 233 235.  Exceptions to criteria.                      <--
     9     Section 234 236.  Calculation procedure.                       <--
    10     Subchapter H.  Alternative Systems
    11     Section 235 237.  Performance alternative.                     <--
    12     Section 236 238.  Nondepletable sources.                       <--
    13     Section 237 239.  Documentation.                               <--
    14  Chapter 3.  Application of Standards:  Establishment of
    15              Committee and Penalties
    16     Section 301.  Modification of standards; criteria.
    17     Section 302.  Application of energy conservation standards.
    18     Section 303.  Energy conservation manual for buildings.
    19     Section 304.  Building Energy Conservation Committee.
    20     Section 305.  Certification.
    21     Section 306.  Variances.
    22     Section 307.  Building permits.
    23     Section 308.  Permits for use or occupancy.
    24     Section 309.  Failure to submit certification.
    25     Section 310.  Inspections.
    26     Section 311.  Appeals.
    27     Section 312.  Penalties.
    28     Section 313.  Enforcement.
    29  Chapter 4.  Department's Standard ADOPTION OF FUTURE STANDARDS    <--
    30     Section 401.  Adoption and promulgation of standards.
    19770H0552B2503                  - 3 -

     1     Section 402.  Effective date.
     2     The General Assembly of the Commonwealth of Pennsylvania
     3  hereby enacts as follows:
     4                             CHAPTER 1
     5                         GENERAL PROVISIONS
     6  Section 101.  Short title.
     7     This act shall be known and may be cited as the "Building
     8  Energy Conservation Act."
     9  Section 102.  Legislative findings and declaration of purpose.
    10     (a)  Findings.--The Legislature hereby determines that:
    11         (1)  Energy shortages in the domestic supply present far-
    12     reaching problems that promise to persist. These energy
    13     shortages affect the continued efficient operation of the
    14     Commonwealth's economy and social structure.
    15         (2)  It is the Commonwealth's responsibility to provide
    16     for energy conservation through regulation of design and
    17     construction standards.
    18         (3)  The Legislature intends, by this act, to respond to
    19     these shortages by devising a specific responsible energy
    20     conservation policy for building systems.
    21     (b)  Purpose.--The purpose of this act is to grant to the
    22  Commonwealth of Pennsylvania and direct it to exercise specific
    23  authority in building construction to assure that such
    24  construction is performed using materials and techniques that
    25  will provide for energy conservation in the future operation and
    26  maintenance of said structure.
    27  Section 103.  Definitions.
    28     The following words and phrases when used in this act shall
    29  have, unless the context clearly indicates otherwise, the
    30  meanings given to them in this section:
    19770H0552B2503                  - 4 -

     1     "Building."  Any structure that provides facilities or
     2  shelter for public assembly or for educational, business,
     3  mercantile, institutional, warehouse or residential occupancy,
     4  or industrial use including, but not limited to, those portions
     5  of factory and industrial occupancy such as office space except
     6  for:
     7         (1)  Buildings and structures or portions thereof whose
     8     peak design rate of energy usage is less than one watt per
     9     square foot or 3.4 BTU/hr per square foot of floor area for
    10     all purposes.
    11         (2)  Structures or those portions of structures used for
    12     manufacturing or processing and whose manufacturing or
    13     processing procedures require the use of substantial heat
    14     producing energy or cooling to create their product.
    15         (3)  Buildings which are neither heated nor cooled.
    16         (4)  Historic buildings.
    17     "Construction."  The erection, fabrication or renovation of a
    18  building.
    19     "Department."  The Pennsylvania Department of Labor and
    20  Industry except that for all units subject to the act of May 11,
    21  1972 (P.L.286, No.70), known as the "Industrialized Housing
    22  Act," and all buildings classified as Use Group R-3, herein,
    23  department means the Pennsylvania Department of Community
    24  Affairs.
    25     "Design."  Calculations and resultant drawings and
    26  specifications which are used for the construction of a
    27  building.
    28     "Historic building."  Any building determined by the State
    29  Historic Preservation Officer to meet the criteria for listing
    30  on the National Register of Historic Places but only to the
    19770H0552B2503                  - 5 -

     1  extent that compliance with this act would prevent preservation
     2  of the historic or architectural integrity of the building.
     3     "Licensed design professional."  A person licensed as an
     4  architect or professional engineer pursuant to the appropriate
     5  licensure act.
     6     "Life-cycle cost."  The cost of a building including its
     7  initial cost, the cost of the energy consumed over its economic
     8  life and the cost of its operation and maintenance.
     9     "Performance standards."  Parameters within which designers
    10  of buildings shall work. The specific practices that a designer
    11  employs shall not be prescribed as long as the result is within
    12  the parameters established by the standards.
    13     "Renovation."  (a)  The rehabilitation of an existing
    14  building which requires more than 25% of the gross floor area or
    15  volume of the entire building to be rebuilt; or
    16     (b)  any addition to an existing building: Provided, however,
    17  That the provisions of this act shall only apply to such
    18  addition and not to the entire building.
    19                             CHAPTER 2
    20                   ENERGY CONSERVATION STANDARDS
    21  Section 201.  Provisions.
    22     The following provisions regulate the design and construction
    23  of the exterior envelopes and selection of HVAC, service water
    24  heating, electrical distribution, and illumination systems and
    25  equipment required for the purpose of effective use of energy
    26  and shall govern the construction of all buildings, or portions
    27  thereof, as provided herein.
    28                            SUBCHAPTER A
    29                      PLANS AND SPECIFICATIONS
    30  Section 202.  Submission.
    19770H0552B2503                  - 6 -

     1     Plans, specifications, necessary computations and any changes
     2  thereto together with the necessary certification required by
     3  section 305 shall be submitted to indicate conformance with this
     4  chapter and other applicable chapters of this act.
     5  Section 203.  Contents.
     6     The plans and specifications shall show in sufficient detail
     7  all pertinent data and features of the building and the
     8  equipment and systems as herein governed, including but not
     9  limited to: exterior envelope component materials, U values of
    10  elements, R values of insulating materials, size and type of
    11  apparatus and equipment, equipment and system controls and other
    12  pertinent data to indicate conformance with the requirements
    13  herein.
    14                            SUBCHAPTER B
    15                      DEFINITIONS RELATING TO
    16                   ENERGY CONSERVATION STANDARDS
    17  Section 204.  Definitions relating to standards.
    18     The following words and phrases when used in this chapter
    19  shall have, unless the context clearly indicates otherwise, the
    20  meanings given to them in this section:
    21     "Coefficient of beam utilization" (CBU).  The ratio of the
    22  luminous flux (lumens) reaching a specified area directly from a
    23  floodlight or projector to the total beam luminous flux.
    24     "Coefficient of performance" (COP) - cooling. The ratio of
    25  the rate of net heat removal to the rate of total energy input,
    26  expressed in consistent units and under designated rating
    27  conditions.
    28     "Coefficient of performance" (COP) - heat pump, heating. The
    29  ratio of the rate of net heat output to the rate of total energy
    30  input, expressed in consistent units and under designated rating
    19770H0552B2503                  - 7 -

     1  conditions.
     2     The rate of net heat output shall be defined as the change in
     3  the total heat contents of the air entering and leaving the
     4  equipment not including supplementary heat.
     5     Total energy input shall be determined by combining the
     6  energy inputs to all elements, except supplementary heaters, of
     7  the heat pump, including, but not limited to, compressors,
     8  pumps, supply air fans, return air fans, outdoor air fans,
     9  cooling tower fans and the heating, ventilating and air
    10  conditioning system equipment control circuit.
    11     "Coefficient of utilization" (CU).  The ratio of the luminous
    12  flux (lumens) from a luminaire received on the work plane to the
    13  lumens emitted by the luminaire's lamps alone.
    14     "Color rendition."  General expression for the effect of a
    15  light source on the color. Appearance of objects in conscious or
    16  subconscious comparison with their color appearance under a
    17  reference light source.
    18     "Degree day, heating."  A unit, based upon temperature
    19  difference and time, used in estimating fuel consumption and
    20  specifying nominal heating load of a building in winter. For any
    21  one day, when the mean temperature is less than 65 F., there
    22  exist as many degree days as there are Fahrenheit degrees
    23  difference in temperature between the mean temperature for the
    24  day and 65 F.
    25     "Energy efficiency ratio" (EER).  The ratio of net cooling
    26  capacity in Btuh to total rate of electric input in watts under
    27  designated operating conditions.
    28     "Equivalent sphere illumination" (ESI).  The level of sphere
    29  illumination which would produce task visibility equivalent to
    30  that produced by a specific lighting environment.
    19770H0552B2503                  - 8 -

     1     "Exterior envelope."  The elements of a building which
     2  enclose conditioned spaces through which thermal energy may be
     3  transferred to or from the exterior.
     4     "Floodlighting."  A lighting system designated to light an
     5  area using projector type luminaires usually capable of being
     6  pointed in any direction.
     7     "Floor area, gross."  Gross floor area shall be the floor
     8  area within the perimeter of the outside walls of the building
     9  under consideration, without deduction for hallways, stairs,
    10  closets, thickness of walls, columns or other features.
    11     "Illumination."  The density of the luminous flux incident on
    12  a surface. It is the quotient of the luminous flux by the area
    13  of the surface when the latter is uniformly illuminated.
    14     "Light loss factor" (LLF).  A factor used in calculating the
    15  level of illumination after a given period of time and under
    16  given conditions. It takes into account temperature and voltage
    17  variations, dirt accumulation on luminaire and room surfaces,
    18  lamp depreciation, maintenance procedures and atmosphere
    19  conditions.
    20     "Luminaire."  A complete lighting unit consisting of a lamp
    21  or lamps together with the parts designed to distribute the
    22  light, to position and protect the lamps and to connect the
    23  lamps to the power supply.
    24     "Packaged terminal air conditioner."  A factory selected
    25  combination of heating and cooling components, assemblies or
    26  sections, intended to serve a room or zone.
    27     "Power."  In connection with machines, power is the time rate
    28  of doing work. In connection with the transmission of energy of
    29  all types, power refers to the rate at which energy is
    30  transmitted; in customary units, it is measured in watts (W) or
    19770H0552B2503                  - 9 -

     1  British thermal units per hour (Btuh) and in SI units is
     2  measured in watts (W).
     3     "Reflectance."  The ratio of the light reflected by a surface
     4  to the light falling upon it.
     5     "Reheat."  The application of sensible heat to supply air
     6  that has been previously cooled below the temperature of the
     7  conditioned space by either mechanical refrigeration or the
     8  introduction of outdoor air to provide cooling.
     9     "Residential buildings."  All buildings and structures or
    10  parts thereof shall be classified in the residential (R) use
    11  group in which families or households live, or in which sleeping
    12  accommodations are provided for individuals with or without
    13  dining facilities, excluding those that are classified as
    14  institutional buildings. Residential buildings shall be
    15  classified as follows:
    16     (1)  Use group R-1 structures.  This use group shall include
    17  all hotel and motel buildings, lodging houses, boarding houses
    18  and dormitory buildings arranged for the shelter and sleeping
    19  accommodation of more than 20 individuals.
    20     (2)  Use group R-2 structures.  This use group shall include
    21  all multiple-family dwellings having more than two dwelling
    22  units; and shall also include all dormitories, boarding and
    23  lodging houses arranged for shelter and sleeping accommodation
    24  by more than five and not more than 20 individuals.
    25     (3) Use group R-3 structures.  This use group shall include
    26  all buildings arranged for the use of one or two family dwelling
    27  units including not more than five lodgers or boarders per
    28  family.
    29     "Resistance, thermal" (R).  A measure of the ability to
    30  retard the flow of heat. The R value is the reciprocal of a heat
    19770H0552B2503                 - 10 -

     1  transfer coefficient, as expressed by U.  (R = 1/U).
     2     "Thermal transmittance" (U).  Overall coefficient of heat
     3  transmission or thermal transmittance (air to air) expressed in
     4  units of BTU per hour per square foot per degree F.  It is the
     5  time rate of heat flow. The U value applies to combinations of
     6  different materials used in series along the heat flow path and
     7  also to single materials that comprise a building section and
     8  include cavity air spaces and surface air films on both sides.
     9     "Thermal transmittance" (Uo).  Overall (average) heat
    10  transmission or thermal transmittance of a gross area of the
    11  exterior building envelope, expressed in units of BTU per hour
    12  per square foot per degree F.
    13     The Uo value applies to the combined effect of the time rate
    14  of heat flows through the various parallel paths, such as
    15  windows, doors and opaque construction areas, comprising the
    16  gross area of one or more exterior building components, such as
    17  walls, floor or roof/ceiling.
    18     "Thermostat."  An instrument which measures changes in
    19  temperature and controls devices for maintaining a desired
    20  temperature.
    21     "Veiling reflections."  Regular reflections superimposed upon
    22  diffuse reflections from an object that partially or totally
    23  obscure the details to be seen by reducing the contrast. This
    24  sometimes is called "reflected glare."
    25     "Work plane."  The plane at which work usually is done and at
    26  which the illumination is specified and measured. Unless
    27  otherwise indicated, this is assumed to be a horizontal plane 30
    28  in. (0.76 m) above the floor.
    29     "Zone."  A space or group of spaces within a building with
    30  heating or cooling requirements sufficiently similar so that
    19770H0552B2503                 - 11 -

     1  comfort conditions can be maintained throughout by a single
     2  controlling device.
     3                            SUBCHAPTER C
     4                         BUILDING ENVELOPE
     5  Section 205.  General provisions.
     6     (a)  Purpose of subchapter.--The intent of this subchapter is
     7  to provide minimum requirements for exterior envelope
     8  construction in the interest of energy conservation.
     9     In addition to the criteria set forth in this subchapter the
    10  proposed design may take into consideration the thermal mass of
    11  the building in considering energy conservation.
    12     (b)  Thermal performance.--All buildings and structures that
    13  are heated or mechanically cooled shall be constructed so as to
    14  provide the required thermal performance of the various
    15  components.
    16     The required thermal transmittance value (Uo) of any one
    17  component, such as roof/ceiling, wall or floor may be increased
    18  and the Uo value for other components decreased provided that
    19  the overall heat gain or loss for the entire building envelope
    20  does not exceed the total resulting from conformance to the
    21  required Uo values.
    22     (c)  Different requirements.--A building that is designed to
    23  be both heated and cooled shall meet the more stringent of the
    24  heating or cooling requirements of the exterior envelope as
    25  provided in this subchapter when requirements differ.
    26     (d)  Exterior walls.--For the purpose of this subchapter the
    27  gross area of exterior walls consists of all opaque wall areas,
    28  including foundation walls above grade, peripheral edges of
    29  floors, window areas including sash, and door areas, where such
    30  surfaces are exposed to outdoor air and enclose a heated or
    19770H0552B2503                 - 12 -

     1  mechanically cooled space.
     2     (e)  Roof assembly.--For the purpose of this subchapter a
     3  roof assembly shall be considered as all components of the
     4  roof/ceiling envelope through which heat flows, thereby creating
     5  a building transmission heat loss or gain, where such assembly
     6  is exposed to outdoor air and encloses a heated or mechanically
     7  cooled space.
     8     The gross area of a roof assembly consists of the total
     9  interior surface of such assembly, including skylights, exposed
    10  to the heated or mechanically cooled space.
    11     Where air ceiling plenums are employed, the roof or ceiling
    12  assembly shall:
    13         (1)  For thermal transmittance purposes not include the
    14     ceiling proper nor the plenum space as part of the assembly.
    15         (2)  For gross area purposes be based upon the interior
    16     face of the upper plenum surface.
    17  Section 206.  Criteria for residential buildings.
    18     (a)  Applicability.--The requirements herein shall apply to
    19  all buildings and structures or portions thereof of use groups
    20  R-1, R-2 and R-3 that are heated or mechanically cooled when not
    21  more than 3 stories or 40 feet in height.
    22     (b)  Walls.--The gross area of exterior walls above grade,
    23  including foundation walls, shall have a combined thermal
    24  transmittance value (Uo) not exceeding those specified in Table
    25  1.
    26                              Table 1
    27                 Maximum Allowable "Uo" Values for
    28                   Gross Exterior Wall Assemblies
    29                                       Detached         All other
    30     Annual heating degree days*   one & two family    residential
    19770H0552B2503                 - 13 -

     1                 4000                    0.25             0.31
     2                 5000                    0.23             0.29
     3                 6000                    0.22             0.27
     4                 7000                    0.20             0.26
     5     *As specified in Chapter 43 ASHRAE Handbook-Systems.
     6     (c)  Roof/ceiling.--The roof/ceiling assemblies shall have a
     7  combined thermal transmittance value (Uo) not to exceed 0.05
     8  except that roof/ceiling assemblies in which the finished
     9  interior surface is essentially the underside of the roof deck,
    10  such as a wooden cathedral ceiling, may have a "Uo" value not to
    11  exceed 0.08. These values presume no significant thermal
    12  transmission through framing members, skylights or other
    13  interruptions in the roof envelope. If such interruptions occur,
    14  calculations must be made showing conformance to the required
    15  "Uo" values.
    16     (d)  Floors over unheated spaces.--The floor of a heated or
    17  mechanically cooled space located over an unheated space shall
    18  have a combined thermal transmittance value (Uo) not to exceed
    19  0.08.
    20     (e)  Slab-on grade floors.--
    21         (1)  For slab-on grade floors, the perimeter of the floor
    22     shall be insulated with a material having a thermal
    23     resistance value (R) not less than those specified in Table
    24     2.
    25                              Table 2
    26             Minimum Allowable "R" Values of Perimeter
    27                Insulation for Slab-On Grade Floors
    28     Annual heating degree days      Heated slab     Unheated slab
    29                 4000*                   5.5             3.5
    30                 5000                    6.3             4.2
    19770H0552B2503                 - 14 -

     1                 6000                    7.0             4.9
     2                 7000                    7.8             5.5
     3     *Table values may be interpolated.
     4         (2)  The insulation shall extend downward from the top of
     5     the slab for a minimum distance of 24 inches or downward to
     6     the bottom of the slab then horizontally beneath the slab for
     7     a minimum total distance of 24 inches.
     8  Section 207.  Other buildings.
     9     (a)  Coverage.--The heating and cooling requirements herein
    10  shall govern all buildings and structures or portions thereof
    11  other than defined by section 206.
    12     (b)  Heating criteria for walls.--All buildings and
    13  structures that are heated shall have a combined thermal
    14  transmittance value (Uo) for the gross area of exterior walls
    15  not exceeding those specified in Table 3.
    16                              Table 3
    17                   Maximum Allowable "Uo" Values
    18                 for Gross Exterior Wall Assemblies
    19                                     3 stories or    More than
    20     Annual heating degree days     40 ft. or less  3 stories or
    21                                                       40 ft.
    22                 4000                    0.31            0.38
    23                 5000                    0.29            0.36
    24                 6000                    0.27            0.33
    25                 7000                    0.26            0.31
    26     (c)  Heating criteria for roof/ceiling.--All buildings and
    27  structures that are heated shall have combined thermal
    28  transmittance value (Uo) for roof/ceiling assemblies not
    29  exceeding those specified in Table 4.
    30                              Table 4
    19770H0552B2503                 - 15 -

     1                   Maximum Allowable "Uo" Values
     2                    for Roof/Ceiling Assemblies
     3     Annual heating degree days              Maximum Uo
     4             4000*                              0.092
     5             5000                               0.084
     6             6000                               0.076
     7             7000                               0.068
     8     *Table values may be interpolated.
     9     (d)  Heating criteria for floors over unheated spaces.--The
    10  floor of a heated space located over an unheated space shall
    11  have a thermal transmittance value (Uo) not exceeding 0.08.
    12     (e)  Heating criteria for slab-on grade floors.--For slab-on
    13  grade floors, the perimeter of the floor shall be insulated with
    14  a material having a thermal resistance value (R) not less than
    15  those specified in Table 5.
    16     The insulation shall extend downward from the top of the slab
    17  for a minimum distance of 24 inches or downward to the bottom of
    18  the slab then horizontally beneath the slab for a minimum total
    19  distance of 24 inches.
    20                              Table 5
    21             Minimum Allowable "R" Values of Perimeter
    22                Insulation for Slab-On Grade Floors
    23     Annual heating degree days      Heated slab    Unheated slab
    24                 4000*                   5.5             3.5
    25                 5000                    6.3             4.2
    26                 6000                    7.0             4.9
    27                 7000                    7.8             5.5
    28     *Table values may be interpolated.
    29     (f)  Cooling criteria for walls.--All buildings and
    30  structures that are mechanically cooled shall have an overall
    19770H0552B2503                 - 16 -

     1  thermal transfer value for the gross area of exterior walls not
     2  exceeding 33.5 BTU's per hour per square foot based on the
     3  following equation:
     4  OTTV = (Uw x Aw X TDEQ) + (Af x Sf x Sc) + (Uf x Af x Delta T)
     5                                     Ao
     6  OTTV = Overall thermal transfer value where:
     7    Uw = The thermal transmittance of all elements of the opaque
     8          wall area Btu/h. ft2.F (W/m2K)
     9    Aw = Opaque wall area, ft2 (m2)
    10    Uf = The thermal transmittance of the fenestration area
    11          Btu/h. ft2.F (W/m2K)
    12    Af = Fenestration area, ft2 (m2)
    13  TDEQ = Value given in the following table,F, (c):
    14                  TABLE FOR TEMPERATURE DIFFERENCE
    15     Wall Construction-mass per unit area        TDEQ
    16             LB/FT2          Kg/m2           F     C
    17             0-25            0-125           44  24.5
    18            26-40          126-195           37  21.0
    19            41-70          196-345           30  17.0
    20            71 and above   346 and above     23  13.0
    21     Weight of wall construction shall be determined from the
    22     1972 ASHRAE Handbook of Fundamentals, Chapter 22.
    23    Sc = Shading coefficient of the fenestration
    24  Delta T = Temperature difference between exterior and interior
    25         design conditions, F, for which the following
    26         temperatures shall apply:
    27                             Indoor          Outdoor
    28                               F  C
    29             Winter           72  22.0       97 1/2%*
    30             Summer           78  25.5        2 1/2%*
    19770H0552B2503                 - 17 -

     1     * Values from 1972 ASHRAE Handbook of
     2  Fundamentals, Chapter 33.
     3    SF = Solar factor value given Btu/h.ft2 (W/m2).
     4         (use 127 Btu/h.ft2)
     5    AO = Gross area of exterior walls, ft2 (m2).  The gross
     6         area of exterior walls consists of all opaque wall
     7         areas (including foundation walls, between floor span-
     8         drels, peripheral edges of floors, etc.), window
     9         areas (including sash), and door areas, where such
    10         surfaces are exposed to outdoor air and enclose a
    11         heated and/or mechanically cooled space (including
    12         intersticial areas between two such spaces).
    13  Note:  Where more than one type of wall and/or fenestration
    14         is used, the respective term or terms shall be expanded
    15         into sub-elements, as:
    16         (Uw x Aw x TDEQ) + (Uw2 x Aw2 x TDEQ2), etc.
    17     (g)  Cooling criteria for roof/ceilings.--All buildings and
    18  structures that are mechanically cooled shall have a combined
    19  thermal transmittance value (Uo) for roof/ceiling assemblies the
    20  same as specified in Table 4 for heating.
    21  Section 208.  Air leakage.
    22     (a)  Application.--The requirements of this section shall
    23  apply to all buildings and structures and apply only to those
    24  locations separating outdoor ambient conditions from interior
    25  spaces that are heated or mechanically cooled and are not
    26  applicable to separation of interior spaces from each other.
    27     (b)  Standard.--Compliance with the criteria for air leakage
    28  shall be determined by ASTM E-283, Standard Method of Test for
    29  Rate of Air Leakage through Exterior Windows, Curtain Walls and
    30  Doors, at a pressure differential of 1.567 lb/ft2 which is
    19770H0552B2503                 - 18 -

     1  equivalent to the effect of a 25 m.p.h. wind.
     2     (c)  Acceptance criteria.--The following criteria shall
     3  represent the maximum allowable air leakage:
     4         (1)  The air infiltration rate for windows shall not
     5     exceed 0.5 cfm per foot of sash crack.
     6         (2)  The air infiltration rate for sliding glass doors in
     7     residential buildings shall not exceed 0.5 cfm per square
     8     foot of door area.
     9         (3)  The air infiltration rate for swinging doors in
    10     residential buildings shall not exceed 1.25 cfm per square
    11     foot of door area.
    12         (4)  The air infiltration rate for swinging, revolving or
    13     sliding doors in other than residential buildings shall not
    14     exceed 11 cfm per lineal foot of door crack.
    15     (d)  Caulking and sealants.--Exterior joints around windows
    16  and door frames, between wall cavities and window or door
    17  frames, between wall and foundation, between wall and roof,
    18  between wall panels, at penetrations or utility services through
    19  walls, floors and roofs, and all other openings in the exterior
    20  envelope shall be caulked, gasketed, weatherstripped, or
    21  otherwise sealed.
    22                            SUBCHAPTER D
    23         WARM AIR HEATING, VENTILATING AND AIR CONDITIONING
    24                       SYSTEMS AND EQUIPMENT
    25  Section 209.  General provisions.
    26     This subchapter applies to air duct systems employing
    27  mechanical means for the movement of air used for warm air
    28  heating, ventilating, air conditioning systems, exhaust systems
    29  and combination heating and air conditioning systems, except
    30  that this subchapter shall not apply to systems for the removal
    19770H0552B2503                 - 19 -

     1  of flammable vapors or residues or to systems for conveying
     2  dust, stock or refuse by means of air currents. Heating,
     3  ventilating and air conditioning systems of all buildings and
     4  structures or portions thereof shall be designed and installed
     5  for efficient use of energy as herein provided. For special
     6  applications such as hospitals, laboratories, thermally
     7  sensitive equipment, computer rooms, and manufacturing
     8  processes, the design concepts and parameters shall conform to
     9  the requirements of the application at minimum energy levels.
    10  Section 210.  Design requirements.
    11     In determining design conditions for calculations under this
    12  section the following design temperatures shall apply:
    13         (1)  Outdoor design temperature shall be selected for
    14     listed locations in Chapter 33 of the ASHRAE Handbook of
    15     Fundamentals, from columns of 97 1/2% values for heating and
    16     2 1/2% values for cooling.
    17         (2)  Indoor design temperature shall be 70 degrees F. for
    18     heating and 78 degrees F. for cooling.
    19         (3)  Indoor design relative humidity for heating shall
    20     not exceed 30%. For cooling, the actual design relative
    21     humidity within the comfort envelope as defined in ASHRAE
    22     Standard 55-74 "Thermal Environmental Conditions for Human
    23     Occupancy" shall be selected for the minimum total heating,
    24     ventilating, and air conditioning system energy use.
    25  Section 211.  Cooling with outdoor air.
    26     (a)  Fan system design.--Each fan system shall be designed to
    27  use up to and including 100% of the fan system capacity for
    28  cooling with outdoor air automatically whenever its use will
    29  result in lower usage of energy than would be required under its
    30  normal operation.
    19770H0552B2503                 - 20 -

     1     (b)  Exceptions.--Cooling with outdoor air is not required
     2  under any one or more of the following conditions:
     3         (1)  Fan system capacity less than 5,000 Cfm or 134,000
     4     Btu/Hr total cooling capacity.
     5         (2)  The quality of the outdoor air is so poor as to
     6     require extensive treatment of the air.
     7         (3)  The need for humidification or dehumidification
     8     requires the use of more energy than is conserved by outdoor
     9     air cooling.
    10         (4)  The use of outdoor air cooling may affect the
    11     operation of other systems (such as return or exhaust air
    12     fans or supermarket refrigeration) so as to increase the
    13     overall energy consumption of the building.
    14         (5)  Internal/external zone heat recovery or other energy
    15     recovery is used.
    16         (6)  When all space cooling is accomplished by a
    17     circulating liquid which transfers space heat directly or
    18     indirectly to a heat rejection device such as a cooling tower
    19     without the use of a refrigeration system.
    20  Section 212.  Mechanical ventilation.
    21     Each mechanical ventilation system shall be equipped with a
    22  readily accessible means for either shut-off or volume reduction
    23  and shut-off when ventilation is not required.
    24  Section 213.  Simultaneous heating and cooling.
    25     Systems that employ both heating and cooling simultaneously
    26  in order to achieve comfort conditions within a space shall be
    27  limited to those situations where more efficient methods of
    28  heating and air conditioning cannot be effectively utilized to
    29  meet system objectives. Simultaneous heating and cooling by
    30  reheating or recooling supply air or by concurrent operation or
    19770H0552B2503                 - 21 -

     1  independent heating and cooling systems serving a common zone
     2  shall be restricted as specified herein.
     3  Section 214.  Recovered energy.
     4     Recovered energy, provided the new energy expended in the
     5  recovery process is less than the amount recovered, may be used
     6  for control of temperature and humidity. New energy is defined
     7  as energy, other than recovered, utilized for the purpose of
     8  heating or cooling.
     9  Section 215.  New energy.
    10     (a)  Prevention of excess humidity.--New energy may be used,
    11  when necessary, to prevent relative humidity from rising above
    12  60% for comfort control or to prevent condensation on terminal
    13  units or outlets.
    14     (b)  Control of temperature.--New energy may be used for
    15  control of temperature if minimized as specified in sections 216
    16  through 220.
    17  Section 216.  Reheat systems.
    18     Systems employing reheat and serving multiple zones, other
    19  than those employing variable air volume for temperature
    20  control, shall be provided with control that will automatically
    21  reset the system cold air supply to the highest temperature
    22  level that will satisfy the zone requiring the coolest air.
    23  Single zone reheat systems shall be controlled to sequence
    24  reheat and cooling.
    25  Section 217.  Dual duct and multizone systems.
    26     These systems shall be provided with control that will
    27  automatically reset the cold deck air supply to the highest
    28  temperature that will satisfy the zone requiring the coolest air
    29  and the hot deck air supply to the lowest temperature that will
    30  satisfy the zone requiring the warmest air.
    19770H0552B2503                 - 22 -

     1  Section 218.  Recooling systems.
     2     Systems in which heated air is recooled directly or
     3  indirectly, to maintain space temperature, shall be provided
     4  with control that will automatically reset the temperature to
     5  which the supply air is heated to the lowest level that will
     6  satisfy the zone requiring the warmest air.
     7  Section 219.  Multiple zones.
     8     For systems with multiple zones, one or more zones may be
     9  chosen to represent a number of zones with similar heating or
    10  cooling characteristics. A multiple zone heating, ventilating
    11  and air conditioning system that employs reheating or recooling
    12  for control of not more than 5,000 Cfm or 20% of the total
    13  supply air of the system, whichever is less, shall be exempt
    14  from the supply air temperature reset requirements of sections
    15  216 through 218.
    16  Section 220.  Concurrent operation.
    17     Concurrent operation of independent heating and cooling
    18  systems serving common spaces, and requiring the use of new
    19  energy for heating or cooling shall be minimized by one or both
    20  of the following:
    21         (1)  By providing sequential temperature control of both
    22     heating and cooling capacity in each zone.
    23         (2)  By limiting the heating energy input, through
    24     automatic reset control of the heating medium temperature (or
    25     energy input rate), to only that necessary to offset heat
    26     loss due to transmission and infiltration and, where
    27     applicable, to heat the ventilation air supply to the space.
    28  Section 221.  Equipment performance requirements.
    29     (a)  Application.--The requirements of this section apply to
    30  equipment and component performance for heating, ventilating and
    19770H0552B2503                 - 23 -

     1  air conditioning systems. Where equipment efficiency levels are
     2  specified, data furnished by the equipment supplier or certified
     3  under a nationally recognized certification program or rating
     4  procedure shall be used to satisfy these requirements.
     5     (b)  Systems equipment - electrical.--Heating ventilating and
     6  air conditioning systems equipment whose energy input in the
     7  cooling mode is entirely electric shall show a coefficient of
     8  performance (COP) and energy efficiency ratio (EER) not less
     9  than the values specified in Table 6. These requirements apply
    10  to, but are not limited to, unitary cooling equipment (air and
    11  water source); packaged air conditioners; and room air
    12  conditioners. These requirements do not apply to equipment used
    13  in areas having open refrigerated food display cases. For
    14  determining coefficient of performance (COP), the rate of net
    15  heat removal shall be defined as the change in the total heat
    16  contents of the air entering and leaving the equipment (without
    17  reheat). Total energy input shall be determined by combining the
    18  energy inputs to all elements of the equipment, including but
    19  not limited to, compressors, pumps, supply-air fans, cooling
    20  tower fans and the system equipment control circuit.
    21                              Table 6
    22       Minimum EER and COP for Electric Heating, Ventilating
    23               and Air Conditioning System Equipment
    24  Standard rating capacity                       EER     COP
    25  Under 65,000 Btu/hr (19,050 watts)             6.1     1.8
    26  65,000 Btu/hr (19,050 watts) and over          6.8     2.0
    27     (c)  Other system equipment.--Heat operated cooling equipment
    28  shall show a coefficient of performance (COP) in the cooling
    29  mode not less than the values specified in Table 7. These
    30  requirements apply to, but are not limited to, absorption,
    19770H0552B2503                 - 24 -

     1  engine-driven and turbine-driven equipment. The coefficient of
     2  performance (COP) is determined excluding the electrical
     3  auxiliary inputs.
     4                              Table 7
     5     Minimum COP for Heating, Ventilating and Air Conditioning
     6               System Heat Operated Cooling Equipment
     7         Heat source                             Minimum COP
     8  Direct fired (gas, oil)                            0.40
     9  Indirect fired (steam, hot water)                  0.65
    10     (d)  System components.--Heating, ventilating and air
    11  conditioning system components whose energy input in the cooling
    12  mode is entirely electric shall show a coefficient of
    13  performance (COP) and energy efficiency ratio (EER) not less
    14  than the values specified in Table 8. For determining
    15  coefficient of performance (COP), the rate of heat removal is
    16  defined as the difference in total heat contents of the water or
    17  refrigerant entering or leaving the component. Total energy
    18  input shall be determined by combining the energy inputs to all
    19  elements and accessories of the component, including but not
    20  limited to, compressors, internal circulating pumps, condenser-
    21  air fans, evaporative-condenser cooling heater pumps, purge, and
    22  the component control circuit.
    23                              Table 8
    24      Minimum COP for Electrically Driven Heating, Ventilating
    25               and Air Conditioning System Components
    26     Component    Condensing means   Air     Water     Evaporation
    27                                   ERR COP  EER COP     EER COP
    28  Self-contained    Centrifugal    7.5 2.2  12.9 3.8
    29  water chillers
    30                     Positive
    19770H0552B2503                 - 25 -

     1                   displacement    7.2 2.1  10.9 3.2
     2  Condenserless      Positive
     3  water chillers   displacement    8.9 2.6  10.9 3.2
     4  Compressor and
     5  condenser units    Positive
     6  65,000 Btu/hr.   displacement    7.8 2.3  11.3 3.3   11.3 3.3
     7  (19,050 watts)
     8  and over
     9     (e)  Heat pumps.--Heat pumps whose energy input is entirely
    10  electric shall show a coefficient of performance (COP), heating,
    11  not less than the values specified in Table 9.
    12                              Table 9
    13              Minimum COP for Heat Pumps, Heating Mode
    14  Source and outdoor temperature (degree F.)         Minimum COP
    15  Air source--47 DB/43 WB                               2.2
    16  Air source--17 DB/15 WB                               1.2
    17  Water source--60 entering                             2.2
    18     (f)  Supplementary heater.--The heat pump shall be installed
    19  with a control to prevent supplementary heater operation when
    20  the heating load can be met by the heat pump alone.
    21  Supplementary heater operation is permitted during transient
    22  periods, such as start-ups, following room thermostat setpoint
    23  advance, and during defrost. A two-stage room thermostat, which
    24  controls the supplementary heat on its second stage, shall be
    25  accepted as meeting this requirement. The cut-on temperature for
    26  the compression heating shall be higher than the cut-on
    27  temperature for the supplementary heat, and the cut-off
    28  temperature for the compression heating shall be higher than the
    29  cut-off temperature for the supplementary heat. Supplementary
    30  heat may be derived from any source of electric resistance
    19770H0552B2503                 - 26 -

     1  heating or combustion heating.
     2     (g)  Combustion heating equipment.--All gas and oilfired
     3  comfort heating equipment shall show a minimum combustion
     4  efficiency of 75% at maximum rated output. Combustion efficiency
     5  shall be determined in accordance with the ASHRAE Standard 90.
     6  Section 222.  Duct insulation.
     7     (a)  Insulation.--All duct systems, or portions thereof,
     8  exposed to nonconditioned spaces shall be insulated to provide a
     9  thermal resistance, excluding film resistance, of
    10             ti - to
    11         R = --------(hr) (sq.ft) (F)/BTU
    12               15
    13  where ti-to is the design temperature differential (absolute
    14  value) between the air in the duct and the surrounding air with
    15  the following exceptions. Duct insulation, except when needed to
    16  prevent condensation, is not required in any of the following
    17  cases:
    18         (1)  Where ti-to is 25 degrees F. or less.
    19         (2)  When the heat gain or loss of the ducts, without
    20     insulation, will not increase the energy requirements of the
    21     building.
    22         (3)  Exhaust air ducts.
    23         (4)  Supply or return air ducts installed in crawl spaces
    24     with insulated walls, basements or cellars in one and two-
    25     family dwellings.
    26     (b)  Vapor barriers.--Where required to prevent condensation,
    27  insulation with vapor barriers shall be installed in addition to
    28  insulation required above.
    29  Section 223.  System controls.
    30     (a)  Application.--All heating, ventilating and air
    19770H0552B2503                 - 27 -

     1  conditioning systems shall be provided controls as specified
     2  herein.
     3     (b)  Temperature.--Each heating, ventilating and air
     4  conditioning system shall be provided with at least one
     5  thermostat for the regulation of temperature. Each thermostat
     6  shall be capable of being set from 55 degrees F. to 75 degrees
     7  F. where used to control heating only and from 70 degrees F. to
     8  85 degrees F. where used to control cooling only. Where used to
     9  control both heating and cooling it shall be capable of being
    10  set from 55 degrees F. to 85 degrees F. and shall be capable of
    11  operating the system heating and cooling in sequence. It shall
    12  be adjustable to provide a temperature range of up to 10 degrees
    13  F. between full heating and full cooling, except as allowed in
    14  section 220.
    15     (c)  Humidity.--If a heating, ventilating and air
    16  conditioning system is equipped with a means for adding moisture
    17  to maintain specific selected relative humidities in spaces or
    18  zones, a humidistat shall be provided. This device shall be
    19  capable of being set to prevent new energy from being used to
    20  produce space relative humidity above 30% R.H.  Where a
    21  humidistat is used in a heating, ventilating and air
    22  conditioning system for controlling moisture removal to maintain
    23  specific selected relative humidities in spaces or zones, it
    24  shall be capable of being set to prevent new energy from being
    25  used to produce a space relative humidity below 60%.
    26     (d)  Temperature zoning.--
    27         (1)  In all buildings and structures of use group R-3, at
    28     least one thermostat for regulation of space temperature
    29     shall be provided for each separate heating, ventilating and
    30     air conditioning system. In addition, a readily accessible
    19770H0552B2503                 - 28 -

     1     manual or automatic means shall be provided to partially
     2     restrict or shut-off the heating or cooling input to each
     3     zone or floor, excluding unheated or uncooled basements and
     4     garages.
     5         (2)  In all buildings and structures of use group R-2,
     6     each individual dwelling unit shall be considered separately
     7     and shall meet the requirements for one and two-family
     8     dwellings above.
     9         (3)  In all buildings and structures other than use group
    10     R-3 and in spaces other than dwelling units in use group R-2,
    11     at least one thermostat for regulation of space temperature
    12     shall be provided for each separate heating, ventilating and
    13     air conditioning system and for each floor of the building.
    14     (e)  Set-back and shut-off.--
    15         (1)  In all buildings and structures, or portions thereof
    16     of use group R-3, the thermostat, or an alternate means such
    17     as a switch or a clock, shall provide a readily accessible,
    18     manual or automatic means for reducing the energy required
    19     for heating and cooling during periods of nonuse or reduced
    20     need.
    21         (2)  In all other buildings and structures, or portions
    22     thereof each heating, ventilating and air conditioning system
    23     shall be equipped with a readily accessible means of reducing
    24     the energy used for heating, ventilating and air conditioning
    25     during periods of nonuse or alternate uses of the building
    26     spaces or zones served by the system, such as with manually
    27     adjustable automatic timing devices, manual devices for use
    28     by operating personnel, or automatic control systems.
    29         (3)  Lowering thermostat set points to reduce energy
    30     consumption of heating systems shall not cause energy to be
    19770H0552B2503                 - 29 -

     1     expended to reach the reduced setting.
     2  Section 224.  Steam and hot water heating piping.
     3     (a)  Piping insulation.--All piping serving as part of a
     4  heating or cooling system installed to serve buildings and
     5  within buildings shall be thermally insulated as shown in Table
     6  10.
     7                              Table 10
     8                      Minimum Pipe Insulation
     9                                 Insulation thickness in inches
    10             Fluid                       for pipe sizes
    11  Piping  temperature
    12  system     range,   Runouts  1" and  1 1/4-  2 1/2-  5&   8" and
    13  types        F.     up to 2"  less     2       4     6    larger
    14  Heating systems
    15     Steam &
    16     hot water
    17  High pressure/
    18  temp       306-450   1 1/2     1 1/2    2    2 1/2  3 1/2  3 1/2
    19  Med. pressure/
    20  temp       251-305   1 1/2     1 1/2    2    2 1/2  3      3
    21  Low pressure/
    22  temp       201-250   1         1       1 1/2 1 1/2  2      2
    23  Low tem-
    24  perature   120-200    1/2       3/4     1    1      1      1 1/2
    25  Steam con-
    26  densate      Any     1         1        1    1 1/2  1 1/2  2
    27  (for feed
    28  water)
    29  Cooling systems
    30  Chilled
    19770H0552B2503                 - 30 -

     1  water,      40-55     1/2       1/2      3/4 1      1      1
     2  Refrigerant,
     3  or brine  Below 40   1         1       1 1/2  1 1/2 1 1/2  1 1/2
     4  Insulation thicknesses are based on insulation having thermal
     5  resistances in the range of 4.0 to 4.6 per inch of thickness on
     6  a flat surface at a mean temperature of 75 degrees F. Minimum
     7  insulation thickness shall be increased for materials having R
     8  values less than 4.0 or may be reduced for materials having R
     9  values greater than 4.6 per inch of thickness as follows:
    10     (b)  High thermal resistance.--For materials with thermal
    11  resistance greater than R=4.6, the minimum insulation thickness
    12  may be reduced as follows:
    13         4.6 x Table 10 Thickness    =   New Minimum Thickness
    14               Actual R
    15     (c)  Low thermal resistance.--For materials with thermal
    16  resistance less than R=4.0 the minimum insulation thickness
    17  shall be increased as follows:
    18         4.0 x Table 10 Thickness    =   New Minimum Thickness
    19               Actual R
    20  Piping insulation, except when needed to prevent condensation,
    21  is not required in any of the following cases:
    22         (1)  Piping installed within heating, ventilating and air
    23     conditioning equipment.
    24         (2)  Piping at temperatures between 55 degrees F. and 120
    25     degrees F.
    26         (3)  When the heat loss or heat gain of the piping,
    27     without insulation, does not increase the energy requirements
    28     of the building.
    29         (4)  Piping installed in basements or cellars in one and
    30     two-family dwellings.
    19770H0552B2503                 - 31 -

     1     (d)  Vapor barriers.--Where required to prevent condensation,
     2  insulation with vapor barriers shall be installed in addition to
     3  insulation required above.
     4                            SUBCHAPTER E
     5                          PLUMBING SYSTEMS
     6  Section 225.  Purpose.
     7     This subchapter sets forth provisions for design and
     8  equipment selection for energy conservation in service water
     9  heating systems.
    10  Section 226.  Fixtures.
    11     (a)  Lavatories.--Lavatories in restrooms of public
    12  facilities shall be equipped with self-closing outlet devices
    13  which limit the flow of hot water to a maximum of 0.5 Gpm,
    14  devices which limit the outlet temperature to a maximum of 110
    15  degrees F. and selfclosing valves which limit the quantity of
    16  hot water to a maximum of 0.25 gallons.
    17     (b)  Showers.--Showers used for other than safety reasons
    18  shall be equipped with flow control devices to limit total flow
    19  to a maximum of 3 Gpm per shower head.
    20  Section 227.  Insulation.
    21     (a)  Piping insulation.--Piping in required return
    22  circulation systems shall be insulated so that heat loss is
    23  limited to a maximum of 25 Btuh per square foot of external pipe
    24  surface for above ground piping and a maximum of 35 Btuh per
    25  square foot of external pipe surface for underground piping.
    26  Maximum heat loss shall be determined at a temperature
    27  differential equal to the maximum water temperature minus a
    28  design ambient temperature no higher than 65 degrees F. except
    29  that conformance with table 10 for "low temperature piping
    30  system" shall be deemed as complying with this section.
    19770H0552B2503                 - 32 -

     1     (b)  Tanks.--Unfired hot water storage tanks shall be
     2  insulated so that heat loss is limited to a maximum of 15 Btuh
     3  per square foot of external tank surface area. For purposes of
     4  determining this heat loss, the design ambient temperature shall
     5  be no higher than 65 degrees F.
     6  Section 228.  Equipment.
     7     (a)  Pump operation.--Circulating hot water systems shall be
     8  arranged so that the circulating pump can be conveniently turned
     9  off either automatically or manually when the hot water system
    10  is not in operation.
    11     (b)  Electric water heaters.--All automatic electric storage
    12  water heaters shall have a stand-by loss not exceeding 4 watts
    13  per square foot of tank surface area. The method of test of
    14  stand-by loss shall be as described in section 4.3.1 of ANSI
    15  C72.1 Household Automatic Electrical Storage-Type Water Heaters.
    16     (c)  Gas and oil-fired water heaters.--All gas and oil-fired
    17  automatic storage heaters shall have a recovery efficiency, ER,
    18  not less than 75% and a stand-by loss percentage S, not
    19  exceeding S=2.3+67/V where V=rated volume in gallons. The method
    20  of test of ER and S shall be as described in section 2.7 of ANSI
    21  Z21.10.3 Circulating Tank, Instantaneous and Large Automatic
    22  Storage Type Water Heaters, Approval Requirements for Gas Water
    23  Heaters.
    24  Section 229.  Controls.
    25     (a)  Temperature controls.--All hot water supply systems
    26  shall be equipped with automatic temperature controls capable of
    27  adjustments from the lowest to the highest acceptable
    28  temperature settings for the intended use.
    29     (b)  Shut down.--A separate switch shall be provided to
    30  terminate the energy supplied to electric hot water supply
    19770H0552B2503                 - 33 -

     1  systems. A separate valve shall be provided to turn off the
     2  energy supplied to the main burner of all other types of hot
     3  water supply systems.
     4                            SUBCHAPTER F
     5                         ELECTRICAL SYSTEMS
     6  Section 230.  System requirements.
     7     (a)  Power factor.--The power factor of the overall
     8  electrical distribution system in a building shall be not less
     9  than 90% under rated design installed load of the building,
    10  either by utilization equipment design or by the use of power
    11  factor corrective devices. The power factor corrective devices
    12  may be installed on individual equipment, rated greater than
    13  1,000 watts and switched therewith, regionally grouped, located
    14  at the service equipment or power factor correction achieved by
    15  other equivalent means. The choice among these corrective
    16  methods should be made based upon an engineering evaluation of
    17  each distribution system.
    18     (b)  Service voltage.--Where a choice of service voltage is
    19  available, the voltage resulting in the least energy loss shall
    20  be used.
    21     (c)  Voltage drop.--In any building, the maximum total
    22  voltage drop shall not exceed 3% in branch circuits or feeders,
    23  for a total of 5% to the farthest outlet based on steady state
    24  design load conditions.
    25     (d)  Lighting switching.--Switching shall be provided for
    26  each lighting circuit, or for portions of each circuit, so that
    27  the partial lighting required for custodial or for effective
    28  complementary use with natural lighting may be operated
    29  selectively.
    30     (e)  Separate metering.--In all multi-family dwellings
    19770H0552B2503                 - 34 -

     1  provisions shall be made to determine the electrical energy
     2  consumed by each tenant.
     3                            SUBCHAPTER G
     4                              LIGHTING
     5  Section 231.  Light power budget.
     6     A lighting power budget is the upper limit of the power to be
     7  available to provide the lighting needs in accordance with a
     8  given set of criteria and given calculation procedure.
     9  Section 232.  Calculation methods.
    10     The criteria specified below shall be utilized for
    11  computation of the lighting power budget. All calculations shall
    12  be in accordance with accepted engineering practice. When
    13  insufficient information is known about the specific use of the
    14  building space (e.g., number of occupants, space function,
    15  location of partitions), the budget shall be based on the
    16  apparent intended use of the building space.
    17  Section 233.  Building interiors.
    18     (a)  Procedure.--The allowable electric power for lighting
    19  shall be established by using the criteria and the calculation
    20  procedures specified in section 236. The value shall be based on
    21  the use for which the space within the building is intended and
    22  on efficient energy utilization.
    23     (b)  Illumination level criteria.--For the purpose of
    24  establishing a budget, levels of illumination shall be those
    25  listed in fig. 9-80 of the IES Lighting Handbook, and those
    26  levels shall be used as follows:
    27         (1)  For task lighting, the levels of illumination listed
    28     are for specific tasks. These levels are for the task areas
    29     defined in the IES Lighting Handbook or, where not defined,
    30     at all usable portions of task surfaces. In some cases, the
    19770H0552B2503                 - 35 -

     1     levels of illumination are listed for locations (e.g.,
     2     auditoriums). These levels are to be considered as average
     3     levels.
     4         (2)  For general lighting, in areas surrounding task
     5     locations, the average level of general lighting, for budget
     6     purposes only, shall be one-third the level for the tasks
     7     performed in the area but in no case less than 20-foot
     8     candles. Where more than one task level occurs in a space,
     9     the general level shall be one-third the weighted average of
    10     the specific task levels.
    11         (3)  For noncritical lighting, in circulation and seating
    12     areas, where no specific visual tasks occur, the average
    13     level of illumination shall be one-third of the average
    14     general lighting in the adjacent task spaces but in no case
    15     less than ten-foot candles.
    16         (4)  For the purpose of establishing a power budget, only
    17     lamp efficacies and coefficients of utilization (CU)
    18     specified in Table 11, shall be assumed.
    19  Section 234.  Building exteriors.
    20     (a)  Basis on use.--In exterior spaces, the lighting power
    21  budget shall be based on the use of which the space is intended
    22  (for task performance, safety, or security) and on efficient
    23  energy utilization.
    24     (b)  Criteria.--The same criteria as those for interior
    25  spaces apply for illumination levels and lighting systems with
    26  the addition of luminaires for flood lighting. For power budget
    27  purposes floodlighting shall be selected with luminaires having
    28  a greater percentage of their beam lumens restricted to the area
    29  to be lighted. Such luminaires are defined as those with at
    30  least the minimum efficiencies listed in the IES Lighting
    19770H0552B2503                 - 36 -

     1  Handbook.
     2     (c)  Facade lighting.--Facade lighting for budget purposes
     3  shall be no greater than 2% of the total interior load of the
     4  building.
     5     (d)  Calculation procedure.--In establishing a lighting power
     6  budget the following procedures shall be used:
     7         (1)  For overhead lighting the procedure specified in
     8     section 236 shall be followed, but using reflectances as
     9     found.
    10         (2)  For flood lighting the beam lumen method, as shows
    11     in the IES Lighting Handbook and a coefficient of beam
    12     utilization (CBU) of 0.75 shall be used for floodlighting
    13     calculations.
    14  Section 235.  Exceptions to criteria.
    15     (a)  Interiors.--The criteria of section 233 shall not apply
    16  to the following areas when calculating the load:
    17         (1)  Portions of residential occupancies except for
    18     kitchens, bathrooms, and laundry areas and public spaces
    19     including lobbies, halls, stairways, basement areas, and
    20     utility rooms.
    21         (2)  Residential type spaces similar to those stated in
    22     paragraph (1) in institutions, such as hospitals, hotels,
    23     funeral homes, churches, museums, etc.
    24         (3)  Theater auditoriums, entertainment and audiovisual
    25     presentations where the lighting is an essential technical
    26     element for the function performed.
    27     (b)  Exteriors.--The criteria of section 234 shall not apply
    28  to the following lamps and luminaries; however, their use shall
    29  be accounted for in the calculation of task lighting loads for
    30  specific tasks. The allowable load shall be based on the
    19770H0552B2503                 - 37 -

     1  luminary wattage to achieve the levels of illumination as
     2  covered in section 233 using a point calculation method given in
     3  the IES Lighting Handbook. The excepted lamps and luminaires are
     4  as follows:
     5         (1)  Luminaires for medical and dental purposes.
     6         (2)  Luminaires for highlighting applications, such as
     7     sculpture exhibits, art exhibits, and individual items of
     8     display merchandise.
     9         (3)  Luminaires for specialized lighting applications
    10     (color matching, where electrical interference cannot be
    11     tolerated, etc.).
    12     (c)  Control of reflectances.--The criteria of Table 11 shall
    13  not apply in spaces where it is impractical to control
    14  reflectances and where a dirty atmosphere cannot be avoided.
    15  Where this condition exists, the values for reflectances and
    16  light loss factors shall be those expected to be found and shall
    17  be approved by the department. The calculation shall make a note
    18  of this deviation.
    19  Section 236.  Calculation procedure.
    20     (a)  Illumination levels and areas.--To establish
    21  illumination levels and areas, the following procedure shall be
    22  used:
    23         (1)  Determine the visual tasks that are expected to be
    24     performed in each space and the number of planned work
    25     locations where tasks will be performed. If assumptions are
    26     made, their bases shall be indicated.
    27         (2)  Select the illumination level, in foot-candles for
    28     those expected tasks in accordance with section 233(b)(1).
    29         (3)  Calculate total task areas to be illuminated to the
    30     same level by multiplying the number of work locations by 50
    19770H0552B2503                 - 38 -

     1     square feet per work location. (Total task areas shall not
     2     exceed actual total space area). If actual task area is
     3     greater than 50 square feet the actual area shall be used. If
     4     special task lighting or localized lighting is to be
     5     employed, use the actual task areas and point calculation
     6     procedures.
     7         (4)  Calculate the level of general lighting by
     8     multiplying the task lighting level by one-third, where there
     9     is only one task level, or by taking one-third of the sum of
    10     the products of the task levels as provided for in paragraph
    11     (2) and their areas as provided for in paragraph (3) divided
    12     by the total task areas.
    13         (5)  Calculate the level of noncritical lighting.
    14     (b)  Lighting system data.--To establish lighting system
    15  data, the following shall be used:
    16         (1)  Light source and luminaire types to use.
    17         (2)  Lamp lumens per watt and luminaire coefficients of
    18     utilization for room and luminaire mounting height
    19     dimensions. Luminaire CUs shall be selected from the IES
    20     Lighting Handbook. In all cases, no luminaire shall have a CU
    21     for RCR = 1 of less than that given in Table 11 lamp
    22     efficacies for the appropriate space.
    23     (c)  Allowable wattage.--To establish allowable wattage, the
    24  following shall be used:
    25         (1)  Using data from subsection (b), the illumination
    26     levels and areas determined in subsection (a), and the
    27     criteria of Table 11 on Reflectance, calculate the allowable
    28     wattages using the lumen method.
    29         (2)  Calculate the total space wattage by adding the
    30     task, general and noncritical lighting loads.
    19770H0552B2503                 - 39 -

     1         (3)  Add the wattage of luminaires allowed in section
     2     235(b).
     3                              Table 11
     4     (a)  Lamp efficacies.--The following are initial lumen output
     5  per watt input, including ballast losses:
     6                 Application                             Lumens
     7                                                        per Watt
     8     Where moderate color rendition is appropriate         55
     9     Where good color rendition is appropriate             40
    10     Where high color rendition is appropriate,
    11     spaces are less than 50 square feet or where
    12     use of low wattage High Intensity Discharge
    13     (HID) lamps under 250 W or fluorescent
    14     lamps under 40 W is appropriate                       25
    15     (b)  Luminary coefficients of utilization (CU).--Coefficients
    16  of utilization (CUs) are to be for luminaires for use in the
    17  types of spaces listed below, and those luminaires shall have a
    18  CU of no less than that listed below (for each type space) for a
    19  Room Cavity Ratio (RCR) of 1 and reflectances as in (c).
    20                 Space Use                           Minimum CU
    21                                                    (at RCR = 1)
    22     For spaces with tasks subjected to veiling
    23     reflections where design levels of
    24     illumination are listed in terms of
    25     equivalent sphere illumination (ESI) and
    26     where visual comfort is important.                  0.55
    27     For spaces without tasks, or with tasks
    28     not subjected to veiling reflections, but
    29     where visual comfort is important.                  0.63
    30     For spaces without tasks and where visual
    19770H0552B2503                 - 40 -

     1     comfort is not a criterion                          0.70
     2     (c)  Other criteria; reflectances.--For interior spaces, the
     3  following initial cavity and surface reflectances shall be
     4  assumed:
     5     Ceiling cavity reflectance              80%
     6     Wall reflectance                        50%
     7     Floor cavity reflectance                20%
     8  Light Loss Factor.  A light loss factor (LLF) of 0.70 shall be
     9  used.
    10                            SUBCHAPTER H
    11                        ALTERNATIVE SYSTEMS
    12  Section 237.  Performance alternative.
    13     Alternative building systems and equipment design may be
    14  approved by the department when they can be shown to have energy
    15  consumption not greater than that of a similar building with
    16  similar forms of energy requirements, designed in accordance
    17  with the provisions of this act or when they can be shown to
    18  have energy consumption not greater than that which shall be
    19  established by the department with the approval of the Building
    20  Energy Conservation Committee, for the purposes of this section.
    21  Section 238.  Nondepletable sources.
    22     When such alternative systems utilize solar, geothermal, wind
    23  or other nondepletable energy sources for all or part of their
    24  energy sources, such nondepletable energy supplied to the
    25  building shall be excluded from the total energy chargeable to
    26  the proposed alternative design.
    27  Section 239.  Documentation.
    28     Proposed alternative designs, submitted as requests for
    29  exception to the standard design criteria, must be accompanied
    30  by an energy analysis prepared in accordance with the ASHRAE
    19770H0552B2503                 - 41 -

     1  Standard 90-75.
     2                             CHAPTER 3
     3              APPLICATION OF STANDARDS: ESTABLISHMENT
     4                     OF COMMITTEE AND PENALTIES
     5  Section 301.  Modification of standards; criteria.
     6     The department, with the approval of the Building Energy
     7  Conservation Committee established pursuant to section 304,
     8  after one or more public hearings, may recommend to the General
     9  Assembly modifications to the energy conservation standards
    10  contained in Chapter 2 hereof. Any recommended modification to
    11  the energy conservation standards shall meet the following
    12  criteria:
    13         (1)  It shall be consistent with the latest and most
    14     effective technology.
    15         (2)  It shall not be in conflict with existing safeguards
    16     for public health and safety.
    17         (3)  It shall be economically feasible as determined by
    18     life-cycle-cost procedures.
    19         (4)  It shall be sufficiently stringent to effect a
    20     significant savings of energy resources.
    21         (5)  It shall be a performance standard for the design of
    22     buildings and systems within buildings to assure maximum
    23     practical conservation of energy.
    24         (6)  Consideration shall be given to building and energy
    25     standards promulgated by national and other state
    26     governmental agencies, private organizations and any other
    27     available energy data, as well as the total energy allocation
    28     approach.
    29  Section 302.  Application of energy conservation standards.
    30     The energy conservation standards contained herein or as
    19770H0552B2503                 - 42 -

     1  promulgated by the department with the approval of the Building
     2  Energy Conservation Committee shall apply to new buildings or to
     3  renovations on which actual construction and/or design has not
     4  commenced prior to their effective dates.
     5  Section 303.  Energy conservation manual for buildings.
     6     (a)  Production of manual.--Concurrent with the adoption of
     7  the energy conservation codes required by this act, the
     8  department shall produce an energy conservation manual for use
     9  by designers, builders, and contractors of residential and
    10  nonresidential buildings. This manual shall contain the
    11  established standards and accepted practices. The manual shall
    12  be furnished upon request to members of the public at a price
    13  sufficient to cover the cost of printing.
    14     (b)  Review of manual.--The manual shall be reviewed by the
    15  department and the Building Energy Conservation Committee at
    16  least annually and shall be updated as significant new energy
    17  conservation information becomes available.
    18  Section 304.  Building Energy Conservation Committee.
    19     (a)  Composition of committee.--In order to further the
    20  coordinated and effective administration of this act, there is
    21  hereby established a Building Energy Conservation Committee. It
    22  shall consist of at least 25 members and no more than 35
    23  members, the membership of which shall be appointed by the
    24  Governor and shall include a representative of each of the
    25  following entities or their successors:
    26         (1)  Department of Education.
    27         (2)  Governor's Energy Council.
    28         (3)  Department of General Services.
    29         (4)  Department of Labor and Industry.
    30         (5)  Department of Community Affairs.
    19770H0552B2503                 - 43 -

     1         (6)  Pennsylvania Builders Association.
     2         (7)  Pennsylvania Associated Builders and Contractors,
     3     Inc.
     4         (8)  Pennsylvania Building Officials Conference.
     5         (9)  Mechanical Contractors Association of America.
     6         (10)  Pennsylvania Chamber of Commerce.
     7         (11)  General Contractors Association of Pennsylvania.
     8         (12)  Pennsylvania Society of Architects.
     9         (13)  Pennsylvania Society of Professional Engineers.
    10         (14)  American Society of Heating, Refrigerating and Air
    11     Conditioning Engineers, Inc..
    12         (15)  Pennsylvania Gas Association.
    13         (16)  Pennsylvania Electric Association.
    14         (17)  Industrialized Housing Manufacturers Association.
    15         (18)  Thermal Insulation Manufacturers Association.
    16         (19)  Pennsylvania Building Trades Council.
    17         (20)  Representatives of such other agencies and
    18     organizations or individuals as the Governor may find are
    19     necessary and proper to carry out the purposes of the
    20     committee including, but not limited to, labor organizations,
    21     financial and lending institutions, and consumer groups.
    22     (b)  Powers and duties.--In addition to the powers and duties
    23  enumerated in this act, the Building Energy Conservation
    24  Committee shall:
    25         (1)  Be responsible for the regular exchange of
    26     information and plans regarding building energy conservation,
    27     for the development, review and approval of proposed and
    28     existing standards, guidelines, regulations, and manuals.
    29         (2)  Elect from its members a Board on Variances.
    30     (c)  Expenses.--The members of the committee shall not
    19770H0552B2503                 - 44 -

     1  receive any compensation for their services but shall be
     2  reimbursed for their actual and necessary expenses incurred in
     3  the performance of their duties. Provided, however, when acting
     4  on matters concerning variances members of the Board on
     5  Variances shall receive $50 per day plus their actual and
     6  necessary expenses.
     7  Section 305.  Certification.
     8     (a)  Compliance with act.--It shall be the duty of the
     9  architect retained in connection with the design, construction
    10  or renovation of a building to certify the drawings,
    11  specifications and other data showing compliance with the
    12  provisions of this act, except as provided in subsection (d). If
    13  the building is subject to the provisions of the act of April
    14  27, 1927 (P.L.465, No.299), referred to as the Fire and Panic
    15  Act, the certification required hereunder shall be submitted on
    16  a form with the application for plan approval under the said
    17  Fire and Panic Act.
    18     (b)  Inspection.--Each architect, other licensed design
    19  professional retained by the owner in lieu of an architect, or
    20  the architect's designee shall make periodic inspections of the
    21  building progression to insure compliance with this act, except
    22  as provided in subsection (d).
    23     (c)  Final certification.--Each architect or other licensed
    24  design professional retained by the owner in lieu of an
    25  architect shall make a final certification of every completed
    26  building showing compliance with the provisions of this act,
    27  except as provided in subsection (d).
    28     (d)  Certification by builder.--If an architect or other
    29  licensed design professional is not retained in connection with
    30  the design, construction or renovation of a building, it shall
    19770H0552B2503                 - 45 -

     1  be the responsibility of the builder or owner, if he is the
     2  builder, to perform the inspections and certification required
     3  by this section.
     4  Section 306.  Variances.
     5     (a)  Requests.--Any request for a variance from the energy
     6  conservation standards contained herein shall be made to the
     7  Board on Variances of the Building Energy Conservation
     8  Committee.
     9     (b)  Criteria.--A variance shall be granted only if it is
    10  found that:
    11         (1)  compliance with the provisions of this act would
    12     result in extreme hardship to the owner; and
    13         (2)  the granting of such variance would not result in a
    14     significant increase in the energy usage of the building.
    15  Section 307.  Building permits.
    16     Any building permit issued by the Commonwealth or any of its
    17  political subdivisions shall have printed upon its face notice
    18  that the provisions of this act must be complied with.
    19  Section 308.  Permits for use or occupancy.
    20     Before any building or structure hereafter constructed or
    21  renovated shall be used or opened for occupancy, the owner
    22  thereof shall notify the department of the completion of the
    23  building and submit the necessary certification therewith.
    24  Within 10 days of receipt of the certification the department
    25  shall forward notice of receipt of such certification to the
    26  owner. No permit for use or occupancy shall be granted until
    27  such submission has been made. No building official of the
    28  Commonwealth or any of its political subdivisions shall issue a
    29  permit until he has received proof of compliance. Provided,
    30  however, that if the certification is forwarded to the
    19770H0552B2503                 - 46 -

     1  department by certified mail with a return receipt requested and
     2  the owner does not receive the notice of receipt of
     3  certification provided for by this section within the time
     4  provided herein, in such case, any building official of the
     5  Commonwealth or any of its political subdivisions shall issue a
     6  permit for use or occupancy upon presentation of the return
     7  receipt by the owner and said building official shall notify the
     8  department that he has issued the same.
     9  Section 309.  Failure to submit certification.
    10     Whenever the owner of any building or structure shall fail to
    11  notify the department of the completion of the building and to
    12  submit the necessary certification and shall nevertheless
    13  proceed with the use or occupancy of the building, the
    14  department or the political subdivision shall serve notice on
    15  the said owner that he is in violation of this act and order him
    16  to comply therewith.
    17  Section 310.  Inspections.
    18     The department may inspect within two years of the date of
    19  completion of construction or renovation any building
    20  constructed or renovated after the effective date of this act to
    21  determine compliance with the provisions of this act, provided
    22  at least 30 days notice has been given to the owner.
    23  Section 311.  Appeals.
    24     Review of any decisions rendered under the provisions of this
    25  act shall be brought in the court of common pleas of the county
    26  wherein the building is situated. Such review shall be limited
    27  to determining whether any such decision was arbitrary and
    28  capricious.
    29  Section 312.  Penalties.
    30     (a)  Violations of act.--Any person who shall willfully or
    19770H0552B2503                 - 47 -

     1  negligently violate any of the provisions of this act, or the
     2  rules and regulations or the orders for the enforcement of the
     3  said provisions or rules and regulations issued by duly
     4  authorized officers of the department or who shall hinder, delay
     5  or interfere with any officer charged with the enforcement of
     6  this act in the performance of his duty, shall, upon conviction
     7  thereof, be punished by a fine of not more than $300 and costs.
     8  In the event of violation of more than one provision of this
     9  act, the violation of each provision shall be deemed a separate
    10  and distinct offense for the purposes of this section.
    11     (b)  Institution of proceedings.--Prosecutions for violations
    12  of this act or the rules and regulations of the department may
    13  be instituted by the Secretary of Labor and Industry or the
    14  Secretary of Community Affairs, or under his directions by an
    15  authorized representative of the department. Upon conviction
    16  after a hearing, the sentences provided in this act shall be
    17  imposed and shall be final unless an appeal be taken in the
    18  manner prescribed by law.
    19     (c)  Disposition of fines.--All fines collected under this
    20  act shall be forwarded to the department who shall pay the same
    21  into the State Treasury for the use of the Commonwealth.
    22     (d)  False certification.--Any architect or other licensed
    23  design professional who willfully provides a false certification
    24  for any building subject to the provisions of this act shall be
    25  subject to the suspension or revocation of his license by the
    26  State Board of Examiners of Architects or other applicable State
    27  licensing board.
    28  Section 313.  Enforcement.
    29     (a)  Applicability.--The provisions of this act shall apply
    30  to every building enumerated in this act, except buildings owned
    19770H0552B2503                 - 48 -

     1  by the Federal Government, including buildings owned in whole or
     2  in part by the Commonwealth or any political subdivision
     3  thereof, and shall be enforced by the Secretary of Labor and
     4  Industry or by the Secretary of Community Affairs, by and
     5  through his authorized representatives.
     6     (b)  Powers of officers.--For the purpose of enforcing the
     7  provisions of this act, all the officers charged with its
     8  enforcement shall have the power to enter any of the buildings
     9  enumerated in this act, and no person shall hinder or delay, or
    10  interfere with any of the said officers in the performance of
    11  his duty, nor refuse any pertinent information necessary to
    12  determine whether the provisions of this act and the rules and
    13  regulations herein provided for, are or will be complied with.
    14                             CHAPTER 4
    15                    ADOPTION OF FUTURE STANDARDS
    16  Section 401.  Adoption and promulgation of standards.
    17     The department, with the approval of the Building Energy
    18  Conservation Committee, shall, after one or more public
    19  hearings, adopt and publish energy conservation standards for
    20  all buildings covered by this act in accordance with the
    21  provisions of the act of July 31, 1968 (P.L.769, No.240), known
    22  as the "Commonwealth Documents Law." The purpose of such
    23  standards is to reduce wasteful or uneconomic consumption of
    24  energy by balancing the cost of energy procurement against the
    25  cost of energy-conserving building practices. The energy
    26  conservation standards shall meet the following criteria:
    27         (1)  They shall be consistent with the latest and most
    28     effective technology.
    29         (2)  They shall not be in conflict with existing
    30     safeguards for public health and safety.
    19770H0552B2503                 - 49 -

     1         (3)  They shall be economically feasible as determined by
     2     life-cycle-cost procedures.
     3         (4)  They shall be sufficiently stringent to effect a
     4     significant savings of energy resources.
     5         (5)  They shall be a performance standard for the design
     6     of buildings and systems within buildings to assure maximum
     7     practical conservation of energy.
     8         (6)  Consideration shall be given to building and energy
     9     standards promulgated by national and other State
    10     governmental agencies, private organizations and any other
    11     available energy data, as well as the total energy allocation
    12     approach.
    13  Section 402.  Effective date.
    14     This act shall take effect as follows:
    15         (1)  Chapter 2 shall take effect in six months and shall
    16     remain in full force and effect for a period of one year
    17     after which time the provisions of Chapter 2 shall have no
    18     legal effect.
    19         (2)  Section 301 shall take effect immediately and its
    20     provisions shall remain in full force and effect for a period
    21     of 18 months after which time said provisions shall have no
    22     legal effect.
    23         (3)  Chapter 4 shall take effect in 18 months.
    24         (4)  All other provisions of this act shall take effect
    25     immediately.




    B10L42JLW/19770H0552B2503       - 50 -